Haes ESPRIT-Argus Installation, Commissioning & Operating  Manual

Haes ESPRIT-Argus Installation, Commissioning & Operating Manual

Addressable fire control panel
Table of Contents

Advertisement

Quick Links

NTRODUCTION
This manual covers
programming and
the ESPRiT Argus Fire Alarm Control Panels for One to Two Loop and One to Four Loop
Haes Systems Ltd, Unit 3, Horton Industrial Park, West Drayton, Uxbridge, UB7 8JD
Model Number
Control and indicating equipment for fire detection and fire alarm systems for buildings.
Output to fire alarm devices, dependency type 'A', test condition
Power supply equipment for fire detection and fire alarm systems for buildings.
ESPRIT-ARGUS
Haes Systems Ltd declare that the products identified below conform to the essential requirements
specified in the Construction Products Regulation CPR305/2011/EU.
ADDRESSABLE FIRE
In addition, the product complies with the following:
CONTROL PANEL
Low Voltage Directive 2014/35/EC, EN60950-1: 2006 Safety of information technology equipment
Electromagnetic Compatibility Directive 2014/30/EC EN61000-6-3:2007 + A1:2011 Emissions,
INSTALLATION,
Class B EN50130-4: 2011 +A1:2014 Immunity, Product Family Standard.
This product has been designed to comply with the requirement of the low voltage safety and the
COMMISSIONING &
EMC directives. Failure to follow the instructions may compromise its adherence to this standard.
OPERATING MANUAL
This manual covers the installation, programming and commissioning of
the one to two loop and one to four loop Esprit-Argus Addressable fire
Esprit – A Analogue Addressable
European Standard EN54-2 : 1997 + A1 : 2006
Provided Options (with requirements):
European Standard EN54-4 : 1998
alarm control panels
0832
18
0832-CPR-2176
the installation,
commissioning of
CPR Number

Advertisement

Table of Contents
loading

Summary of Contents for Haes ESPRIT-Argus

  • Page 1 European Standard EN54-4 : 1998 Power supply equipment for fire detection and fire alarm systems for buildings. ESPRIT-ARGUS Haes Systems Ltd declare that the products identified below conform to the essential requirements specified in the Construction Products Regulation CPR305/2011/EU. ADDRESSABLE FIRE...
  • Page 2: Introduction

    European Standard EN54-4: 1998 Power supply equipment for fire detection and fire alarm systems for buildings. Haes Technologies Ltd declare that the products identified above conform to the essential requirements specified in the Construction Products Regulation CPR305/2011/EU. In addition, the product complies with the following:...
  • Page 3 ESPRIT-Argus User Manual INTRODUCTION List of optional functions with requirements: EN54-2: 1997 + A1 Control and indicating equipment for fire detection and fire alarm systems for buildings Provided options: 7.8 Outputs to Fire Alarm Devices 7.9 Fire alarm routing 7.11 Delays to outputs 7.12 Dependencies on more than one alarm signal (Type A, B &...
  • Page 4: Safety

    ESPRIT-Argus User Manual SAFETY SAFETY IMPORTANT NOTICE PLEASE READ THIS MANUAL CAREFULLY BEFORE HANDLING THE EQUIPMENT AND OBSERVE ALL ADVICE GIVEN WITHIN IT. THIS PARTICULARLY APPLIES TO THE PRECAUTIONS NECESSARY TO AVOID ELECTRO-STATIC DISCHARGE Important Safety Notes The panel is safe to operate provided it has been installed in compliance with the manufacturer’s instructions and used in accordance with this manual.
  • Page 5: Cautions

    ESPRIT-Argus User Manual SAFETY Cautions Equipment Guarantee This product has been manufactured in conformance with the requirements of all applicable EU Council Directives and is not guaranteed unless the complete system is installed and commissioned in accordance with the laid down national standards by an approved and competent person or organisation.
  • Page 6: Table Of Contents

