MULTI SPLIT TYPE ROOM AIR CONDITIONER
INSTALLATION MANUAL
This manual describes the installation of outdoor unit only
For the installation of the indoor unit, see the installation manual accompanying indoor unit.
SAFETY PRECAUTIONS
• Installation must be made in accordance with the installation
manual by qualified service personnel.
Incorrect work will cause electric shock, water leak, fire.
• Be sure to use the attached accessories parts and specified parts
for installation.
Use of other parts will cause electric shock, water leak, fire, the unit
falling.
• The appliance shall be installed in accordance with national wir-
ing regulations.
Wrong connection can cause overheating or fire.
• After installation has complete, check that there is no leakage of
refrigerant gas.
If the refrigerant gas contact with fire, it may generate toxic gas.
• Ventilate the room if refrigerant gas leaks during installation.
If the refrigerant gas contact with fire, it may generate toxic gas.
• Use the specified electrical cable.
Make sure the cable is secured in place and that the terminals are free
of any excess force from the cable. Otherwise overheating or fire may
result.
• Form the cable so that the control box cover, the cord holder and
cable holder are not loose.
Otherwise overheating, fire or electric shock may result.
ACCESSORIES
ITEMS
Q'ty
APPLICATION
1 Manual
Installation manual
3 Drain tray
1
2 Cable fixing band
To bind the cables.
4 Drain joint
1
NOTES ON LOCATIONS
1. Place the outdoor unit on a stable base.
2. Provided sufficient space around the unit. It should also be well
ventilated.
3. The unit should not be exposed to strong wind nor splashed
with rain water.
4. Water drain from the unit should be let out without problem. Lay
a drain hose if required. In cold regions, installation of the drain
pipe is not advisable as freezing could result.
5. Keep TV set, radio and the like 1 m or more away from the unit.
6. Avoid locations exposed to machine oil vapor, salty air (facing
the seashore, for example), hot spring vapor sulfur gas, etc. Such
location can cause breakdown.
7. Avoid locations exposed to muddy water (along a road, for exam-
ple) or where the unit can be tampered with.
8. Select a location where the outgoing air or operating noise can-
not annoy others.
9. Keep the air outlet opening free of any obstacle. This could affect
the performance of the unit and create loud noises.
PIPING
Max. piping
Max. total piping length of all
Min. piping
length:A
unit
length:A
25 m
50 m(2 units) / 60 m(3 units)
3 m
1. Standard piping length is 5 m.
2. When the outdoor unit is placed at a higher level than the indoor unit, provide a trap near the hose's lead-in port.
Use the refrigerant pipes shown in the table below.
Pipe size
Pipe thickness
Liquid side
1/4" (ø 6.35 mm)
Thickness: 6 mm or thicker
3/8" (ø 9.52 mm)
0.8 mm
Material: Polyethylene foam
Gas side
1/2" (ø 12.7 mm)
• The thermal insulation should cover both the gas and liquid pipes.
A3AUX3M24RV.indd
1
AU-X3M24RV
• Tighten the flare nut with a torque wrench according to the specified
method.
If the flare nut is tightened too hard, the flare nut may be broken after a long
time and cause refrigerant gas leakage.
• When installing the unit, take care not to enter air substance other than
the specified refrigerant(R410A) in the refrigerant cycle.
Otherwise, it will cause burst and injury as a result of abnormal high pres-
sure in the refrigerant cycle.
• Be sure to connect the refrigerant pipe before running the compressor.
Otherwise, it will cause burst and injury as a result of abnormal high pres-
sure in the refrigerant cycle.
• Earth the unit.
Incomplete earth may cause electrical shock.
• Install an earth leakage breaker to avoid electric shock in case of leak.
