Electrical Connections - Riello 20083501 Manual

Electronic cascading accessory for dhw mixers
Table of Contents

Advertisement

Available languages

Available languages

CAVO CAN BUS
CAN BUS CABLE
CAN CAN VFS2 VFS1
ALIMENTAZIONE
SENSOR AND CONTROL TERMINALS
LATO SONDE E CONTROLLO
+
S6
V2
V1 S5 S4 S3 S2 S1
-
R3 R3I R2 R1 L N
S5
S4
AFS
Max. low voltage 12 VAC / DC
Terminal:
Connection for:
S1
Recirculation
S2
Cold water sensor
S3
Primary flow rate (optional)
S4
Storage cylinder top sensor
S5
V1
Primary pump PWM signal
V2
0-10V/PWM signal (optional)
S6
Primary return (optional)
-
Cold water draw-off sensor
VFS2
optional
The cascade of ACS 40 E DHW mixers is controlled electronically by the control units. The various mixers in the cascade
are connected via a CAN bus cable between their control units.
- Unscrew the screw at the bottom of the front cover and open the control unit.
- Plug the CAN bus cable into the connector in the control unit (see terminal diagram).
- Fit terminating jumpers to the start and end connectors in the first and last DHW mixers in the cascade.
- Connect the various control units with the CAN bus cable provided.
- Connect the solenoid valve in the cold water inlet pipe to each DHW mixer to relay 3 in the power terminals of the mixer's
control unit.
- Connect the recirculation pump to the first mixer in the cascade, connecting the power cable to relay 2 in the power
terminals and connecting the control cable to control terminal V2.
Procedure for recognising the CAN bus cable and activating the cascade function:
- Switch on the control unit.
- When the display lights up, press ESC key for 10 seconds.

ELECTRICAL CONNECTIONS

LATO
CAN CAN VFS2 VFS1
230 V
POWER
TERMINALS
230 V
SENSOR AND CONTROL TERMINALS
LATO SONDE E CONTROLLO
+
S6
V2
V1 S5 S4 S3 S2 S1
S5
S4
CAVO CAN BUS
CAN BUS CABLE
LATO
CAN CAN VFS2 VFS1
230 V
ALIMENTAZIONE
POWER
TERMINALS
230 V
SENSOR AND CONTROL TERMINALS
LATO SONDE E CONTROLLO
-
R3 R3I R2 R1 L N
+
S6
V2
AFS
Power terminals 230 VAC 50-60 Hz
Terminal:
Connection for:
L
Mains power, phase L
N
Mains power, N
R1
Primary circuit pump
R2
Relay 2 (recirculation option)
R3
Relay 3 (normally open)
R3I
Relay 3 (normally open)
The earth wire must be connected to the metallic PE
terminal!
11
LATO
230 V
ALIMENTAZIONE
POWER
TERMINALS
230 V
V1 S5 S4 S3 S2 S1
-
R3 R3I R2 R1 L N
S5
S4
AFS