Haes Alarm Sense Plus Installation, Commissioning & Operating Manual

12 zone fully functional repeater panel
Hide thumbs Also See for Alarm Sense Plus:

Advertisement

Quick Links

R E P EATE R PA N EL
12 ZONE FULLY FUNCTIONAL REPEATER PANEL
Installation, Commissioning &
Operating Manual
Approved Document UI-ASP-R-01 Issue 3.0

Advertisement

Table of Contents
loading

Summary of Contents for Haes Alarm Sense Plus

  • Page 1 R E P EATE R PA N EL 12 ZONE FULLY FUNCTIONAL REPEATER PANEL Installation, Commissioning & Operating Manual Approved Document UI-ASP-R-01 Issue 3.0...
  • Page 2 Haes Systems Ltd, Columbia House, Packet Boat Lane, Cowley Peachey, Uxbridge, UB8 2JP Model Number AlarmSense PLUS 12 zone repeater panel ASP-R-12 European Standard EN54-2 : 1997 + A1 : 2006 Control and indicating equipment for fire detection and fire alarm systems for buildings.
  • Page 3: Table Of Contents

    CONTENTS Page ABOUT THIS PANEL PRODUCT OVERVIEW CABINET DETAILS CIRCUIT BOARDS MAIN PCB TERMINALS COMMS PCB TERMINALS TECHNICAL SPECIFICATION POWER SUPPLY MODULE INSTALLATION SAFETY ESD PRECAUTIONS GENERAL MOUNTING THE CABINET MAINS CONNECTIONS CONNECTING THE BATTERIES CABLING SETUP & PROGRAMMING INSTALL COMMS PCB SET NUMBER OF REPEATER PANELS REPEATER PANEL ADDRESSING PROGRAMMING REPEATER PANELS...
  • Page 4: About This Panel

    ABOUT THIS PANEL PRODUCT OVERVIEW The AlarmSense PLUS repeater panels have the same, easy to use, controls and indications as the main control panel but mounted in a smaller cabinet. The repeaters are fully functional with ‘Silence’, ‘Resound’ and ‘Reset’ controls, as well as Disable and Test Mode functions.
  • Page 5: Cabinet Details

    ABOUT THIS PANEL CABINET 80mm 57mm 260mm 308mm 250mm 300mm ASP-R Installation, Commissioning & Operating Manual Approved Document Ref: UI-ASP-R-01 Issue 3.0...
  • Page 6: Circuit Boards

    ABOUT THIS PANEL CIRCUIT BOARDS AlarmSense PLUS repeater panels comprise of three circuit boards TPCA01-R - Master PCB 28V 0V FIRE FAULT SNDR1 SNDR2 ZONE1 ZONE2 ZONE3 ZONE4 + - + - C NC NO C NC NO -OP -OP -IP -IP BATTERY TPCA05 - Comms PCB (with V3.0 software) COMS A...
  • Page 7: Main Pcb Terminals

    ABOUT THIS PANEL MAIN PCB TERMINALS Switched -ve inputs Switched -ve outputs Max load 40mA 28V 0V FIRE FAULT SNDR1 SNDR2 ZONE1 ZONE2 ZONE3 ZONE4 + - + - C NC NO C NC NO -OP -OP -IP -IP BATTERY COMMS PCB TERMINALS Relay Coil COMS A...
  • Page 8: Technical Specification

    ABOUT THIS PANEL TECHNICAL SPECIFICATION Electrical Specification Inputs & Outputs - TPCA01-R Main PCB Terminal capacity 0.5mm to 2.5mm solid or stranded wire. PSU @ output Power supply voltage control line. For temperature compensation control. PSU Input + - 28vdc supply input. Diode protected for Max input current 3 amps.
  • Page 9: Power Supply Module

    ABOUT THIS PANEL POWER SUPPLY MODULE Power Supply Specification Mains supply 230vac +10% / -15% 50Hz max current Mains supply fuse 2 Amp (T2A 250V) Not accessible for servicing. Internal to switch mode power unit Internal power supply rating 1.5 Amps total including battery charging Maximum load shared between outputs = 900mA Maximum continuous load for battery...
  • Page 10: Installation

    INSTALLATION SAFETY Suppliers of articles for use at work are required under section 6 of the Health and Safety at Work Act 1974 to ensure as reasonably as is practical that the article will be safe and without risk to health when properly used.
  • Page 11: Esd Precautions

