Connecting Output Power Cables
3.3
•
The metal terminals are delivered together with the DC output terminal.
•
The recommended crimping tool is XCXY-02. The locator model is DWQ-18.
•
Recommended heat-shrink tubing diameter: 6 mm; recommended temperature resistance: 125°C; recommended baking temperature:
110°C
•
The metal terminals must be reliably crimped. Minimum pulling-out force: 300 N for the cross-sectional area 5.26 mm
cross-sectional area 6 mm
The DC output terminal can be installed in the following two scenarios. Install it based on the site requirement.
•
Used with an address board (DC output terminal and address board supplied by the user)
•
Not used with an address board (DC output terminal supplied by the user)
Connecting Output Power Cables (Used with an Address Board)
1. Install DC output power cables.
Keep a distance of 3–5 mm between the front end of the heat shrink tubing and the metal terminal buckle.
2. Install emergency shutdown cables.
3. Install CAN communications cables.
A 120-ohm resistor must be connected in parallel between the cables of the first and last chargers. Otherwise, communication may be poor.
2
.
4
2
or 350 N for the