Use the current-activated, high-sensitivity, high-speed type breaker with a
rated sensitivity current of below 30 mA and an operating time of below 0.1
second.
• Arrange the drain hose to ensure smooth drainage.
Insufficient drainage may cause wetting of the room, furniture etc.
• This room air conditioner uses refrigerant R410A.
Use the pipe, flare nut and tools exclusively for R410A.
ITEMS
Q'ty
APPLICATION
ITEMS
To connect the
5 Joint
drain hose to the
1
outdoor unit.
6 Seal Ring
1
7 Flare nut
(3/8
)
"
INSTALLATION DIAGRAM
300
mm or more
300
mm or more
300
mm or more
1000
mm or more
• Install at least 2 indoor units.
400
mm or more
• Provide as much installation
For installation work
space as possible for efficient
air-conditioning.
Max. height difference:
B
C
D
10 m
10 m
10 m
Thermal insulation
Carefully read and follow these instructions for
B508
smooth and trouble-free installation.
1
OUTDOOR UNIT INSTALLATION
Before installation, remove the
packing pad from the outdoor
unit.
Installation dimension
Referring to the figure, firmly fas-
ten the outdoor unit with bolts.
2
CONNECTING THE REFRIGERANT PIPES
The flare coupling refrigerant pipes.
Q'ty
APPLICATION
Outdoor unit
To connect 3/8"
pipe to the port "A-
1
1/4"
UNIT"
1
3/8"
1
1/4"
3/8"
1/4"
1/2"
*Make sure to connect 18000BTU/h-class indoor
unit to the port "A-UNIT".
Coating tape
(Commercially available)
Note:
• Make sure the flare nuts of the outdoor unit are securely closed for those not connected to the indoor unit.
Piping cover
Flaring the pipe end
(1) Cutting with a pipe cutter
Cut at a right angle.
(2) Deburring
Allow no cuttings in the pipe.
(3) Putting in the flare nut
Connecting the pipes
Connect the pipes for the indoor unit first and then
for the outdoor unit.
A
(1) Tighten the flare nuts by hand for the first 3-4
turns.
B
(2) Use a wrench and torque wrench to tighten up
D
the pipes.
C
• Do not over tighten the pipes; it may be de-
formed or damaged.
Trap
Notes:
• Bend the pipes carefully as not to damage them.
• Lay the drain hose below the pipes.
Connecting the drain hose
The unit discharged water from its drain port. Con-
nect a commercial drain hose if drainage is neces-
Packing pad
sary.
557
Drain hose (Commercially available)
Inside diameter: ø16 mm
Indoor unit
1/4"
Connecting 7000/9000/12000 BTU/h-class indoor unit to
the port "A-UNIT"
3/8"
Make sure to use the joint, flare nut and seal ring.
1/4"
Outdoor unit
3/8"
1/4"
1/4"
1/2"
*18000BTU/h
1/2"
class
S
e
a
r l
n i
g
6
90°
(4) Flaring
A
Flare processing
dimensions(A)
(5) Checking
To be flared perfectly circular.
Flare nut not missing.
Flare nut
Wrench
Torque wrench
Flare nut tightening torque
Pipe size
Torque
Liquid side
1/4" (ø 6.35 mm) 16±2 N·m (1.6±0.2 kgf·m)
3/8" (ø 9.52 mm) 38±4 N·m (3.8±0.4 kgf·m)
Gas side
1/2" (ø 12.7 mm) 55 ± 5 N·m (5.5 ± 0.5 kgf·m)
ENGLISH
Drain tray 3
Drain joint 4
Fit the drain joint into the
Drain port
drain tray and connect the
drain port.
Indoor unit
1/4"
3/8"
Flare nut (3/8") 7
Joint (1/2"
3/8") 5
Tool
A
R410A tool
0 - 0.5 mm
Conventional tool 1.0 - 1.5 mm

Advertisement

loading

Summary of Contents for Sharp AU-X3M24RV

  • Page 1 Carefully read and follow these instructions for MULTI SPLIT TYPE ROOM AIR CONDITIONER B508 smooth and trouble-free installation. AU-X3M24RV INSTALLATION MANUAL ENGLISH This manual describes the installation of outdoor unit only OUTDOOR UNIT INSTALLATION For the installation of the indoor unit, see the installation manual accompanying indoor unit.
  • Page 2 AIR REMOVAL WIRE CHECK Miswiring of connecting cable will be self-corrected by the wire check operation. Perform air removal using a vacuum pump. Use a vacuum pump, gauge manifold and hoses exclusively for R410A. (1) Turn the circuit breaker on. Gauge manifold (1) Remove both valve shaft caps of the stop valves.