    INSTALLATION ESD PRECAUTION Electronic components are vulnerable to damage by Electrostatic Discharges (ESD). An ESD wrist strap, suitably grounded, should be worn at all times when handling pcbs. These wrist straps are designed to prevent the build up of static charges, not only within a persons body, but on many other materials. ESD damage is not always evident immediately, faults can manifest themselves at anytime in the future.
  • Page 12: Mains Connections

    INSTALLATION Typical panel layout Incoming mains wiring Comms loop wiring 28V 0V FIRE FAULT SNDR1 SNDR2 ZONE1 ZONE2 ZONE3 ZONE4 + - + - C NC NO C NC NO -OP -OP -IP -IP COMS A COMS B SW -ve OUTPUTS + - + - ADDRESS BATTERY...
  • Page 13: Connecting The Batteries

    INSTALLATION CONNECTING THE BATTERIES Batteries of even very small capacity are capable of delivering very high currents which can cause fire or injury, therefore battery connections should be done with caution. The panel is supplied with battery leads already connected to the battery terminals on the main PCB. These leads are coloured red for +ve and black for -ve.
  • Page 14: Cabling

    INSTALLATION POWERING REPEATER VIA A 24 VOLT SUPPLY WHEN NO LOCAL MAINS SUPPLY IS PRESENT This can be achieved by using the following method. Disconnect & remove the PSU module from the repeater panel Connect 24v supply from remote PSU or control 24v Supply Input 24v (22 to 28v dc) panel to the PSU +, - terminals on the main circuit...
  • Page 15 INSTALLATION To change the Comms monitoring type at the main control panel use: Panel Wide Settings RESOUND SILENCE RESET There are 6 general, panel wide, settings available. Enter the above code and press the ENTER button. The 6 programmable ENTER options are represented by fire zone LEDs 1 - 6, Option 6 being the, Disable Test...
  • Page 16: Setup & Programming

    SETUP & PROGRAMMING REPEATER PANEL SETUP & PROGRAMMING The panels can support up to 8 repeaters. The repeater panels are fully functional with ‘Silence’ ‘Resound’ and ‘Reset’ controls, as well as Disable and Test Mode functions. It is possible to disable the controls of each or all repeater panels to make them passive.
  • Page 17 SETUP & PROGRAMMING To change the internal PCB configuration at the main control panel use: Panel Wide Settings RESOUND SILENCE RESET There are 6 general, panel wide, settings available. Enter the above code and press the ENTER button. The 6 programmable ENTER options are represented by fire zone LEDs 1 - 6, Option 5 being the, ‘set Disable...
  • Page 18: Set Number Of Repeater Panels

    SETUP & PROGRAMMING To set the number of repeater panels at the main control panel use: Panel Wide Settings RESOUND SILENCE RESET There are 6 general, panel wide, settings available. Enter the above code and press the ENTER button. The 6 programmable ENTER options are represented by fire zone LEDs 1 - 6, Option 2 being the, ‘set Disable...
  • Page 19: Programming Repeater Panels

    SETUP & PROGRAMMING Programming Repeater Panels All repeater programming is done at the main control panel with Level 3 programming mode active, see main control panel instruction manual. The repeater panels have 2 inputs located on the main circuit board, Class Change (CC) and Alert (PUL). Switching a negative voltage into these inputs will cause the alarm sounders to operate.
  • Page 20: Operating

    OPERATING PANEL CONTROLS & INDICATIONS Zonal Fire Indicator LEDs Zones in Fire Zones In Fault, Zones Disabled or Zones In Test Indicator LEDs Zone Fault / Disabled / Test Suppl y Healthy Test Mode Delay Status RESOUND SILENCE RESET General Fire Sounder Status Repeater Fault General Fault...
  • Page 21 OPERATING Status LED Indicators LED On LED Pulsing Zones in Fire 1 - 12 Indicates alarm condition in zone. Zone Fault/Disabled/Test Indicates zone circuit is disabled or in test Indicates a fault in the zone circuit. 1 - 12 mode. Indicates mains and/or battery supply is Supply Healthy: present.
  • Page 22: Disable Mode

    OPERATING DISABLE MODE Disable Mode is used to disable or isolate individual zone circuits or all sounder circuits, all auxiliary outputs and any delays to outputs. To initialise Disable Mode firstly activate the controls by turning RESOUND SILENCE RESET the key switch or by entering the four digit code. Then press and hold the Disable Mode button (1) for 3 seconds.
  • Page 23: Test Mode

    OPERATING TEST MODE Test Mode is used when testing the fire alarm system. In test mode the devices in the zone(s) in test, detectors and call points etc, can be activated and the panel will automatically reset, enabling the system to be tested by one person.
  • Page 24 www.haes-systems.com...

Table of Contents