TYPES CM...N SM...N MM...N
AUTOMATIC CONTROL SYSTEMS FOR
GAS BURNERS AND GAS BURNING
APPLIANCES WITH OR WITHOUT FAN
(MANUAL RESET)
15756_r02
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวี ว ั ฒ นา กทม. 10170.
website:
https://www.add-furnace.com/
Line ID: @add11 e-mail: add028883472@gmail.com
DESCRIPTION
This series of electronic systems is suitable to control
atmospheric gas burners for non-permanent operation with
or without fan in the combustion circuit.
All control units are provided with non-volatile lockout, i.e.
restart from the safety shutdown condition can only be
accomplished by manually resetting the system.
The control units of this series are suitable for:
- combi boilers
- heating boilers
- hot air generators
- radiant tube heaters
- water heaters.
Their technical and manufacturing characteristics and the
variety of models make them suitable also for
automation of ovens, cookers, stoves and, more generally,
for gas firing appliances equipped with atmospheric burner.
FEATURES
Table 1 shows the main features of this series.
Other important features are mentioned below:
EC type examination certificate (EC Reg. no. 51BT3691)
in accordance with the European Gas Appliance
Directive 90/396 and the following amendment 93/68;
in compliance with EN298:2003 (European standard for
automatic gas burner control and flame detection
systems);
flame detection exploiting the flame rectification effect
(ionization);
two independent safety contacts in series on the gas
valve output;
electrical service life at max declared loading > 250.000
operations;
inbuilt manual reset; some models can be provided with
remote reset;
incorporated highly efficient and completely solid-state
design ignition device;
 auxiliary contact for low-power ignition or main valve
control for intermittent pilot systems (this is not a SELV
contact and is therefore not suitable to control circuits
type SELV – Safety Extra Low Voltage, e.g. 24V –);
different connection and fixing possibilities.
โทร: 02-888-3472
the
1/6

Advertisement

loading

Summary of Contents for BRAHMA EUROBOX Series

  • Page 1 44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวี ว ั ฒ นา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: add028883472@gmail.com EUROBOX SERIES TYPES CM...N SM...N MM...N AUTOMATIC CONTROL SYSTEMS FOR GAS BURNERS AND GAS BURNING APPLIANCES WITH OR WITHOUT FAN...
  • Page 2: Technical Data

    44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวี ว ั ฒ นา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: add028883472@gmail.com BURNER OPTIONS RESET CONNECTION TABLE 1 CM191N AMCLXN SM191N AMCLXN SM192N AMCLXN CM381N FMCLXN CM391N FMCLXN SM152N AMCLXN SM592N AMCLXN MM191N AMCLXN...
  • Page 3: Overall Dimensions

    CM381. Socket type P differs from type R on positions 8 and 10 The EUROBOX series burner control units can be provided with a for the availability of through holes to suit female fast-on terminals different casing according to the characteristics and fixing systems of standard type.
  • Page 4 44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวี ว ั ฒ นา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: add028883472@gmail.com A ventilated installation environment and a suitably low fault in the amplifier leading to flame simulation prevent the control temperature ensure the longest life of the control system....
  • Page 5: Connection Diagrams

    44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวี ว ั ฒ นา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: add028883472@gmail.com CONNECTION DIAGRAMS TYPE CM191N TYPE CM391N TYPE SM191N TYPE SM192N SM152N TYPE MM191N TYPE MM192N TYPE CM381N TYPE SM592N THERMOSTAT AIR PRESSURE FUSE...
  • Page 6 THERMOSTAT AIR PRESSURE IGNITION FLAME LOCKOUT FIRST SECOND AUXILIARY EXTERNAL IGNITION SWITCH DEVICE SIGNAL SIGNAL GAS VALVE GAS VALVE CONTACT TRANSFORMER ATTENTION -> Company Brahma S.p.A. takes no responsibility for any damage resulting from Customer's tampering with the device. 15756_r02...

This manual is also suitable for:

Cm191nSm191nSm192nCm381nCm391nSm152n ... Show all