    ESPRIT-Argus User Manual TABLE OF CONTENTS TABLE OF CONTENTS INTRODUCTION ........................1 SAFETY ..........................3 IMPORTANT NOTICE ....................... 3 Important Safety Notes ...................... 3 Disclaimer ......................... 3 Warnings ........................3 Cautions ........................4 TABLE OF CONTENTS ......................5 PRODUCT OVERVIEW ......................9 General Description of the Equipment ................
  • Page 7 ESPRIT-Argus User Manual TABLE OF CONTENTS Safety ..........................20 ESD Precaution ......................20 Installing the system ......................21 General ........................21 Environment ......................... 21 Mounting the cabinet ....................21 Mains connections ....................... 22 Connecting the batteries ....................22 Battery charging voltage checks .................. 23 Battery Charging Voltage Calibration ................
  • Page 8 ESPRIT-Argus User Manual TABLE OF CONTENTS CONFIGURING THE SYSTEM ................... 36 Dependency Modes (False Alarm Management) ............. 36 Accessing the Menu Structure ..................37 Learn System ........................38 USER MENU ........................41 USER MENU: DISABLE ....................42 DISABLE MENU: 1: REMOVE ALL DISABLEMENTS ..........42 DISABLE MENU: 2: GENERAL ................
  • Page 9 ESPRIT-Argus User Manual TABLE OF CONTENTS CONFIG Menu Breakdown ..................66 Report Menu........................72 REPORT Menu: EVENTS .................... 73 REPORT EVENTS Menu: ALARM ................73 Report EVENTS Menu: FAULT ................74 Report EVENTS Menu: DISABLE................75 Report EVENTS Menu: TEST .................. 76 REPORT EVENTS Menu: OTHER ................
  • Page 10: Product Overview

    The ESPRiT-Argus Addressable fire control panel is designed to be intuitive and flexible for the fire alarm engineer to programme and incorporates a large 240 x 64-pixel graphical display, with an easy-to-navigate menu system, which uses simple discernible icons in each section.
  • Page 11: Cabinet (One To Two Loops)

    ESPRIT-Argus User Manual PRODUCT OVERVIEW Cabinet (One to Two Loops) 350 mm 85.00 363.00 mm Approved Document Ref: UI-ESA-01 Issue 1.0...
  • Page 12: Cabinet (One To Four Loops)

    ESPRIT-Argus User Manual PRODUCT OVERVIEW Cabinet (One to Four Loops) 450 mm 105 mm Approved Document Ref: UI-ESA-01 Issue 1.0...
  • Page 13: Circuit Boards

    ESPRIT-Argus User Manual PRODUCT OVERVIEW Circuit Boards TPC2879-206 PSU PCB & TPC2889-206 Argus Loop Card PCB Approved Document Ref: UI-ESA-01 Issue 1.0...
  • Page 14: Circuit Description/Function

    ESPRIT-Argus User Manual PRODUCT OVERVIEW Circuit Description/Function TPC2879-206 PSU PCB PSU (+ -) Monitored 29.0VDC input from power supply module 28V / 0V (+ -) 28V output, fused at 500mA Class Change Input (-IP) Class Change switch (–ve) input, which causes the common and loop sounders to operate.
  • Page 15: Technical Specification

    ESPRIT-Argus User Manual PRODUCT OVERVIEW Technical Specification General Specification Enclosure Steel IP30. Epoxy powder coated Interpon Radon, silver grey. Cabling Fire resistant screened cable, minimum size 1 mm . Max cable length 1 Km (20 Ohm). FireBurn, FP200 or equivalent (max capacitance 1uF, max inductance 1 millihenry).
  • Page 16: Electrical Specification Inputs & Outputs - Tpc2879-206 Psu Pcb

    ESPRIT-Argus User Manual PRODUCT OVERVIEW Battery type YUASA NP7-12 (12V 7.0Ah)/ NP18-12 (12V 17.2Ah) Battery fuse Maximum quiescent current Approx. 180mA at 28V For 1 to 2 loops system Approx. 250mA at 28V For 1 to 4 loops system Electrical Specification Inputs & Outputs – TPC2879-206 PSU PCB Terminal capacity 0.5mm...
  • Page 17: Design Considerations

    ESPRIT-Argus User Manual DESIGN CONSIDERATIONS DESIGN CONSIDERATIONS System Design and Planning Note: This guide is intended as an aid to designers and installers of fire detection systems. It is NOT to be used as a substitute to BS5839 which should be read in full.
  • Page 18: Beacons

