Maintenance

<Daily maintenance>
Be sure to stop the air conditioner before cleaning of air
filter, then turn off the circuit breaker.
Take out the air filter.
• Push down hook of the air filter on the front
panel (Lower side).
• Pull the air filter toward you to remove it.
Front panel (Lower)
Air filter knob
• Cleaning with water or vacuum cleaner
• If dirt is heavy, clean the air filter by tepid
water with neutral detergent or water.
• After cleaning with water, dry the air filter
sufficiently in a shade place.
• Mount the air filter.
CAUTION
CAUTION
Do not start the air conditioner while leaving air filter
removed.
35-EN
Periodic Maintenance
For environmental conservation, it is strongly recommended that the indoor and outdoor units of the air conditioner
in use be cleaned and maintained regularly to ensure efficient operation of the air conditioner.
When the air conditioner is operated for a long time, periodic maintenance (once a year) is recommended.
Furthermore, regularly check the outdoor unit for rust and scratches, and remove them or apply rustproof
treatment, if necessary.
As a general rule, when an indoor unit is operated for 8 hours or more daily, clean the indoor unit and outdoor unit at
least once every 3 months. Ask a professional for this cleaning / maintenance work.
Such maintenance can extend the life of the product though it involves the owner's expense.
Failure to clean the indoor and outdoor units regularly will result in poor performance, freezing, water leakage, and
even compressor failure.
Inspection before maintenance
Following inspection must be carried out by a qualified installer or qualified service person.
Parts
Access from inspection opening and remove the access panel. Examine the heat
Heat exchanger
exchanger if there is any clogging or damages.
Fan motor
Access from inspection opening and check if any abnormal noise can be heard.
Access from inspection opening and remove the access panel. Examine the fan if there
Fan
are any waggles, damages or adhesive dust.
Filter
Go to installed location and check if there are any stains or breaks on the filter.
Access from inspection opening and remove the access panel. Check if there is any
Drain pan
clogging or drain water is polluted.
Maintenance List
Parts
Unit
Heat exchanger
Indoor / Outdoor
Fan motor
Indoor / Outdoor
Filter
Indoor
Fan
Indoor
Air intake /
Indoor / Outdoor
discharge grilles
Drain pan
Indoor
Ceiling panel,
Indoor
louvres
Exterior
Outdoor
– 18 –
Inspection method
Check (visual / auditory)
Maintenance
Dust / dirt clogging,
Wash the heat exchanger when it is
clogged.
scratches
Take appropriate measures when
Sound
abnormal sound is generated.
• Wash the filter with water when it is
contaminated.
Dust / dirt, breakage
• Replace it when it is damaged.
• Replace the fan when vibration or balance
• Vibration, balance
is terrible.
• Dust / dirt, appearance
• Brush or wash the fan when it is
contaminated.
Fix or replace them when they are
Dust / dirt, scratches
deformed or damaged.
Dust / dirt clogging, drain
Clean the drain pan and check the
downward slope for smooth drainage.
contamination
Wash them when they are contaminated or
Dust / dirt, scratches
apply repair coating.
• Rust, peeling of insulator
Apply repair coating.
• Peeling / lift of coat
36-EN