6.2 Electrical Wiring Connection
(1) Perform the electrical wiring work for the Switch Boxes. Select the wire size according to the table below.
(2) Pay attention to the marks on the terminal block when connecting wires for Switch Box and I.U./O.U.
Refer to "Example of Electrical Wiring" for the wiring connection on the next page.
Electrical Data and Recommended Wiring, Breaker Size/1 Outdoor Unit
Power
Model
Supply
HCHS-N06X
220-240V~
50Hz
HCHS-N10X
220V~60Hz
Field Minimum Wire Sizes for Power Source
220-240V~
HCHS-N06X
50Hz
HCHS-N10X
220V~60Hz
NOTES:
ELB: Earth Leakage Circuit
Breaker Remarks:
(1) The field wiring shall be conducted according to local laws.
(2) The sizes of above power lines shall comply with relevant standards.
(3) The shielded wire shall be used for the control system and be grounded.
(4) The sheathed lines shall be used for power lines and shall be copper conductors.
(5) In case of tandem connection of power lines, the current values shall be added up to select the electric wire.
Selection According to EN60 335-1
Currect i(A)
6
6
10
10
16
16
25
25
32
40
32
40
63
63
*2: In the case that currennt exceeds 63A,do not connect cables in series.
Max.Running
Current(A)
-
-
Wire Size (mm
2
)
2.5
2.5
2.5
4.0
6.0
10.0
16.0
2
*
ELB
Nominal
Nominal Sensitive
Current(mA)
Current(A)
15
EN60335-1
0.75
16
Fuse(A)
30
15
EN60335-1
0.75