Wire Type
Communication Line L(m)
Light/Common PVC
Jacket Soft Wire
3.3.2 Select communication line for indoor unit and indoor unit (outdoor unit)
Outdoor
Outdoor
unit1
unit 2
LO1
L=LO1+LO2+LO3+Li1+Li2+.......+Lin(n≤80)
Total Length of
Wire Type
ommunication
Light/Common PVC
Jacket Soft Wire

3.4 Wiring Requirements

(1) Power Cord Size and Air Switch Capacity
Model
GMV-NX140P/A(X1.2)-K
GMV-NX224P/A(X2.0)-M
GMV-NX280P/A(X2.5)-M
GMV-NX280P/A(X3.0)-M
GMV-NX450P/A(X4.0)-M
Notes:
① The size of circuit breaker and power cord in above sheet is selected based on the max
power (max current) of unit.
② Above selection requirements of power cord size: Power cord size is based on multicore
copper core cable with operation temperature of 90°C when laying on wire groove at 40°C ambient
temperature (IEC 60364-5-523). If the operation condition is different, please calculate according to
national standard.
③ Above selection requirements of circuit breaker size: Circuit breaker size is based on ambient
temperature of 40°C when the circuit breaker is working. If the operation condition is different, please
calculate according to circuit breaker specification.
(2) Install circuit breaking device near the unit. The minimum distance between each stage of
circuit breaking should be 3mm (The same for both indoor unit and outdoor unit).
Total Length of
L ≤ 250
Outdoor
Outdoor
unit 3
unit 4
LO2
LO3
Wire Gauge (mm
Line L(m)
L ≤ 1000
≥ 2×0.75
Power Supply
220-240V ~50Hz
380-415V 3N ~50Hz
380-415V 3N ~50Hz
380-415V 3N ~50Hz
380-415V 3N ~50Hz
Multi Variable Air Conditioners Duct Type Indoor Unit
2
Wire Gauge (mm
)
Wire Standard
2×0.75~2×1.25
IEC 60227-5
Fig 3.3.2
2
) Wire Standard
IEC 60227-5
Air Switch
Minimum Sectional
apacity
(A)
6
6
6
6
6
7
The total length of
communication line
should not exceed 250m
Lin
Remark
If wire gauge is 2X1 mm
it's OK to increase the length of
communication line. But total
length should not exceed 1500m.
Area of Ground
Sectional Area of
2
Wire(mm
)
Power
1.0
1.0
1.0
1.0
1.0
Remark
2
, then
Minimum
2
Cord(mm
)
1.0
1.0
1.0
1.0
1.0