Summary of Contents for IBA BM-DIS-i-8o

  • Page 1 ibaBM-DIS-i-8o Data distributor Manual Issue 1.2...
  • Page 2 However, the information in this publication is updated regularly. Required corrections are contained in the following regulations or can be down- loaded on the Internet. The current version is available for download on our web site http://www.iba-ag.com. Protection note ®...
  • Page 3: Table Of Contents

    ibaBM-DIS-i-8o Manual Table of contents About this manual ................... 5 Target group ....................5 Designations ....................5 Used symbols ....................6 Safety instructions ..................7 Designated use ....................7 Designated environment of use ..............7 Special safety advice ..................7 Scope of delivery ....................
  • Page 4 Manual ibaBM-DIS-i-8o Support and contact ..................21 Issue 1.2...
  • Page 5: About This Manual

    ibaBM-DIS-i-8o Manual About this manual This manual describes the construction, the use and the operation of the device ibaBM-DIS-i-8o. Target group This manual addresses in particular the qualified professionals who are familiar with handling electrical and electronic modules as well as communication and measurement technology.
  • Page 6: Used Symbols

    Manual ibaBM-DIS-i-8o Used symbols If safety instructions or other notes are used in this manual, they mean: The non-observance of this safety information may result in an imminent risk of death or severe injury:  By an electric shock!  Due to the improper handling of software products which are coupled to input and output procedures with control function! If you do not observe the safety instructions regarding the process and the system or...
  • Page 7: Safety Instructions

    The device is electrical equipment. It may be used only in the following applications:  Automation of industrial systems  Measurement data logging and analysis  Applications of iba software products (ibaPDA, ibaLogic etc.) and iba hardware products The device must not be operated in mains supply circuits!
  • Page 8: Product Properties

    Manual ibaBM-DIS-i-8o Product properties Description The device ibaBM-DIS-i-8o is a member of iba’s device family for distribution of signals via fiber optic cables. The device can be operated in several modes:  Copy mode  Distribution mode  Copy and cut mode Modes of operation 4.2.1...
  • Page 9: Distribution Mode

    ibaBM-DIS-i-8o Manual 4.2.2 Distribution mode In distribution mode 1 incoming fiber optic data stream, transmitted at 32 Mbit/s and containing 512 analog and 512 digital signals, is split into 8 fiber optic output streams, containing 64 analog and 64 digital signals each and transmitted at 3.3 Mbit/s. An additional output provides for a mirrored input data stream.
  • Page 10: Certificates

    Manual ibaBM-DIS-i-8o Certificates The device is certified according to:  CE  FCC (Class B) Device views 4.4.1 Front view Operating status indicators L1 … L4 On/off switch (S11) Connector for power supply 24 V X14 Rotary switch S1 Connection FO input (RX) X10 Connection FO output (TX) X11 Connection FO outputs (TX) X34 …...
  • Page 11: Top View

    Manual 4.4.2 Top view Manufacturer: iba AG Support: iba@iba-ag.com Internet: www.iba-ag.com Certification: CE, FCC (Class B) Power supply: DC 24 V, ±10 %; 0.2 A Product name: ibaBM-DIS-i-8o Figure 4: Top view 4.4.3 Bottom view Connectors on the device bottom:...
  • Page 12: Indicators

    Manual ibaBM-DIS-i-8o Indicators Different colored LEDs indicate the device status. Device status Status Description L1: Green Blinking Ready for operation, power supply is on Out of order, no power supply L2: Yellow On A valid 2.0 Mbit/s, 3.3 Mbit/s or 5.0 Mbit/s signal has been de- tected No signal detected or 32 Mbit/s L3: White On...
  • Page 13: Principle Diagram

    ibaBM-DIS-i-8o Manual Position Mode Description Copy and cut mode Input: 32 Mbit/s Outputs: 8 x 3.3 Mbit/s (INT/REAL) Input cycle time ≥ 100 µs: the first 256 bytes of analog data (any data type) and the first 8 bytes of digital data are transmitted Input cycle time <...
  • Page 14: Operation

     ibaNet fiber optic (FO) connections and cabling  In copy mode: Input: Any iba device with ibaNet FO output Outputs: Any iba device with ibaNet FO input (some restrictions apply)  In distribution mode: Input: iba devices with 32 Mbit/s FO output Outputs: iba devices with 3.3 Mbit/s FO input...
  • Page 15 5.2.1.2 Multiplication of synchronization signals If synchronous sampling of many iba field devices (e. g. single or interconnected iba- PADU-8) in a large scale installation is required, the devices can be synchronized by means of an ibaBM-DIS-i-8o. One FO telegram is multiplied with the ibaBM-DIS-i-8o and serves as synchronous source for all FO links.
  • Page 16: Distribution Mode

    5.2.2.1 Distribution of signals of a 32 Mbit/s data stream If the output signals of an iba device with 32Mbit ibaNet protocol should be transmitted and distributed to ibaPADU-8-O or ibaNet750 devices then up to 8 FO links (3.3 Mbit/s) can be supplied with data.
  • Page 17: Installation, Connection, Disassembly

    ibaBM-DIS-i-8o Manual Installation, Connection, Disassembly Installation 1. Insert the clip of the mounting rail fastened on the device into the mounting rail. 2. Press the device down in such a way that the clip of the mounting rail engages with a click.
  • Page 18: Technical Data

    Indicators 4 LEDs (operating status) Operating elements Rotary switch (operation mode) Compliant devices In copy mode: Input Any iba device with an FO output link Output Any iba device with FO input link (some restrictions ap- ply) Issue 1.2...
  • Page 19 Manual In distribution and copy and cut mode: Input iba devices with 32 Mbit/s FO output, e.g. ibaFOB-D cards, ibaBM-COL-8i-o, ibaBM-DPM-S Output iba devices with 3.3 Mbit/s FO input, e. g. ibaNet750-BM Operating and environmental conditions Installation Mounting rail according to DIN EN 60715...
  • Page 20: Dimension Sheet

    Manual ibaBM-DIS-i-8o Dimension sheet (Dimensions given in mm) Figure 11: Dimension sheet Issue 1.2...
  • Page 21 Koenigswarterstr. 44 90762 Fuerth Germany Phone: +49 911 97282-0 Fax: +49 911 97282-33 E-Mail: iba@iba-ag.com Contact: Mr. Harald Opel Regional and Worldwide For contact data of your regional iba office or representative please refer to our web site www.iba-ag.com. Issue 1.2...