Ask your electricity provider if necessary.
If the electricity provider can not adjust it, it could translate into a tension reduction on the power supply for few
seconds when the heat pump starts up.
Maximum water pressure : 2 bars (29 PSI).

Installation

Installation conditions

Installation location
The pool heat pump must be installed outdoors with a distance greater than 2 m from the Pool according to
laws in force (NF C 15 100).
Install the pool heat pump on a flat, horizontal, and stable surface. (Concrete base would be ideal).
Maintain at least 1 m (40") / minimum 30 cm (12") of space on the rear (evaporator air inlet) and minimum 3 m (120")
on the outlet side of the fan on a completely free space.
Make sure that the discharged air will not be sucked back into the evaporator again.
Provide enough space to allow access to temperature controller.
To improve your installation
Avoid directing the flow of ventilated air towards a noise sensitive area (room window for example), or a space where
people normally gather (the discharged air will be cold)
Avoid positioning the pool heat pump on a surface that can transmit vibrations.
Try to avoid placing the appliance under a tree or exposed to water or mud, which would be likely to complicate
performance and maintenance.
For best performance the water pipes from the heat pump to the pool should be insulated, especially if the heat pump
is far away from the swimming pool.
Inlet air flow:
1 m (40 ") / minimum 30 cm
Outlet air flow:
Open space / minimum 3 m (120 ")
(12")
- 5 -