COMPACT 3.0
• Verify the load by checking the pressure; if it is below 0.5 bars or above 5.0 bars
with the unit running, recover the load in the faulty circuit and empty for at least 30
minutes, then introduce 330 g.
• Check and correct the condenser fan cable clamp connection.
• Clean the capacitor with pressurised air.
• Replace the condenser fan.
• Check the pressure; if it is below 0.5 bars with the unit running, clean the faulty
circuit or replace obstructed components (possibly the continuous flow capillary
tube, as this is the component with least diameter).
!
In many cases, gas recovery will not be exact since part of the gas remains
in the recovery circuit.
Solution
25
EN
®