TEF 4600 CONTROL SYSTEM - INSTALLATION AND USER MANUAL TABLE OF CONTENTSNTS: INTRODUCTION APPLICATIONS CONTENT IN BOX SAFETY PRECAUTIONS ABOUT THE SYSTEM TERMINAL CONNECTIONS CONFIGURATION STATUS LIGHTS 7.1.1 Enable Installed Lights 7.1.2 Status Light Automatic Test: 7.1.3 Status Light On Timeout 7.1.4 Status Light Dim Timeout...
Activation timeout will deactivate the Status light system when the timer has elapsed. Default value is 30 minutes. The TEF 4600 control cabinet shall be stored in a dry The Button will be green when Enabled. place. Storage temperature range (non-condensing): -10°C to +55°C...
TEF 4600 CONTROL SYSTEM - INSTALLATION AND USER MANUAL CONFIGURATION CIRCLE & H 7.2.1 Adjustment of the «BRIGHT» light level The “bright” light level can be adjusted up to twice the intensity specification of “standard” level. The purpose of this facility is to ensure adequate performance at installa- tions with high levels of background lighting without risk- ing glare at less well-lit installations.
TEF 4600 CONTROL SYSTEM - INSTALLATION AND USER MANUAL OPERATION 10.1 Control Screen The Control Screen contains control and monitoring of The available lights to control are: Helideck lights. Each button controls one light circuit. Helideck lights: Turn on/off all Helideck lights. (Flood- The circuits are toggled on and off by pressing and hold- lights Dim and Circle &...
TEF 4600 CONTROL SYSTEM - INSTALLATION AND USER MANUAL 10.2 Status Light Screen The Status light screen contains control and monitoring of the Status light system. 10.2.1 Suppress The Suppress function is activated/deactivated by pressing and holding the Suppress button for 4 seconds.
TEF 4600 CONTROL SYSTEM - INSTALLATION AND USER MANUAL 10.2.2 Activate (Manual activation) 10.2.6 Inspection Interval The Activate function is activated/deactivated by press- Inspection interval is a time span of days which, when ing and holding the Activate button for 2 seconds.
TEF 4600 CONTROL SYSTEM - INSTALLATION AND USER MANUAL 10.3 Setup screen, page 1 10.3.1 Activate Modbus TCP If Modbus TCP is used for control and monitoring with external control system this function is activated here. For new connection, disable Modbus, enter IP-address of Client, and finally enable Modbus again.
TEF 4600 CONTROL SYSTEM - INSTALLATION AND USER MANUAL 10.3 Setup screen, page 2 10.3.3 Internal Horn Audible Alarm. This function will enable/disable the internal buzzer of the HMI touch panel. When enabled the buzzer will acti- vate when an alarm is present.
TEF 4600 CONTROL SYSTEM - INSTALLATION AND USER MANUAL 10.3 Setup screen, page 3 10.3.5 Local Remote Mode Enable 10.3.6 Panel is local If there are two touch panels or one touch panel and Enable this if the Panel is local.
TEF 4600 CONTROL SYSTEM - INSTALLATION AND USER MANUAL 10.3 Setup screen, page 4 10.3.8 Enable lights for function “All Helidecks Lights on” This setup page dictates which light circuits are enabled for the function “All Helideck Lights On”. F. ex if Flood lights are to be exempt from the “All helideck lights on”...
TEF 4600 CONTROL SYSTEM - INSTALLATION AND USER MANUAL 10.4 Alarms Screen The Alarms Screen contain information of Alarms that are currently active or acknowledged. An Alarm will blink when raised and unacknowledged. • Ack Sel will acknowledge selected alarm.