Technical specifications
5.1 Technical specifications
Article number
Work memory
integrated (for program)
integrated (for data)
Load memory
Plug-in (SIMATIC Memory Card), max.
Backup
maintenance-free
CPU processing times
for bit operations, typ.
for word operations, typ.
for fixed point arithmetic, typ.
for floating point arithmetic, typ.
CPU-blocks
Number of elements (total)
DB
Number range
Size, max.
FB
Number range
Size, max.
FC
Number range
Size, max.
OB
Size, max.
Number of free cycle OBs
Number of time alarm OBs
Number of delay alarm OBs
Number of cyclic interrupt OBs
Number of process alarm OBs
Number of startup OBs
Number of asynchronous error OBs
Number of synchronous error OBs
Number of diagnostic alarm OBs
Nesting depth
per priority class
34
6ES7518-4JP00-0AB0
9 Mbyte
60 Mbyte
32 Gbyte
Yes
4 ns
6 ns
6 ns
24 ns
20 000; Blocks (OB, FB, FC, DB) and UDTs
1 ... 60 999; subdivided into: number range that
can be used by the user: 1 ... 59 999, and number
range of DBs created via SFC 86: 60 000 ... 60 999
16 Mbyte; For DBs with absolute addressing, the
max. size is 64 KB
0 ... 65 535
1 Mbyte
0 ... 65 535
1 Mbyte
1 Mbyte
100
20
20
20; with minimum OB 3x cycle of 100 µs
50
100
4
2
1
24; Up to 8 possible for F-blocks
CPU 1518HF-4 PN (6ES7518-4JP00-0AB0)
Equipment Manual, 05/2021, A5E49868646-AA

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cpu 1518hf-4 pn