9.17 Adjusting Maximum Heating Power

Maximum boiler heating power can be reduced to suit
requirements of heating system it serves.
Table showing parameter P13 values according to
desired maximum power model is shown for each single
boiler.
To access and edit P13 values, proceed as described in
Section 9.15 Parameter Settings.
Boiler Model - PARAMETER P13 (%)/ Heating Output
Btu/h
KW
20,400
6.0
23,800
7.0
27,200
8.0
30,700
9.0
34,100
10.0
40,900
12.0
47,700
14.0
54,500
16.0
61,400
18.0
68,200
20.0
75,100
22.0
81,900
24.0
88,700
26.0
95,500
28.0
102,300
30.0
109,200
32.0
112,600
33.0
9 - START UP PROCEDURE
Btu/h
17,060
20,473
23,885
27,297
30,709
34,121
40,946
47,770
54,594
61,419
68,243
75,067
81,891
85,400
DCBF-125 DCCF-150
0
0
4
3
7
6
11
9
15
12
22
18
30
24
37
29
44
35
52
41
59
47
67
53
74
59
80
65
88
71
96
75
100
80
kW
DCBF-100 DCCF-115
5.0
0
0
6.0
4
3
7.0
7
6
8.0
11
9
9.0
15
12
10.0
18
15
12.0
25
21
14.0
35
28
16.0
45
35
18.0
57
45
20.0
68
55
22.0
80
65
24.0
95
75
25.0
100
80
Btu/h
27,400
31,300
35,800
41,300
46,500
55,900
65,700
74,500
83,200
92,300
101,900
110,000
118,000
127,000
136,900
145,300
151,700
54
kW
DCBF-165 DCCF-205
8.0
0
0
9.2
4
3
10.5
7
6
12.1
11
9
13.6
15
12
16.4
22
18
19.3
30
24
21.8
37
29
24.4
44
35
27.0
52
41
29.9
59
47
32.2
67
53
34.8
74
59
37.2
80
65
40.1
88
71
42.6
96
75
44.4
100
80
240013375 REV A, [07/01/2021]

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dccf-115Dcbf-125Dccf-150Dcbf-165Dccf-205

Table of Contents