Sigineer Power TPH Series User Manual

Transformer based 3 phase pure sine wave inverter charger 24v/48v to 120/208vac & 230/400vac 6kw to 45kw

Advertisement

TPH Series Transformer based
3 Phase Pure Sine Wave Inverter Charger
24V/48V to 120/208Vac & 230/400Vac
6KW to 45KW
User's Manual
Version 1.0
Sigineer Power Limited
Email: info@sigineer.com
TEL: +86 0769 82817616
Manufacturer Information
- 1 -

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the TPH Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Sigineer Power TPH Series

  • Page 1 TPH Series Transformer based 3 Phase Pure Sine Wave Inverter Charger 24V/48V to 120/208Vac & 230/400Vac 6KW to 45KW User’s Manual Version 1.0 Sigineer Power Limited Email: info@sigineer.com TEL: +86 0769 82817616 Manufacturer Information - 1 -...
  • Page 2: Table Of Contents

    2. Introduction ..................................- 5 - 2-1. General Information ............................... - 5 - 2-2. Application ..................................- 5 - 2-3 The Appearance and Mechanical Drawing of TPH Series ....................- 7 - 2-4 Features ................................... - 7 - 2-5 Electrical Performance ..............................- 7 - 2.5.1 Inverter .................................
  • Page 3: Important Safety Information

    1. Important Safety Information WARNING! This manual contains important instructions for all TPH Inverter/Charger models that shall be followed during installation and maintenance of the inverter. 1-1. General Safety Precautions 1. Before installing and using the TPH Inverter/Charger, read all instructions and cautionary markings on the TPH Inverter /Charger and all appropriate sections of this guide.
  • Page 4 9. If you need to remove a battery, always remove the grounded terminal from the battery first. Make sure all accessories are off so you don’t cause a spark. 10. Always use identical types of batteries. 11. Never install old or untested batteries. Check each battery’s date code or label to ensure age and type. 12.
  • Page 5: Introduction

    AC source and recharges the batteries. Accessories allow the TPH series to also serve as a central hub of a renewable energy system. Set the TPH Series inverter to battery priority mode, designates the inverter-preferred UPS configuration. In this configuration, the load power in normally provided by the inverter.
  • Page 6 Office equipment – computers, printers, monitors, facsimile machines, scanners. Household items – vacuum cleaners, fans, fluorescent and incandescent lights, shavers, sewing machines. Kitchen appliances – coffee makers, blenders, ice markers, toasters. Industrial equipment – metal halide lamp, high – pressure sodium lamp. Home entertainment electronics –...
  • Page 7: The Appearance And Mechanical Drawing Of Tph Series

    The peak efficiency of TPH-PV series is 88%. Overload Capacity The TPH series inverters have different overload capacities, making it ideal to handle demanding loads. 1 For 110%<Load<125%(± 10%), no audible alarm in 14 minutes, beeps 0.5s every 1s in the 15th minute, and Fault(Turn off) after the 15th minute.
  • Page 8: Ac Charger

    2.5.2 AC Charger TPH Series is equipped with an active PFC (Power Factor Corrected) multistage battery charger. The PFC feature is used to control the amount of power used to charge the batteries in order to obtain a power factor as close as possible to 1.
  • Page 9 Charging depleted batteries The TPH series inverter allows start up and through power with depleted batteries. For 12VDC model, after the battery voltage goes below 10V, if the switch is still (and always) kept in "ON"...
  • Page 10: Transfer

    48 Vdc 65 ± 5 Amp 12.000 48 Vdc 100 ± 5 Amp 18,000 24Vdc 300 ± 5 Amp 18,000 48 Vdc 150 ± 5 Amp 24,000 48 Vdc 200± 5 Amp 36,000 48 Vdc 300± 5 Amp 45,000 48 Vdc 350±...
  • Page 11 Power saver off Power saver on (Load detected) Note: The minimum power of load to take inverter out of sleep mode (Power Saver On) is 25 Watts. Table 2.5.6 TPH Series Idle Power Consumption Power Saver Off Power Saver Auto...
  • Page 12: Protections

    The inverter will go to Over temp protection when heat sink temp. ≥105º C, and go to Fault (shutdown Output) after 30 seconds. The switch has to be reset to activate the inverter. The TPH series Inverter has back feeding protection which avoids presenting an AC voltage on the AC input terminal in Invert mode.
  • Page 13: Led Indicator & Lcd

    POWER SAVER ON GREEN LED lit in Power Saver Mode 2.5.9 Audible Alarm Table 2.5.9 TPH Series Audible Alarm Spec Battery Voltage Low Inverter green LED lit, and the buzzer beeps 0.5s every 5s. Inverter green LED lit, and the buzzer beeps 0.5s every 1s and Fault after 60s.
  • Page 14: Dip Switches

     Fan noise level target <60db at a distance of 1m. 2.5.11 DIP Switches On the front panel of inverter, there are 5 DIP switches which enable users to customize the performance of the device. Table 2.5.11 TPH Series Dip Switch Function Setting DIP Switch NO. Switch Function Position: 0 Position: 1 10.0Vdc...
  • Page 15: Other Features

    50Hz/60Hz). This will avoid frequent switches between battery and generator. But some sensitive loads will suffer from the low quality power. The pros and cons should be clearly realized. SW3: Power Saver Auto Setting : In Power Saver Mode, when the SW3 is switched to position“0”, inverter will work in Unit Off Charging mode, it will stay in standby mode without sensing loads.
  • Page 16: Installation

