SECTION FIVE – Equipment Start-Up Checklist
Fan coil units must be filled with water before operating the circulator. The circulator bearings are water
lubricated and should not be allowed to operate dry. Filling the system properly will result in immediate
lubrication of the bearings.
Receiving and Inspection
Unit received undamaged
Unit received complete as ordered
"Furnish only" parts accounted for
Unit arrangement/hand correct
Unit structural support complete and correct
Handling and Installation
Mounting grommets/isolators used
Unit mounted level and square
Proper access provided for unit and accessories
Proper electrical service provided
Proper over-current protection provided
Proper service switch/disconnect provided
Proper chilled water line size to unit
Proper hot water line size to unit
All services to unit in code compliance
All shipping screws and braces removed
Unit protected from dirt and foreign matter
Heating Connections
Protect valve package components from heat
Mount valve packages
Connect field piping to unit
Pressure test all piping for leaks
Install drain line and traps, as required
Insulate all piping, as required
Install drip lip under piping, as required
IMPORTANT
Ductwork Connections
Install ductwork, fittings and grilles, as required
Flexible duct connections at unit
Proper supply and return grille type and size
Control outside air for freeze protection
Insulate all ductwork, as required
Electrical Conditions
Refer to unit wiring diagram
Connect incoming power service or services
Install and connect "furnish only" parts
Unit Start-up
General visual unit and system inspection
Check for proper fan rotation
Record electrical supply voltage
Check all wiring for secure connections
Close all unit isolation valves
Flush water systems
32