GDS Corp GASMAX CX Operation And Maintenance Manual

GDS Corp GASMAX CX Operation And Maintenance Manual

Gasmax cx gas monitor with gds-ir infrared sensor for combustibles and carbon dioxide

Advertisement

Quick Links

 
 
Operation and Maintenance
Manual
GASMAX CX + GDS-IR
GASMAX CX Gas Monitor with GDS-IR Infrared Sensor for
Combustibles and Carbon Dioxide
GDS Corp.
1245 Butler Road
League City, TX
77573
409-927-2980
409-927-4180 (Fax)
ww.gdscorp.com
 

Advertisement

Table of Contents
loading

Summary of Contents for GDS Corp GASMAX CX

  • Page 1     Operation and Maintenance Manual GASMAX CX + GDS-IR GASMAX CX Gas Monitor with GDS-IR Infrared Sensor for Combustibles and Carbon Dioxide GDS Corp. 1245 Butler Road League City, TX 77573 409-927-2980 409-927-4180 (Fax) ww.gdscorp.com  ...
  • Page 2 GASMAX CX + GDS-IR Operation & Maintenance Manual, Revision 1.0   CAUTION: FOR SAFETY REASONS THIS EQUIPMENT MUST BE OPERATED AND SERVICED BY QUALIFIED PERSONNEL ONLY. READ AND UNDERSTAND INSTRUCTION MANUAL COMPLETELY BEFORE OPERATING OR SERVICING. ATTENTION: POUR DES RAISONS DE SÉCURITÉ, CET ÉQUIPEMENT DOIT ÊTRE UTILISÉ, ENTRETENU ET RÉPARÉ...
  • Page 3: Table Of Contents

    GASMAX CX + GDS-IR Operation & Maintenance Manual, Revision 1.0   CONTENTS  SAFETY INFORMATION  _______________________________________________  5     OVERVIEW _________________________________________________________  6     INSTALLATION ______________________________________________________  7     INITIAL STARTUP ___________________________________________________  12     CALIBRATION ______________________________________________________  16     MAINTENANCE  _ ____________________________________________________  19     TROUBLESHOOTING_________________________________________________  21  ...
  • Page 4 GASMAX CX + GDS-IR Operation & Maintenance Manual, Revision 1.0  TABLE OF FIGURES    FIGURE 2‐1: GASMAX CX + GDS‐IR LOCAL SENSOR .................. 6   FIGURE 2‐2: GASMAX CX + GDS‐IR REMOTE SENSOR  .................. 6   FIGURE 3‐1: GASMAX CX I/O POWER & SIGNAL WIRING ................ 8   FIGURE 3‐2: GASMAX CX ETHERNET INTERFACE  .................... 9   FIGURE 3‐3 GASMAX CX OPTIONAL RELAY / MODBUS INTERFACE  .............. 9   FIGURE 3‐4: GASMAX CX + GDS‐IR LOCAL SENSOR WIRING DIAGRAM  ............ 10   FIGURE 3‐5: GASMAX CX + GDS‐IR REMOTE SENSOR WIRING DIAGRAM ............ 10   FIGURE 3‐6: MODBUS WIRING JUNCTION BOX  .................... 11   FIGURE 3‐7: MODBUS JBOX LOCATION OPTIONS .................. 11  ...
  • Page 5: Safety Information

    GASMAX CX + GDS-IR Operation & Maintenance Manual, Revision 1.0   1 SAFETY INFORMATION  Important – Read Before Installation  Users should have a detailed understanding of GASMAX CX operating and maintenance instructions.  Use  the GASMAX CX only as specified in this manual or detection of gases and the resulting protection  provided may be impaired.  Read the following WARNINGS prior to use.  WARNINGS   CAUTION: KEEP EXPLOSION PROOF COVER TIGHT WHILE CIRCUITS ARE ALIVE    MISE EN GARDE : GARDER EXPLOSION COUVERTURE PREUVE TIGHT CIRCUITS PENDANT QUE SONT  ALIVE   Unit must be installed, operated and maintained in accordance with information contained herein.  Installation in any hazardous area must comply with all applicable restrictions, requirements and  guidelines for said hazardous areas. It is the end user customer’s final decision to ensure that the  GASMAX CX is suitable for the intended use.    The GASMAX CX + GDS‐IR is designed and constructed to measure the level of certain gases in  ambient air. Accuracy in atmospheres containing steam or inert gases cannot be guaranteed.   The GDS‐IR infrared sensor may be mounted vertically or horizontally. Do not mount the GDS‐IR  upside down. If using the GDS Rain Shield [IRRS], the sensor must be mounted horizontally.    Do not paint transmitter or sensor assembly.    Do not operate the GASMAX CX + GDS‐IR if the enclosure is damaged or cracked or has missing  components. Make sure the cover, internal PCB’s and field wiring are securely in place before ...
  • Page 6: Overview

