PW7K1R1E Wiring and Setup

Specifications

2.15 Specifications

The interface must be used in low voltage, class 2 circuits only.
The installation of this device must comply with all local fire and electrical codes.
Power Input • PoE Power Input 12.95W, compliant to IEEE 802.3af
Power Out-
put
Output
Inputs
Reader Interface
20
www.honeywell.com
- OR -
• PoE+ (25 W), compliant to IEEE 802.3at
OR
-
-
• 12VDC 10%, 900mA maximum
• PoE: VO (TB4-1) and RVO (TB7-4), combined: 12 Vdc @.
A maximum PoE+
-OR-
• 12 Vdc: VO (TB4-1) 12 Vdc @ 1 A maximum, RVO, (TB7-
4) 12 Vdc @.5 A maximum
• Reader (TB3) 12 VDC (10.3 through 12.6) @ 150mA
maximum
• AUX (TB5) 12 VDC (10.7 through 13.0) @ 700 mA
maximum
• Four relays, Form-C contacts rated at 2 A @ 30 Vdc
• Six unsupervised/supervised, End of Line resistors, 1k/1k
ohm, 1%, ¼ watt
• Standard
Reader Power:
• 12VDC @ 5mA maximum (RVO,TB7-
4)
• 2-Wire RS-485, OSDP protocol, four
Communication:
devices maximum
Reader LED Out-
• TTL compatible
put
• High > 3.0V
• Low < 0.5V
• 5mA source/sink maximum
Buzzer Output
• Open collector
• 5VDC open circuit maximum
• 10mA sink maximum
Reader Data Inputs • TTL compatible inputs
or
• 2-wire RS-485

Hide quick links: