NEMA Type 7/9 Disconnect Switch
Installation & Maintenance Information
APPLICATION
Eaton's NEMA Type 7/9 Disconnect Switches are suited for Class I, Divisions
1 & 2, Groups B, C, D; Class II, Division 1, Groups E, F , G; Class II, Division 2,
Groups F , G; Class III; and Class I, Zones 1 & 2, Groups IIB + H
the National Electrical Code
®
as well as in damp, wet or corrosive locations.
INSTALLATION
To avoid risk of electrical shock, electrical power must be OFF before
and during product installation and maintenance. Failure to comply can
result in damage to equipment, injury or death to personnel.
1.
Select a mounting location that will provide suitable strength and rigidity
for supporting the Eaton's NEMA Type 7/9 Disconnect Switch. Weights
and dimensions are listed below.
A
B
Series
in
mm
in
mm
DS361UX
9.74
247
5.00
127
DS362UX
9.90
251
7 .00
178
DS363UX
10.28
261
9.00
229
DS361FX
10.02
255
7 .00
178
DS362FX
9.90
251
7 .00
178
DS363FX
10.40
264
15.00
380
2.
Securely fasten enclosure to the mounting location, and then attach
enclosure into conduit system. Install approved conduit or cable sealing
fittings in all conduit entries within 18 inches (46cm) of enclosure per the
National Electrical Code requirements.
To avoid risk of explosion, hazardous location information specifying
Class and Group listing of each device is marked on the nameplate of
each enclosure. Class and Group list for and device penetrating the
enclosure must be suitable for the classification of location in which the
enclosure is installed. Conduit sealing fittings MUST be installed in each
attached conduit run within 18 inches of the enclosure per the National
Electrical Code.
3.
For Eaton's NEMA Type 7/9 Disconnect Switch enclosures furnished
with disconnect switch, please view Step 4. For Eaton's NEMA Type 7/9
Disconnect Switch enclosures furnished without disconnect switch, select
appropriate disconnect switch from Table 2 below (ordered separately).
Series
Amperage
DS361UX
30A
DS362UX
60A
DS363UX
100A
DS361FX
30A
DS362FX
60A
DS363FX
100A
IF 1772 • 11/15
SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE
WARNING
ONLY DS363FX
Figure 1
Table 1
C
D
E
in
mm
in
mm
in
mm
10.47
266
11.13
283
12.47
317
12.53
318
15.13
384
16.53
420
14.67
373
17 .13
435
18.67
474
12.67
322
13.13
333
14.67
373
12.53
318
15.13
384
16.53
420
17 .31
440
11.50
292
23.31
592
CAUTION
Table 2
Switch Type
Manufacturer
EATON
Non-fusible
EATON
EATON
EATON
Fusible
EATON
EATON
Copyright
Additionally, this series is suitable for NEMA 3, 4, 4X applications. Eaton's
NEMA Type 7/9 Disconnect should be installed, inspected, maintained and
operated by qualified and competent personnel only.
, as defined by
2
a. Using hardware provided, securely mount disconnect switch on
mounting plate with "Line" terminals on top and "Load" terminals on
bottom. Use existing holes in mounting plate; please refer to mounting
plate drawing below. Be sure to tighten screws to 3 ft.-lbs. (0.4 Kg.-m.).
b. The rating for each disconnect can be observed in Table 3.
Table 3 Fusible and Non-fusible Switches, 3-pole 600 VAC Max., 250 VDC Max.
Mfr.'s
F
Weight
Part #
in
mm
Ib
Kg
DS16U
3.50
89
33
15
DS26U
3.50
89
51
23
DS36U
3.50
89
72
33
DS161R
3.50
89
47
21
DS262R
3.50
89
51
23
DS363R
3.50
89
108
49
4.
Ensure the operator is in the OFF position and then remove the cover
bolts while securing cover. Carefully open the cover fully to prevent
damage to the machined joint flame path and cover gasket.
To avoid the risk of explosion, hammers or prying tools must
not be allowed to damage the flat machined joint surfaces or cover
gasket. Do not handle covers roughly or place them on surfaces that
might damage or scratch the flat machined joint surfaces.
To avoid the risk of explosion, do not use cover bolts as a means to
lift the enclosure. Excessive force on the partially retracted cover bolts
may damage the bolt. Use appropriate lifting method for safety.
5.
Pull wires into enclosure, making sure they are long enough to make
the required electrical connections. Install the proper wire clamps or
other approved devices to hold the wires securely in place. Install the
ground, line and load wires. Tighten the wire binding screws to torque
Mfr.'s Part #
values shown on Table 4.
DS16U
Note:
DS26U
a. The internal grounding terminal shall be used as equipment
DS36U
grounding means. The external terminal is only a supplemental bonding
DS161R
connection.
DS262R
DS363R
2015, Eaton's Crouse-Hinds Division
©
Mounting Plate Drawing
Figure 2
Maximum Horsepower Rating
Ampere
Fuse
480 VAC
Rating
Type
30
15
60
N/A
30
100
60
30
15
60
Class J
30
100
60
CAUTION
CAUTION
IF 1772
600 VAC
250 VDC
Voltage
20
5
50
10
600 VAC,
75
20
125/250
20
5
VDC
50
10
75
20
Page 1

Advertisement

loading

Summary of Contents for Eaton CROUSE-HINDS Series

  • Page 1 Installation & Maintenance Information SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE APPLICATION Additionally, this series is suitable for NEMA 3, 4, 4X applications. Eaton’s NEMA Type 7/9 Disconnect should be installed, inspected, maintained and operated by qualified and competent personnel only.
  • Page 2 All statements, technical information and recommendations contained herein are based on information and tests we believe to be reliable. The accuracy or completeness thereof are not guaranteed. In accordance with Eaton’s Crouse-Hinds Division’s “Terms and Conditions of Sale,” and since conditions of use are outside our control, the purchaser should determine the suitability of the product for his intended use and assumes all risk and liability whatsoever in connection therewith.

This manual is also suitable for:

Nema 7Nema 9