    ESPRIT-Argus User Manual DESIGN CONSIDERATIONS and 1000Hz. The maximum sound level should not be greater than 120dB(A) at any normally accessible point. This may be reduced to 60dB(A) in stairways, enclosures up to and specific points of limited extent. For areas where people are sleeping, sounder devices should produce a minimum 75dB(A) at the bed-head with all doors shut.
  • Page 19 ESPRIT-Argus User Manual DESIGN CONSIDERATIONS This should be secure from unauthorised operation and be marked ‘FIRE ALARM’. The mains supply must be exclusive to the fire panel. As an alternative to a switched fused spur, an appropriately fused double pole isolating device may be used providing it meets the appropriate national wiring regulations.
  • Page 20: Typical Sounder Circuit Conventional System Schematic

    ESPRIT-Argus User Manual DESIGN CONSIDERATIONS Typical Sounder Circuit Conventional System Schematic 6K8 END OF LINE RESISTOR Approved Document Ref: UI-ESA-01 Issue 1.0...
  • Page 21: Installation

    ESPRIT-Argus User Manual INSTALLATION INSTALLATION Safety The product must be installed, commissioned and maintained for operation in accordance with the instructions and the applicable wiring codes of practice and national standard regulations for fire systems appropriate to the country and location of the installation.
  • Page 22: Installing The System

    ESPRIT-Argus User Manual INSTALLATION Installing the system General Care should be taken with regards to avoiding the close proximity of high voltage cables or areas likely to induce electrical interference. Earth links should be maintained on all system cables and grounded in the control panel. The detection and sounder circuit cabling is classed as extra low voltage and must be segregated away from mains voltage.
  • Page 23: Mains Connections

    ESPRIT-Argus User Manual INSTALLATION Mains connections Note: All connections must be carried out in accordance with local requirements and regulations. Do not connect the mains supply to the panel until you are fully conversant with the layout and features of the equipment.
  • Page 24: Battery Charging Voltage Checks

    ESPRIT-Argus User Manual INSTALLATION Battery charging voltage checks The battery charging voltage is factory calibrated to 27.3VDC +/- 0.2V at 20 C. This should not normally require adjustment. Where battery problems are experienced, the following information should be considered. a) If a battery is disconnected from the charger, no voltage will appear on the output leads or terminals, due to intelligent battery controls.
  • Page 25: Sounders/Output Circuits

    ESPRIT-Argus User Manual INSTALLATION • The Main Menu will become available for operation • On the Main Menu, use Left/Right arrow keys to move cursor box to Report menu • Press Enter ✓ key to select the Report menu •...
  • Page 26: Relay Outputs

    ESPRIT-Argus User Manual INSTALLATION Relay Outputs The panel is equipped with two relay outputs, which activate on Fault and/or Fire Alarm conditions respectively, by default. The relays can be programmed to turn OFF or ON in Continuously Mode or in Pulsing Mode (1s ON and 1s OFF) and can be set to operate as General Alarm, Evacuation Alarm, Fails Safe, Fault and Can be Silenced.
  • Page 27: Operating Instructions

    ESPRIT-Argus User Manual OPERATING INSTRUCTIONS OPERATING INSTRUCTIONS Panel Control and Indications Control Panel The Control Panel contains: • LCD Display screen • 5 button control keypad • Up/down/left/right arrow keys and enter (✓) key curser control keypad • Panel status LED indicators •...
  • Page 28: Keypads

    ESPRIT-Argus User Manual OPERATING INSTRUCTIONS Keypads Use to resound the alarms after they have been silenced. Can also be used to invoke full evacuation. Resound Alarms Use to silence the sounders during an alarm condition. Silence Alarms Resets the panel back to standby mode.
  • Page 29: Status Led Indicators

