AL-602-03-902 EnoPuck BASIC
Product manual
Offset
Size
24
4
28
1
29
2
31
1
Table 12: EnOcean transmit data
Note:
The EnoPuck BASIC sends EnOcean telegrams according to the following rules:
•
Immediately when the PIR or VIB sensors detect a motion or vibration event.
The bits are coded as follows:
Bit 7
Bit 6
Motion
Reserved
detected
Table 13: EnOcean data, PIR and vibration message coding
Bit 7:
1 = motion detected
Bit 6:
Reserved
Bit 5:
Reserved
Bit 4:
Reserved
Bit 3:
Reserved
Bit 2:
Reserved
Bit 1:
1 = Vibration detected;
Bit 0:
1 = PIR motion detected;
© DEUTA Controls GmbH
06.07.2021
Technical data might change
Page 12 of 19
Bitrange
Data
DB0.7...DB0.4
Not used (= 0)
DB0.3
LRN bit
DB0.2...DB0.1
Not used (= 0)
DB0.0
Supply
voltage
available
Bit 5
Bit 4
Reserved
Reserved
0 = No vibration detected;
0 = PIR motion detected;
Paffrather Str. 140, 51465 Bergisch Gladbach
Hauptstraße 76, 32479 Hille
info@deuta-controls.de;
Shortcut
Description
LRNB
LRN Bit
SVA
Supply
voltage
availability
at DB_3
Bit 3
Bit 2
Reserved
Reserved
Tel.:+49 2202 285 57- 61
Tel: +49 5734 51466 - 0
www.deuta-controls.dnet
Fax:+49 5734 51466 - 28
Valid
Scale
Unit
range
0: Teach-in telegram
1: Data telegram
1: Supply voltage is
supported
Bit 1
Bit 0
Vibration
PIR
sensor
Need help?