INTRODUCTION OF THE AHU CONTROL PANEL
Settings are applied via the service menu

SERVICE MENU

0-10V external control (0-10V hood,remote monitoring) select the deployment
SENSOR 1 "EXT" or SENSOR 2 "EXT"
External control controls the basic speed , replaces the fan speed set in the menu.
Out-of-home, overpressure and boost are in use normally.
The main screen shows the fan speed at REMOTE CONTROL and
below of it is the speed of the inlet fan.
FAN SPEED PRIORITY
Fan speed preselection is performed from the control panel service menu.
Inlet and outlet fans can be individually adjusted for five different speeds with fan speeds of 20-100%
BOOSTING FROM THE COOKER HOOD WITH CONTACT TIP INFORMATION.
Intensification time settings 0 and 5...120 min. In 0 position with different switch
pre-data.
Intensification limit settings 1...4 (the air impellers higher than basic speed)
SEPARATE FIREPLACE SWITCH OR PRESSURE COMPENSATION
Overpressure duration specification 0 and 5...20 min. In 0 position with different
switch pre-data.
Overpressure limit regulation 1...4 (inlet air impeller higher than outlet air impeller)
REGULATION of the INLET AIR TEMPERATURE
Inlet air temperature range 5...30
can be adjusted via SETTINGS menu
CO
AND/or RH SENSORS ACTIVATION
2
CO
AND HUMIDY PERCENTAGE SETTING
2
Note: set the sensor on in the settings menu
MODBUS MENU
Check the separate Modbus manual
THE CHANGES OF THE SERVICE MENU SETTINGS ALWAYS HAVE TO BE SAVED
SETTINGS
o
C,
Note: swipe right at
the top of the screen
External control fan speeds
0-2V
2-5V
5-7V
7-9V
9-10V fan 5
.
9
fan 0
fan 2
fan 3
fan 4
DEFAULT SETTINGS
1. 30 %
2. 40 %
3. 60 %
4. 80 %
5. 100 %
Factory setting
10 min
3
Factory setting
10 min
1
Factory setting
17
C
o