    ESPRIT-Argus User Manual OPERATING INSTRUCTIONS Status LED Indicators LED Name LED ON LED Pulsing Detection Zones: Indicates alarm condition in zone. Zones 1 - 18 Indicates mains and/or battery Supply Healthy: supply is present. General Fire: Indicates panel is in alarm condition Indicates panel is in the unsilenced that has been silenced.
  • Page 30 ESPRIT-Argus User Manual OPERATING INSTRUCTIONS Description Type Sub-type Altair Thermal High-Temperature Detector Thermal Differential Sensor Thermal static-differential Sensor Vega Call Point Input Module On/Off Vega Output Module Vega Analogue Input Module Vega Multi-Module (404) Vega Multi-Module (422) Vega Multi-Module (602)
  • Page 31 ESPRIT-Argus User Manual OPERATING INSTRUCTIONS Description Type Sub-type Special Gasses Sensor Petrol Fumes Sensor Carbon Monoxide Sensor Hydrogen Sensor LPG Sensor Propane Sensor Ammonia Fumes Sensor High Toxicity Ammonia Fumes Sensor Acetylene Sensor Excess Oxygen Quantity Sensor Defective Oxygen Quantity Sensor...
  • Page 32: User Controls

    ESPRIT-Argus User Manual OPERATING INSTRUCTIONS User Controls Three levels of control, with programmable code entry, are available on the panel: • General User (Access level 1) • Authorised User (Access level 2) • Engineer (Access level 3) (CONFIG Mode). In General User (Access level 1) mode; most of the keypad controls are inactive, to protect the system from unauthorised operation.
  • Page 33: Available Functions

    ESPRIT-Argus User Manual OPERATING INSTRUCTIONS Note: If the Activate Controls key is in the On position, the keypad will remain active. Note: It is not possible to remove the key, whilst it is in the On position. Note: The padlock symbol is shown on the LCD screen, to the right of the Time and Date indication.
  • Page 34: Available Functions

    ESPRIT-Argus User Manual OPERATING INSTRUCTIONS Note: The Access level 3 code 3333 is the factory default. Available Functions The functions that can be performed at Access level 3 are: • Set the panel to automatically learn what internal cards are fitted within the panel, and what remote units (connected via the RS-485 Peripheral BUS) and devices (detectors, sounders, call-points, etc.) are connected to the internal cards.
  • Page 35: Panel Alarm Conditions

    ESPRIT-Argus User Manual OPERATING INSTRUCTIONS Panel Alarm Conditions Fire Alarm Condition The display shows location/origin of the fire alarm and the total number of zones in a fire alarm condition. If two or more zones enter the fire alarm condition, the display also shows the location of the last zone to enter a fire alarm condition.
  • Page 36 ESPRIT-Argus User Manual OPERATING INSTRUCTIONS o Fire alarms can still be detected and controlled by the panel. • Power Supply Board o System Fault LED pulsing o General Fault LED pulsing o Power Supply Fault LED pulsing o Fault relay activated o Mains or battery power will still operate the panel.
  • Page 37: Configuring The System

    ESPRIT-Argus User Manual CONFIGURING THE SYSTEM CONFIGURING THE SYSTEM When the system is installed and is ready to be commissioned, configure as follows: • Use the CONFIG MENU > CONFIG PANEL sub-menu > LEARN option, to enable the panel to automatically learn what internal cards, external devices (detectors, sounders, etc.), and Peripheral BUS (P-BUS) RSUs are connected in the system.
  • Page 38: Accessing The Menu Structure

    ESPRIT-Argus User Manual CONFIGURING THE SYSTEM Dependency ‘C’ will apply the following sequence: 1. The first detector will indicate at the control panel but not activate the sounders. 2. The panel will not activate a full fire condition unless a second detector is activated in the same or any other zone.
  • Page 39: Learn System

    ESPRIT-Argus User Manual CONFIGURING THE SYSTEM On the LCD screen, the box surrounding the menu icon is the cursor; this can be navigated through the menu options by using the Left/Right arrow keys to select required menu option and then pressing the ✓ key.
  • Page 40 ESPRIT-Argus User Manual CONFIGURING THE SYSTEM • The system will perform a learning routine, in order to acknowledge the Internal Cards installed, the External Devices connected to it, and the P-BUS (Peripheral BUS, which is achieved using a RS485 network) connection. The following...
  • Page 41 ESPRIT-Argus User Manual CONFIGURING THE SYSTEM • Press return key again o P-BUS: The LEARN PANEL sub-menu will display a list containing all 16 RSUs and show if they are connected or not, using the P-BUS, indicated by PRESENT or NOT PRESENT:...
  • Page 42: User Menu

    ESPRIT-Argus User Manual CONFIGURING THE SYSTEM USER MENU Accessible from the MAIN MENU (Access level 2), the USER MENU and its subsequent sub-menus are used to set-up the panel ready for configuration. The USER MENU sub- menus are: • USER o DISABLE ▪...
  • Page 43: User Menu: Disable

