PELLET STOKER KMP PX50 Content Description Description ................3 The KMP stoker is designed to be installed in a boiler and is to be fired with wood- en pellets. The attached screw feeds pellets from a barrel or similar, alternatively a Fitting ................
Fitting Screw feeder Allways observe the following: The PX50 stoker is to be mounted to one of the boiler hatches. The best place is • The feeder inlet opening is not to be less than 100 mm from the bottom often where the oil burner normally goes, but if there is not sufficient room for 150 mm from the nearest side wall of the storage bin.
Page 4
PELLET STOKER KMP PX50 Pellet storage The combustion chamber The storage is to be designed in a Clearance between the top of the stoker and the inside of the combustion chamber fashion that the amount of dust is to be minimum 50 mm, and at least 150 mm in front of the aperture.
PELLET STOKER KMP PX50 Electric installation Electric circut diagram All electric connections on the stoker and screw feeder have fast action connectors Terminal block on PC-card as below 10 11 12 13 14 15 16 17 18 19 20 1. To boiler temperature sensor 2.
PELLET STOKER KMP PX50 Start and setting If the boiler has been fired with wood earlier, the smoke can be dark and smelly because of the combustion of tar on the boiler walls. First start Note! The blaze normally varies in colour (dark and light yellow) even when burn- The stoker is not shipped with a basic setting for normal conditions.
However, the cost of installing a new storage tank is normally not profitable due to where the sensor can be attached conveniently. A special storage tank control unit is the extremely high thermal efficiency of the PX50 stoker. as extra accessories.
Note that all cables have to be unplugged before removing the cover. Safety systems The PX50 stoker meets all current safety regulations and standards. There are two separate safety systems to avoid fire and hot gases going backwards: a slooping stainless steel tube for the pellet feeder, and a cut-out thermostat on the tube.
Page 9
PELLET STOKER KMP PX50 NOTE! Changing light sensor All work as described in the following text must be done by a qualified 1. Disconnect all three cables on the stoker. person. 2. Remove the three brass nuts holding the cover, and pull the cover backwards.
Page 10
PELLET STOKER KMP PX50 Troubleshooting and repair Fault Cause What to do Fault Cause What to do Stoker has stopped, • Burner has been overheated. Clean out ashes from burner and Stoker ignites • To large start dose, or feeding...
PELLET STOKER KMP PX50 Exploded view / Technical data Technical data Dimensions outside boiler (b x h x d) ..300 x 310 x 300 mm Dimensions inside boiler (Ø x l) ......Ø180 x 200 mm Efficiency ..............ca 95% Output maximum ............
PELLET STOKER KMP PX50 Warranty For warranty issues Ariterm Sweden AB refers to our local Distributor. ARITERM SWEDEN AB Installation Instructions - 2007.12.14 - 12/16...
PELLET STOKER KMP PX50 Installation certificate Installed product: Pellet stoker type PX50 (Customers copy) Serial number: ........Date of installation: ......Chimney draught (cold): ....Pa Temperature outside: ......°C Flue gas temperature (max power): ... °C CO2 content: ......% Chimney draught (hot): .....
Page 15
PELLET STOKER KMP PX50 Installation certificate Installed product: Pellet stoker type PX50 (Sellers copy) Serial number: ........Date of installation: ......Chimney draught (cold): ....Pa Temperature outside: ......°C Flue gas temperature (max power): ... °C CO2 content: ......% Chimney draught (hot): .....
Page 16
If these instructions are not followed during installation, operation and maintenance, the obligations of Ariterm Sweden AB under the warranty regulations are no longer binding. Ariterm reserve the right to alter any details and specifications without prior notice. Ariterm Sweden AB Flottiljvägen 15, SE-392 41 Kalmar...
Need help?
Do you have a question about the PX50 and is the answer not in the manual?
Questions and answers