INTRODUCTION
Thank you for choosing an HK Instruments MM Series liquid col-
umn manometer. The MM Series is intended for use in commercial
environments for air and non-corrosive gases. The MM Series is
designed with overpressure reservoir to protect the manometer
liquid from leaking into the duct during over pressure.
The MM Series includes a field adjustable zero point calibration
and pressure limit stickers. The MM Series is available with op-
tional level bubble and NIST standard calibration certificates.
APPLICATIONS
MM series devices are commonly used in HVAC/R systems for:
• fan, blower and filter monitoring
• pressure and flow monitoring
• pressure monitoring in cleanrooms
SPECIFICATIONS
Performance
Accuracy:
MM-0202
±0.004 inWC
MM-04
±0.004 inWC
MM-0420
-0.4–0 inWC
±0.02 inWC
0–2.0 inWC
±0.1 inWC
MM-00824
0–0.8 inWC
±0.02 inWC
0.8–2.4 inWC
±0.1 inWC
Overpressure:
Max Pressure: 800 inWC (200 kPa)
Copyright HK Instruments, Inc. 2017
DIFFERENTIAL PRESSURE GAUGES
& MANOMETERS – MM Series
• READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING TO
• Failure to observe safety information and comply with instructions can result in
• To avoid electrical shock or damage to equipment, disconnect power before
• To avoid potential fire and/or explosion do not use in potentially flammable or
• Retain these instructions for future reference.
• This product, when installed, will be part of an engineered system whose
• LISEZ ATTENTIVEMENT CES INSTRUCTIONS AVANT DE PROCÉDER À
• Le non-respect des informations et instructions de sécurité peut entraîner DES
• Afin d'éviter les chocs électriques et les dommages matériels, déconnectez
• Afin de prévenir les risques d'incendie et/ou d'explosion, n'utilisez pas l'appareil
• Conservez ces instructions à titre de référence.
• Une fois installé, ce produit fera partie d'un système technique dont les
Technical Specifications
Media Compatibility:
Dry air or non-aggressive gases
Measuring units:
inWC
Measuring ranges:
-0.2–0–0.2 inWC
0–0.4 inWC
-0.4–0–2.0 inWC
0–0.8–2.4 inWC
Environment:
Operating temperature:
-40–140 °F (-40–60ºC)
Gauge fluid:
Red: s.g. 49.068 lb/ft3 (0.786 kg/dm
(Isopar M)
MM-0202 RED
MM-04 RED
MM-0420 RED
MM-00824 RED
www.hkinstrumentsinc.com
WARNING
INSTALL, OPERATE OR SERVICE THIS DEVICE.
PERSONAL INJURY, DEATH AND/OR PROPERTY DAMAGE.
installing or servicing and use only wiring with insulation rated for full device
operating voltage.
explosive atmospheres.
specifications and performance characteristics are not designed or controlled
by HK Instruments. Review applications and national and local codes to assure
that the installation will be functional and safe. Use only experienced and
knowledgeable technicians to install this device.
AVERTISSEMENT
L'INSTALLATION, LA MISE EN SERVICE OU L'ENTRETIEN DE CET APPAREIL.
DOMMAGES CORPORELS, LA MORT ET/OU DES DÉGÂTS MATÉRIELS.
l'alimentation électrique avant l'installation ou l'entretien, et utilisez uniquement du
câblage avec isolement assigné pour une tension d'alimentation optimale.
dans des environnements potentiellement inflammables ou explosifs.
spécifications et les caractéristiques de performance ne sont ni conçues ni
contrôlées par HK Instruments. Consultez les applications et les codes nationaux
et locaux pour garantir le fonctionnement correct et sûr de l'installation. Ne faites
appel qu'à des techniciens expérimentés et compétents pour installer cet appareil.
Physical
Case:
ABS
Cover:
PMMA
Knobs:
Polycarbonate (PC)
O-ring:
Nitrile rubber (NBR)
Weight
14.82 oz (420 g)
Safety
Product equipped with integral reservoir to prevent
) (15 °C)
gauge fluid leakage during overpressure situation.
3
Product is tested and meets the NRTL product approval
requirements.
COMPANY WITH
MANAGEMENT SYSTEM
CERTIFIED BY DNV GL
= ISO 9001 = ISO 14001 =
INSTALLATION
INSTRUCTIONS
RoHS 2
2011/65/EU
Installation version 2.0 2017

Advertisement

loading

Summary of Contents for HK Instruments MM Series

  • Page 1 & MANOMETERS – MM Series INTRODUCTION WARNING Thank you for choosing an HK Instruments MM Series liquid col- • READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING TO INSTALL, OPERATE OR SERVICE THIS DEVICE. umn manometer. The MM Series is intended for use in commercial •...
  • Page 2 3) Connect the pressure tubes. Connect positive pressure to port labeled “+” and negative pressure to port “-”. NOTE! Only use gauge fluid approved by HK Instruments to guaran- tee accuracy and functionality of the device. Copyright HK Instruments, Inc. 2017 www.hkinstrumentsinc.com...

This manual is also suitable for:

Mm-0202Mm-04Mm-0420Mm-00824