e. SUN2000-36KTL (excluding the ground
cable but including the neutral wire)
M8
8 N·m
NOTE
Choose whether to connect the neutral wire to the SUN2000-36KTL based on the application
scenario. When the SUN2000-36KTL is used in a low-voltage scenario without the neutral wire, set
Output mode to Three-phase, three-wire without N line on the SUN2000 APP, SmartLogger, or
NetEco.
10.Use a torque wrench with an open end of 52 mm to tighten the locking caps to a torque of 7.5 N·m.
4.4
Installing DC Input Power Cables
Selecting DC input terminals
Number
of Inputs
1
2
3
4
5
6
7
8
SUN2000
Connects to any route.
Connects to routes 1 and 5.
Connects to routes 1, 3, and 5.
Connects to routes 1, 3, 5, and 7.
Connects to routes 1, 2, 3, 5, and 7.
Connects to routes 1, 2, 3, 5, 6, and 7.
Connects to routes 1, 2, 3, 4, 5, 6, and 7.
Connects to routes 1, 2, 3, 4, 5, 6, 7, and 8.
f. SUN2000-36KTL (including the ground
cable and neutral wire)
M8
8 N·m
M6
5 N·m
NOTE
The inverter provides two DC switches,
namely, DC SWITCH 1 and DC SWITCH 2.
DC SWITCH 1 controls the first to the fourth
routes of DC input terminals, while DC
SWITCH 2 controls the fifth to the eighth
routes of DC input terminals.
8