Bushing Preparation - GE PHI 530.1425.2500 Operating And Maintenance Instructions Manual

Hvdc transformer bushings
Table of Contents

Advertisement

Bushing type
Ambient conditions:
Max valve hall temperature
Min valve hall temperature
Max transformer oil temperature
Pollution condition
Indoor
Minimum creepage distance
Indoor
Minimum arcing distance
Indoor
Seismic condition
Altitude above sea level (up to)
Installation angle
5

Bushing preparation

All operators involved in components unpacking and assembly have to be careful not to damage the objects.
During the unpacking operation, it is necessary to check that all components supplied by GE Energy
Connections RPV are available and not damaged during the transportation.
All incoming goods must be stored in a covered area and prepared for the installation.
At the arrival, the crate must be inspected. Any damage of the crate or indication of the visual external shock
indicator (see Figure 3) must be reported to the Foreman and GE Energy Connections RPV Supervisor.
A detailed control check list is listed in Table 4 at Paragraph 5.2.
HVDC TRANSFORMER BUSHINGS
PHI 530.1425.2500
PHI 265.850.1500
Kepco project
Table 3 – Environmental conditions
Figure 3 – Visual external shock indicator
PHI 530.1425.2500
PHI 265.850.1500
+ 50
+5
+85
Very low
>10080
>4728
0.225
<1000
23° -33°
IS 2664 GB
Page 9 of 70
+ 50
° C
+5
° C
+85
° C
Very low
>4125 mm
>2994 mm
0.225 g
<1000 m
23-° 40° From horizontal