• Ref No: NISM/EV-UV/01
• Date: 16.04.09 • Issue: 1
• evolution
• EV-UV
NITTAN (UK) LTD. Hipley Street, Old Woking, Surrey, England, GU22 9LQ. UK
Tel: +44 (0) 1483 769555 • Fax: +44 (0) 1483 756686
Web Site: www.nittan.co.uk • E-mail: sales@nittan.co.uk
ultraviolet flame
• analogue addressable ultraviolet flame sensor instruction manual
Quality System Certificate No. 041
Assessed to BS EN ISO 9001:2000
EV-UV
analogue
addressable
instruction manual
sensor

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Evolution EV-UV and is the answer not in the manual?

Questions and answers

Summary of Contents for Nittan Evolution EV-UV

  • Page 1 Quality System Certificate No. 041 Assessed to BS EN ISO 9001:2000 NITTAN (UK) LTD. Hipley Street, Old Woking, Surrey, England, GU22 9LQ. UK Tel: +44 (0) 1483 769555 • Fax: +44 (0) 1483 756686 Web Site: www.nittan.co.uk • E-mail: sales@nittan.co.uk...
  • Page 2 The EV-UV analogue addressable flame sensor forms part of a range of analogue addressable fire sensors from Nittan (UK) Ltd called evolution. The EV-UV together with the EV-PH, EV-H, EV-P and EV-DP are all elegantly designed, low profile fire sensors which are aesthetically pleasing, thus enabling them to blend unobtrusively into modern working environments.
  • Page 3: Table Of Contents

    Section 1 - INTRODUCTION Section 1 Introduction Page 3 The EV-UV is an attractively-styled, low profile ultraviolet flame sensor for use with Nittan 'evolution' protocol control panels. Section 2 The EV-UV utilises the ultraviolet light detection method. Sensor models Page 3...
  • Page 4: Location

    • Ref No: NISM/EV-UV/01 • Date: 16.04.09 • Issue: 1 • evolution advanced • EV-UV • analogue addressable ultraviolet flame sensor instruction manual Section 4 - LOCATION Note: Use correct sensitivity position. See Section 12 on page 5 for more details on positioning. i) Determine suitable mounting location according to supervision angle, and effective detection range.
  • Page 5: Maintenance

    • Ref No: NISM/EV-UV/01 • Date: 16.04.09 • Issue: 1 • evolution advanced • EV-UV • analogue addressable ultraviolet flame sensor instruction manual Section 6 - MAINTENANCE AND CLEANING Maintenance: The EV-UV detector is a high quality product engineered for reliability.
  • Page 6: Cleaning

    Nittan (UK) Ltd. for service. Technical Manual: EV-UV - 000023 (Changes are subject to DCRN)
  • Page 7: Specifications

    • Ref No: NISM/EV-UV/01 • Date: 16.04.09 • Issue: 1 • evolution advanced • EV-UV • analogue addressable ultraviolet flame sensor instruction manual Section 7 - SPECIFICATIONS Model Reference: - EV-UV Computer Reference: - F16J71005 Sensing Wavelength: - 185 - 260nm Detection Angle: - 100 degrees Sensor Type:...
  • Page 8: Connections

    • Ref No: NISM/EV-UV/01 • Date: 16.04.09 • Issue: 1 • evolution advanced • EV-UV • analogue addressable ultraviolet flame sensor instruction manual Section 10 - CONNECTIONS Auxiliary terminal RIL current limited to 2mA. Section 11 - DIMENSIONS 43 mm 27 mm 20 mm 2.8 x 6 mm...
  • Page 9: Area Coverage

    • Ref No: NISM/EV-UV/01 • Date: 16.04.09 • Issue: 1 • evolution advanced • EV-UV • analogue addressable ultraviolet flame sensor instruction manual Section 12 - AREA COVERAGE Fig. 1. shows the area coverage of an EV-UV detector when mounted at a height of 10 metres on a ceiling. The approximate area coverage is 340 square metres.
  • Page 10 • Ref No: NISM/EV-UV/01 • Date: 16.04.09 • Issue: 1 • evolution advanced • EV-UV • analogue addressable ultraviolet flame sensor instruction manual FIG. 3. FIG. 4. The EV-UV sensor may be positioned in two ways. Each way determines the distance and area coverage of a single detector.
  • Page 11: Disposal

    • Ref No: NISM/EV-UV/01 • Date: 16.04.09 • Issue: 1 • evolution advanced • EV-UV • analogue addressable ultraviolet flame sensor instruction manual Section 13 - DISPOSAL This symbol on the EV-UV indicates that this product must not be disposed of with household waste. Instead, it is your responsibility to dispose of your waste equipment by handing it over to a designated collection point for the recycling of waste electrical and electronic equipment.
  • Page 12: Flameproof Housing

    Section 15 - FLAMEPROOF HOUSING The EV-UV detector may also be used with the NITTAN NFD-FPH Flameproof housing. The NFD-FPH is for use in areas made potentially hazardous by the presence of flammable liquids or vapours (zone 1 or zone 2).

Table of Contents