Technical specifications
5.1 Technical specifications
Article number
Traces
•
Number of configurable Traces
•
Memory size per trace, max.
Interrupts/diagnostics/status information
Diagnostics indication LED
•
RUN/STOP LED
•
ERROR LED
•
MAINT LED
•
Connection display LINK TX/RX
Supported technology objects
Motion Control
Controller
•
PID_Compact
•
PID_3Step
•
PID-Temp
Counting and measuring
•
High-speed counter
Standards, approvals, certificates
Suitable for safety functions
Highest safety class achievable in safety mode
•
Performance level according to ISO 13849-
1
•
SIL acc. to IEC 61508
Probability of failure (for service life of 20 years
and repair time of 100 hours)
Low demand mode: PFDavg in accord-
–
ance with SIL3
High demand/continuous mode: PFH in
–
accordance with SIL3
Ambient conditions
Ambient temperature during operation
•
horizontal installation, min.
•
horizontal installation, max.
•
vertical installation, min.
•
vertical installation, max.
40
6ES7518-4JP00-0AB0
8
512 kbyte
Yes
Yes
Yes
Yes
No
Yes; Universal PID controller with integrated op-
timization
Yes; PID controller with integrated optimization
for valves
Yes; PID controller with integrated optimization
for temperature
Yes
No
Yes; e.g. emergency stop, acknowledgment but-
ton
PLe
SIL 3
< 2.00E-05
< 1.00E-09
0 °C
60 °C; Display: 50 °C, at an operating temperature
of typically 50 °C, the display is switched off
0 °C
40 °C; Display: 40 °C, at an operating temperature
of typically 40 °C, the display is switched off
CPU 1518HF-4 PN (6ES7518-4JP00-0AB0)
Equipment Manual, 05/2021, A5E49868646-AA