Mitsubishi Electric LGH-50RVS-E Installation Instructions Manual page 26

Lossnay heat recovery ventilator
Hide thumbs Also See for LGH-50RVS-E:
Table of Contents

Advertisement

No.66
CO
sensor or BMS setting
2
According to the type of external input, set this item.
Lossnay changes fan speed according to input voltage to CN26 when
3rd party's CO
sensor or BMS is setting.
2
When connecting with PZ-70CSW-E or PZ-70CSB-E, refer to their
manuals for detail.
Do not set other than below settings.
* The function of [CO
control: No/Yes ] on PZ-62DR-E is not
2
applicable for this product. Do not change that setting.
DIP-SW
PZ-62DR-E
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
5-6 OFF
5-7 OFF
5-8 OFF
5-6 OFF
5-7 OFF
5-8 ON
SW5-6
SW5-7
5-6 OFF
66
SW5-8
5-7 ON
5-8 ON
5-6 ON
5-7 OFF
5-8 OFF
5-6 ON
5-7 ON
5-8 OFF
[Pattern Z]
Lossnay changes fan speed as the table below. (Connection
example: BMS (Building Management System))
Input voltage[VDC] Fan speed
0 - 1.0
-
1.5 - 2.5
1
3.5 - 4.5
2
5.5 - 7
3
8.5 - 10
4
When the input voltage is in-between, it will cause unstable operation.
No.67
Threshold minutes for PZ-70CSW-E LED
LED turns from orange to red when the CO
limit concentration for decided minutes.
The threshold minutes can be changed.
Refer to the Installation manual of PZ-70CSW-E for more detail.
DIP-SW
PZ-62DR-E
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
-
-
67
N/A
-
-
-
-
-
-
Setting
CO
sensor or BMS
2
check
setting
0
DIP-SW priority
(Factory setting)
No external fan speed
1
control input
3rd party's CO
sensor
2
2
(0-10 VDC equals to
0-2000 ppm)
BMS
4
Refer to pattern Z below
5
PZ-70CSW-E
7
PZ-70CSB-E
Fan speed changing from
Remote controller
Available
N/A
N/A
N/A
N/A
level is kept over the
2
Setting
Threshold minutes for
check
PZ-70CSW-E LED
0
10 min
1
15 min
2
20 min
(Factory setting)
3
25 min
4
30 min
Threshold concentration for PZ-70CSW-E
No.68
LED
The threshold concentration for wall mounted CO
green to orange can be changed.
Refer to the Installation manual of PZ-70CSW-E for more detail.
DIP-SW
Setting
check
SW No.
Setting
-
-
-
-
-
-
-
-
-
-
N/A
-
-
-
-
-
-
-
-
-
-
-
-
No.69
Emergency stop setting
This function can select the priority of Remote OFF signal to CN32.
When the emergency stop is selected and Lossnay receives remote
off signal, Lossnay does not operate Night purge, after cooling or
some other operations until remote off signal stops.
DIP-SW
Setting
check
SW No.
Setting
-
-
N/A
-
-
- When installing the centralized management devices (including the
system controller) in Mitsubishi Electric Air-Conditioner Network
System (MELANS), perform emergency stop by the centralized
management devices. In this case, do not use the function No. 69.
Eng-26
sensor LED from
2
PZ-62DR-E
Setting
Threshold concentration
check
for PZ-70CSW-E LED
Function No. Setting Data
0
1000 ppm
1
1100 ppm
2
1200 ppm
3
1300 ppm
4
1400 ppm
5
68
1500 ppm
(Factory setting)
6
1600 ppm
7
1700 ppm
8
1800 ppm
9
1900 ppm
10
2000 ppm
PZ-62DR-E
Setting
Mode
check
Function No. Setting Data
Emergency
0
(Factory setting)
stop
69
Normal
1
stop
Lossnay
operation
When stopped
by Remote
OFF input,
Night purge,
after cooling
and some other
operation does
NOT work.
When stopped
by Remote
OFF input,
Night purge,
after cooling
and some other
operation does
work.