    ESPRIT-Argus User Manual CONFIGURING THE SYSTEM USER MENU: DISABLE Used to enable/disable outputs, devices and Zones: • On the MAIN MENU, use Left/Right arrow keys to move cursor box to USER menu icon • Press ✓ key to select the USER MENU •...
  • Page 44: Disable Menu: 2: General

    ESPRIT-Argus User Manual CONFIGURING THE SYSTEM DISABLE MENU: 2: GENERAL To enable or disable SOUNDERS/LOOP OUTPUTS/FIRE Relay/FARE OUTPUT/FAULT Relay/FWRE OUTPUT: • On the MAIN MENU, use Left/Right arrow keys to move cursor box to USER menu icon • Press ✓ key to select the USER MENU.
  • Page 45: Disable Menu: 4: Zones

    ESPRIT-Argus User Manual CONFIGURING THE SYSTEM • Press ✓ key to open the LOOP DEVICES sub-menu, the following DISABLE MENU will be displayed: LOOP: 1 – 2 or 1 – 4 DISABLE MENU DEVICE: 001 - 240 TYPE: nnn – device type in numerical form (e.g. 012 – wall sounder, refer to...
  • Page 46: User Menu: Test

    ESPRIT-Argus User Manual CONFIGURING THE SYSTEM • Press return key to return to MAIN MENU. USER MENU: TEST In TEST MODE, the devices in the Zone(s) in test (i.e. detectors, call points, etc.) can be activated and the panel will automatically reset, enabling the panel to be tested by one person.
  • Page 47: Test Menu: Settings

    ESPRIT-Argus User Manual CONFIGURING THE SYSTEM still activate Fire Alarms in the standard way. The Test Mode amber LED will not illuminate. • Use the Left/Right arrow keys to select one of the above options and then press ✓ key to activate it.
  • Page 48: User Menu: Delay

    ESPRIT-Argus User Manual CONFIGURING THE SYSTEM USER MENU: DELAY If, during configuration of the panel, DELAY DEPENDENCY is set to DELAY (for false alarm management, refer to CONFIG PANEL Menu: OPTIONS instructions), the DELAY sub- menu allows for the DELAY DEPENDENCY to be enabled/disabled, at Access Level 2: •...
  • Page 49: User Menu: Time&Date

    ESPRIT-Argus User Manual CONFIGURING THE SYSTEM USER MENU: TIME&DATE The TIME&DATE sub-menu is used to set the system clock and to set the period where the system clock is moved forward 1 hour, to reflect local Daylight Savings Time (DST): •...
  • Page 50: User Menu: Lamp Test

    ESPRIT-Argus User Manual CONFIGURING THE SYSTEM • To change the Set DayLight Savings sub-menu options, to match local start and end of DST: o Use Left/Right arrow keys to move between the various fields (indicated by underline curser). Use Up/Down arrow keys to toggle to the required setting for each field: Monday –...
  • Page 51: User Menu: Contrast

    ESPRIT-Argus User Manual CONFIGURING THE SYSTEM o Second, the following Detection Zone LEDs will come on, at the same time, for a couple of seconds: (Loop 1 – 2) • Zone 1 to Zone 9 • Zone 10 to Zone 18 o Third, the following Detection Zone LEDs will come on, at the same time, for a couple of seconds (Loop 3 –...
  • Page 52: User Menu Breakdown

    ESPRIT-Argus User Manual CONFIGURING THE SYSTEM USER MENU Breakdown Approved Document Ref: UI-ESA-01 Issue 1.0...
  • Page 53 ESPRIT-Argus User Manual CONFIGURING THE SYSTEM Approved Document Ref: UI-ESA-01 Issue 1.0...
  • Page 54 ESPRIT-Argus User Manual CONFIGURING THE SYSTEM Approved Document Ref: UI-ESA-01 Issue 1.0...
  • Page 55 ESPRIT-Argus User Manual CONFIGURING THE SYSTEM Approved Document Ref: UI-ESA-01 Issue 1.0...
  • Page 56: Config Menu

