Residual Current Devices
Local Indication RCCB
Status indication LED
Permanent light green
Permanent light yellow
Permanent light red
Flashing yellow/red

Remote Indication

Potential-free auxiliary switch for use in control circuits, insulated from main circuit of the switch gear according to IEC/EN60664.
0.25A ohmic load / 240V AC, terminal capacity: 0.25 - 1.5 mm

Dimensions (mm)

Correct connection

3+N
(240/415V)
Electronic works within 50-264V AC !
- Disconnect load side of the switch gear, if you make a insulation test of the installation!
2
3-phase load without N
(240V AC AC Phase-Phase)
Chapter 2.2.1. – 5
red / yellow / green
Normal operation
The measured residual current is bigger than 30% of the nominal trip-
ping value.
The measured residual current is bigger than 50% of the nominal trip-
ping value.
Check the device with test key. If the LEDs are still flashing check the
direction of connection (supply side / load side).
.
3-phase load without N
(415V AC Phase-Phase)
1+N (240V)
EATON CORPORATION xxxxx+xxxx-xxxxEN