Installation and wiring
Mounting the detector
Gas detector for monitoring of flammable gases and leakages of toxic gases should be installed close to
potential sources of release. For gases heavier than air below and for gases lighter than air above the
source of release. Detectors for monitoring at working places are installed at face / respiration level.
When deciding on the position for the transmitter, make sure that it is always accessible for service and
maintenance.
Mechanical mounting
Gas detector is attached to the wall via 4 mounting screws. Sensor opening to be placed downwards. Drill
4 holes according to the drilling diagram.
Drilling diagram:
Electrical connections
The electrical connection must be carried out by a specialist and (with the controller) with the power
supply disconnected.
7