    ESPRIT-Argus User Manual CONFIGURING THE SYSTEM CONFIG Menu Accessible from the MAIN MENU (Access level 2); the CONFIG Menu (Access level 3), and its subsequent sub-menus, is used to configure the panel and its attached devices. The sub- menus available are: •...
  • Page 57: Config Menu: Panel

    ESPRIT-Argus User Manual CONFIGURING THE SYSTEM Note: Access level 3 Menu will deactivate after 30 sec if not used. CONFIG Menu: PANEL Under the PANEL sub-menu, the following sub-menus are available to configure the panel controls and outputs: • LEARN •...
  • Page 58 ESPRIT-Argus User Manual CONFIGURING THE SYSTEM • On completion of the learning routine, the LEARN PANEL sub-menu will display all the internal cards, devices and RSUs that were found available: o INTERNAL CARDS: The LEARN PANEL menu will display the internal cards found connected, or not, indicated by YES or NO: •...
  • Page 59: Config Panel Menu: Tones

    ESPRIT-Argus User Manual CONFIGURING THE SYSTEM • Press the return key to finally accept. A short acknowledgement sound will be present. Note: The status of the RSUs may be changed, using the Up/Down arrow keys and the ✓ key to change between PRESENT or NOT PRESENT. However, any differences between detected devices and changes made by user, will result in a System Fault condition.
  • Page 60: Config Panel Menu: Options

    ESPRIT-Argus User Manual CONFIGURING THE SYSTEM • The ZONES SETTINGS for the selected Zone will be presented: ZONE 01 – 18 or 01 – 36 ZONE SETTINGS 1: ZONE NAME: DEVICE ZONE 001 – 018 or 001 - 036 2: ZONE DEPENDENCY: ENABLED/DISABLED •...
  • Page 61: Config Panel Menu: Default

    ESPRIT-Argus User Manual CONFIGURING THE SYSTEM in place of the event counts (A nn F nn D nn O nn) on any of the EVENT reports (ALARM, FAULT, DISABLE and OTHER). Note: If SOUNDER TWO FWRE (option 3) is set to YES, faults on the SOUNDER TWO circuit will NOT be indicated (all other fault indications are unaffected).
  • Page 62: Config Menu: Devices

    ESPRIT-Argus User Manual CONFIGURING THE SYSTEM CONFIG Menu: DEVICES Under the PANEL sub-menu, the following sub-menus are available, to configure external devices (call points, detectors, sounders, relays, etc.) connected to the system: • DEVICES • SOUNDERS • RELAY CONFIG DEVICES Menu: DEVICES To configure Device Name, Zone, output, tones, volume, etc.
  • Page 63: Config Devices Menu: Sounders

    ESPRIT-Argus User Manual CONFIGURING THE SYSTEM • Next press ✓ key again and a list containing information about the selected device will be displayed as follows (or, if finished, press return key to return to CONFIG DEVICES menu): 1: DEVICE NAME: name 2: ZONE: 001 –...
  • Page 64: Config Devices Menu: Relay

    ESPRIT-Argus User Manual CONFIGURING THE SYSTEM • The sounders information, available under SOUNDERS sub-menu will be presented as follows: SOUNDERS <PSU SNDR ONE/TWO> 1: IN ALARM: OFF/PULSING/CONTINUOUS 2: IN EVAC OFF/PULSING/CONTINUOUS 3: IN DELAY: OFF/PULSING/CONTINUOUS 4: IN ALERT: OFF/PULSING/CONTINUOUS 5: IN CLASS CHANGE: OFF/PULSING/CONTINUOUS 6: SOUNDER CAN BE SILENCED: YES/NO •...
  • Page 65: Config Menu: P-Bus

    ESPRIT-Argus User Manual CONFIGURING THE SYSTEM CONFIG Menu: P-BUS If RSU(s) have been added or removed from the P-BUS, since the last CONFIG LEARN routine, the RUSs on the P-BUS can be configured from the P-BUS menu: • From the CONFIG MENU, highlight P-BUS option and then press ✓ key in order to gain access to it.
  • Page 66: Config Menu: Psu

    ESPRIT-Argus User Manual CONFIGURING THE SYSTEM CONFIG Menu: PSU To configure Power Supply Unit settings, access the PSU menu: • From the CONFIG Menu, highlight PSU option and then press ✓ key in order to gain access to it. •...
  • Page 67: Config Menu Breakdown