    The auto generator start feature will only work with generators designed to work with this feature. There is an open/closed relay that will short circuit the positive and negative cable from a generator. The input DC voltage can vary, but the Max current the relay can carry is 16Amp. Battery temperature sensor (BTS) A battery temperature sensor (BTS) option can easily be installed in the system to ensure proper charging of the batteries based on temperature.
  • Page 17 It is suggested the battery bank be kept as close as possible to the inverter. The following able is a suggested wiring option for 1m DC cable. Please find the following minimum wire size. In case of DC cable longer than 1m, please increase the cross section of cable to reduce the loss.
  • Page 18: Ac Wiring

    CAUTION: Equipment Damage The inverter is not reverse polarity protected. Reversing the battery polarity on the DC input connections will cause permanent damage to the inverter which is not covered under warranty. Always check polarity before making connections to the inverter. WARNING: Shock Hazard Ensure the inverter is off before disconnecting the battery cables, and that AC power is disconnected from the inverter input.
  • Page 19: Install Flange

    TPP Series Inverter&Charger Topology Diagram Bypass & Charger Mode 3 Phase AC Circuit Breaker AC Output R-CB Transfer SW-R INPUT R S-CB Transfer SW-S 3 Phase Delta Load INPUT S Y- 220/400Vac T-CB Transfer SW-T INPUT T 1 Phase Load * 3 120/230Vac INPUT N Transfer SW-N...
  • Page 20 TPH 24-36KW Model TPH 45KW Model - 20 -...
  • Page 21: Battery Information

    TPH 3-18KW Wall mount 4 Battery Information 4-1 Battery Type There are two principal types of batteries: Starting type and Deep-Discharge type. Batteries can be either sealed or non-sealed(Vented). A. Starting type: Automotive(Starting type) batteries are designed to provide high starting current for short periods of time and are not appropriate for solar system.
  • Page 22: Battery Capacity Rating

    4-2 Battery Capacity Rating 4.2.1 Battery Discharge Rate Deep cycle batteries have their amp-hour rating expressed as “at the x-hour rate”. The hour rating refers to the time it takes to discharge the batteries. A faster hour rate (10 hour rate) means more current is withdrawn from the batteries during their discharge period.
  • Page 23: Battery Configurations

    Motors typically require 3 to 6 times their running current when starting. Check the manufacturer’s data sheets for their starting current requirements. If you will be starting large motors from the inverter, increase the battery bank size to allow for the higher start-up current. 4.2.4 Battery Configurations The battery bank must be wired to match the inverter’s DC input voltage specifications (12 or 24 or 48Vdc).
  • Page 24: Batteries Maintenance

    Table 4.2.2 Battery Wiring In Parallel Configuration Table 4.2.3 Battery Wiring In Series-Parallel Configuration Important: Connecting the positive and negative wires to the inverter from different strings ensures a balanced charge/discharge through the batteries, resulting in longer run times and improved battery life. 4.2.6 Batteries Maintenance To get the best performance from an inverter system, the batteries must be properly setup and maintained.
  • Page 25: Troubleshooting Guide

    Ensure the batteries are protected from extreme temperatures. 5 Troubleshooting Guide Troubleshooting contains information about how to troubleshoot possible error conditions while using the TPH Series Inverter & Charger. The following chart is designed to help you quickly pinpoint the most common inverter failures. Indicator and Buzzer Status Information From LED Indicator &...
  • Page 26 Over-Temp R:0.5s On 0.5s Off; In Charge Mode S:1.0s On 0.5s Off; √ √ √ × × × × × × T:2.0s On 0.5s Off; Beep continuous After 30s. 0.5s On 0.5s Off; √ √ Over-Charger × × × × ×...
  • Page 27 Beep continuous After R:0.5s On 0.5s Off; S:1.0s On 0.5s Off; Fan Lock On Line √ Blink √ Blink × × × × × × × T:2.0s On 0.5s Off; Mode Beep continuous After Abnormal Mains √ Blink √ Blink / ×...
  • Page 28 Appendix 1 TPH Series Three Phase Inverter & Charger Electrical Specifications...
  • Page 29 Line Mode >95% Efficiency Power Factor 0.9-1.0 Connection mode 3-phase 4-wire system+Ground Output voltage 3AC/N 400V or 208V rating Output phase 120/230VAC 120/230VAC 120/230VAC 230VAC 230VAC 230VAC 230VAC voltage Output Voltage ± 10% RMS Regulation Output Frequency 50/60Hz ± 0.3Hz Short Circuit Yes, Current Limit Function (Fault after 60ms) Protection...
  • Page 30 A.G.M 1 56.4 53.6 A.G.M 2 58.4 54.8 Sealed Lead Acid 57.6 54.4 Gel Euro 57.6 55.2 Open Lead Acid 59.2 53.2 Calcium 60.4 53.8 De-sulphation 62V for 4hrs Input Voltage Sine wave (Grid or Generator) Waveform Nominal Phase 120Vac 220Vac Voltage Low Voltage Trip...
  • Page 31 SAVE THIS MANUAL! READ THIS MANUAL BEFORE INSTALLATION, IT CONTAINS IMPORTANT SAFETY, INSTALLATION AND OPERATING INSTRUCTIONS. KEEP IT IN A SAFE PLACE FOR FUTURE REFERENCE. Sigineer Power Limited Email: info@sigineer.com TEL: +86 0769 82817616 - 31 -...