    ESPRIT-Argus User Manual CONFIGURING THE SYSTEM CONFIG Menu Breakdown Approved Document Ref: UI-ESA-01 Issue 1.0...
  • Page 68 ESPRIT-Argus User Manual CONFIGURING THE SYSTEM Approved Document Ref: UI-ESA-01 Issue 1.0...
  • Page 69 ESPRIT-Argus User Manual CONFIGURING THE SYSTEM Approved Document Ref: UI-ESA-01 Issue 1.0...
  • Page 70 ESPRIT-Argus User Manual CONFIGURING THE SYSTEM Approved Document Ref: UI-ESA-01 Issue 1.0...
  • Page 71 ESPRIT-Argus User Manual CONFIGURING THE SYSTEM Approved Document Ref: UI-ESA-01 Issue 1.0...
  • Page 72 ESPRIT-Argus User Manual CONFIGURING THE SYSTEM Approved Document Ref: UI-ESA-01 Issue 1.0...
  • Page 73: Report Menu

    ESPRIT-Argus User Manual CONFIGURING THE SYSTEM Report Menu From the REPORT menu, on the Main Menu, the following sub-menus are available: • REPORT o EVENTS: ▪ ALARM ▪ FAULT ▪ DISABLE ▪ TEST ▪ OTHER o STATUS: ▪ LOOP ▪...
  • Page 74: Report Menu: Events

    ESPRIT-Argus User Manual CONFIGURING THE SYSTEM REPORT Menu: EVENTS From the REPORT Menu EVENTS sub-menu, reports on the number and type of Alarm, Fault, Disablements, etc. events can be displayed: REPORT EVENTS Menu: ALARM To get ALARM events information: •...
  • Page 75: Report Events Menu: Fault

    ESPRIT-Argus User Manual CONFIGURING THE SYSTEM Report EVENTS Menu: FAULT To get FAULT events information: • On the MAIN MENU, use Left/Right arrow keys to move cursor box to REPORT icon • Press ✓ key to select the REPORT menu.
  • Page 76: Report Events Menu: Disable

    ESPRIT-Argus User Manual CONFIGURING THE SYSTEM Report EVENTS Menu: DISABLE To get DISABLE events information on system disablements: • On the Main Menu, use Left/Right arrow keys to move cursor box to Report menu • Press ✓ key to select the Report menu.
  • Page 77: Report Events Menu: Test

    ESPRIT-Argus User Manual CONFIGURING THE SYSTEM Report EVENTS Menu: TEST To get TEST events information on system test modes enabled: • On the Main Menu, use Left/Right arrow keys to move cursor box to Report menu • Press ✓ key to select the Report menu.
  • Page 78: Report Events Menu: Other

    ESPRIT-Argus User Manual CONFIGURING THE SYSTEM REPORT EVENTS Menu: OTHER To obtain a report on OTHER events information (any events not covered under ALARM, FAULT or DISABLE – e.g. Non-Fire alarm events): • On the MAIN MENU, use Left/Right arrow keys to move cursor box to REPORT menu icon •...
  • Page 79: Report Menu: Status

    ESPRIT-Argus User Manual CONFIGURING THE SYSTEM REPORT Menu: STATUS From the REPORT STATUS sub-menu, status information can be displayed for system Loops, individual external devices, the PSU card and the batteries: REPORT STATUS Menu: LOOP To get status information on the system’s loops, access the LOOP status menu: •...
  • Page 80: Report Status Menu: Device

    ESPRIT-Argus User Manual CONFIGURING THE SYSTEM REPORT STATUS Menu: DEVICE To get status information on external devices fitted to the system, access the DEVICE STATUS menu: • On the MAIN MENU, use Left/Right arrow keys to move cursor box to REPORT menu icon •...
  • Page 81: Report Status Menu: Psu Card

    ESPRIT-Argus User Manual CONFIGURING THE SYSTEM • Next, press return key to return to the REPORT STATUS menu. REPORT STATUS Menu: PSU CARD To get status information for the panel’s PSU card, access the PSU Card Status menu: • On the MAIN MENU, use Left/Right arrow keys to move cursor box to REPORT menu icon •...
  • Page 82: Report Menu: Versions

    ESPRIT-Argus User Manual CONFIGURING THE SYSTEM REPORT Menu: VERSIONS To access the software Versions information: • On the MAIN MENU, use Left/Right arrow keys to move cursor box to REPORT menu icon • Press ✓ key to select the REPORT menu.
  • Page 83: Report Menu: History

    ESPRIT-Argus User Manual CONFIGURING THE SYSTEM REPORT Menu: HISTORY To access EVENT HISTORY information: • On the MAIN MENU, use Left/Right arrow keys to move cursor box to REPORT menu icon • Press ✓ key to select the REPORT menu.
  • Page 84: Report Menu: Counter

    ESPRIT-Argus User Manual CONFIGURING THE SYSTEM REPORT Menu: COUNTER To get ALARM COUNT information: • On the MAIN MENU, use Left/Right arrow keys to move cursor box to REPORT menu. • Press ✓ key to select the REPORT menu. •...
  • Page 85: Report Menu Breakdown

    ESPRIT-Argus User Manual CONFIGURING THE SYSTEM REPORT Menu Breakdown Approved Document Ref: UI-ESA-01 Issue 1.0...
  • Page 86 ESPRIT-Argus User Manual CONFIGURING THE SYSTEM Approved Document Ref: UI-ESA-01 Issue 1.0...
  • Page 87: Eng Menu

    ESPRIT-Argus User Manual CONFIGURING THE SYSTEM ENG Menu From the ENG menu on the MAIN MENU, the following sub-menus are available • OUTPUTS • ERROR SEEK To access the CONFIG menu: • Turn Activate Controls Key to On • Use the keypad to enter code 1111: o Press ✓...
  • Page 88: Eng Menu: Error Seek

    ESPRIT-Argus User Manual CONFIGURING THE SYSTEM ENG Menu: ERROR SEEK To locate system errors, open the ERROR SEEK menu: • On the MAIN MENU, use Left/Right arrow keys to move cursor box to highlight ENG menu icon • Press ✓ key to select the ENG menu.
  • Page 89: Eng Menu Breakdown

    ESPRIT-Argus User Manual CONFIGURING THE SYSTEM ENG Menu Breakdown Approved Document Ref: UI-ESA-01 Issue 1.0...
  • Page 90: Service And Maintenance

    ESPRIT-Argus User Manual SERVICE AND MAINTENANCE SERVICE AND MAINTENANCE Note: The following section is a summary of the requirements in BS5839 Part 1. For comprehensive information, a copy of BS5839 Part 1 can be purchased from the British Standards Institution via their web site at www.bsi-global.com.
  • Page 91: Periodic Inspection And Servicing

    ESPRIT-Argus User Manual SERVICE AND MAINTENANCE weekly test should be carried out at approximately the same time each week. Instructions to the occupants should be that they report any instance of poor audibility of the fire alarm signal. A different manual call point should be used at the time of every weekly test so that all manual call points in the building are tested in rotation over a prolonged period.
  • Page 92: Schedule Of Testing

    ESPRIT-Argus User Manual SCHEDULE OF TESTING SCHEDULE OF TESTING This section to be used to record ALL weekly tests of the fire alarm system Date & Device Tested & Initials of Comments (if any) Location Tester Time of Test Approved Document Ref: UI-ESA-01 Issue 1.0...
  • Page 93 ESPRIT-Argus User Manual SCHEDULE OF TESTING Date & Device Tested & Initials of Comments (if any) Location Tester Time of Test Approved Document Ref: UI-ESA-01 Issue 1.0...
  • Page 94 ESPRIT-Argus User Manual SCHEDULE OF TESTING Date & Device Tested & Initials of Comments (if any) Location Tester Time of Test Approved Document Ref: UI-ESA-01 Issue 1.0...
  • Page 95 ESPRIT-Argus User Manual SCHEDULE OF TESTING Date & Device Tested & Initials of Comments (if any) Location Tester Time of Test Approved Document Ref: UI-ESA-01 Issue 1.0...
  • Page 96 ESPRIT-Argus User Manual SCHEDULE OF TESTING Approved Document Ref: UI-ESA-01 Issue 1.0...
  • Page 97 www.haes-tech.com...

This manual is also suitable for:

Esa-1001Esa-1002