    GASMAX CX + GDS-IR Operation & Maintenance Manual, Revision 1.0 2 OVERVIEW  The GASMAX CX is a next‐generation single or dual channel fixed‐point gas monitor designed to provide  continuous monitoring of toxic or combustible gases in hazardous areas.  Gas values are displayed in  calibrated engineering units on a highly visible color LCD display. The GDS‐IR is a high performance gas  sensor that uses infrared technology to detect the presence of combustible hydrocarbon gases.    The GASMAX CX + GDS‐IR combination is available in both Local Sensor and Remote Sensor configurations  as shown below:  GASMAX CX  GDS‐IR Rain Shield   Gas Monitor   Vertical  Configuration   Local GDS‐IR Horizontal  Infrared Sensor   Configuration    Figure 2-1: GASMAX CX + GDS-IR Local Sensor   Remote GDS‐IR  Infrared Sensor  GASMAX CX ...
  • Page 7: Installation

    GASMAX CX + GDS-IR Operation & Maintenance Manual, Revision 1.0   3 INSTALLATION       SELECTING A LOCATION Factors such as prevailing winds, target gas density, potential leak sources, air movement machinery and  similar environmental variables are important when selecting a location for the GASMAX CX + GDS‐IR gas  monitor or gas sensor.  Even though the GASMAX CX + GDS‐IR is designed for rugged service, sensors and  electronics should be protected from environmental damage due to water, snow, shock, vibration and  dirt. In addition, the sensor and / or display should be located such that regular maintenance and periodic  sensor replacement can be readily accomplished.  While there are no industry standards for gas detector  placement, professional tools exist that can simulate leaks or spills and provide excellent guidance for  locating gas detectors throughout a facility.   INSTALLATION  GASMAX CX monitors with GDS‐IR sensors are certified for use in Class 1 Division 1 hazardous areas.   Installation in these areas should follow best industry standard practices and all appropriate electrical  codes. Generally, these codes require rigid metal conduit, poured seals and other installation elements  necessary to ensure safety.  12” MIN   12” MIN  When installing the GASMAX CX + GDS‐IR, leave a minimum  of 12 inches of clearance below the sensor for vertical  configurations and 12” below and 12” to the right of  horizontal configurations to allow for gas flow and removal  of the stainless steel barrel for maintenance and cleaning.   12” MIN     For maximum protection against RF interference or electrical surge, the GASMAX CX enclosure, all remote  sensors and interconnecting conduit must be properly grounded.   ...
  • Page 8: Figure 3-1: Gasmax Cx I/O Power & Signal Wiring

    GASMAX CX + GDS-IR Operation & Maintenance Manual, Revision 1.0 CONNECTING DC POWER & OUTPUT SIGNAL WIRING   To access the GASMAX signal and power connections, remove the cover on the GASMAX CX explosion‐ proof enclosure, loosen the 2 thumbscrews holding the display assembly and remove it. The display will  remain connected to the IO/Power Supply PCB mounted in the back of the enclosure by a short ribbon  cable.      TB1 – 1: +12‐30VDC Input  TB1 – 2: Channel 1 4‐20mA Out  TO DISPLAY TB1 – 3: Channel 2 4‐20mA Out  TB1 – 4: Power / Signal Common  Note:  Local GDS‐IR output is on Channel 2  LOCAL  SENSOR  Remote GDS‐IR output can be configured  for either channel.  CH 2  CH 1      Figure 3-1: GASMAX CX I/O Power & Signal Wiring  ...
  • Page 9: Figure 3-2: Gasmax Cx Ethernet Interface

    GASMAX CX + GDS-IR Operation & Maintenance Manual, Revision 1.0   CONNECTING ETHERNET SIGNAL WIRING  The GASMAX CX provides a standard RJ‐45 Ethernet connector on the center of the IO/Power Supply PCB.  Data can be accessed using the MODBUS/TCP data protocol or via the built‐in web page. See GASMAX CX  manual for more details.   NOTE: USER MENU CHANGES TO  NETWORK SETUP PARAMETERS  TO DISPLAY REQUIRES A DEVICE REBOOT.   S1 – Ethernet   RJ‐45 Connector  NOTE: STANDARD ETHERNET  CABLES WITH MOLDED STRAIN  RELIEF FITTINGS ARE NOT  RECOMMENDED DUE TO SPACE  LOCAL  SENSOR  CONSTRAINTS.  CH 2  CH 1    Figure 3-2: GASMAX CX Ethernet Interface   OPTIONAL RELAY / MODBUS INTERFACE  ...
  • Page 10: Figure 3-4: Gasmax Cx + Gds-Ir Local Sensor Wiring Diagram

    GASMAX CX + GDS-IR Operation & Maintenance Manual, Revision 1.0 LOCAL GDS‐IR SENSOR WIRING  A GASMAX CX with local GDS‐IR sensor is pre‐wired at the factory as shown below. The GASMAX CX  includes a sensor personality board that adapts the GDS‐IR wiring to the GASMAX CX inputs and provides  a magnetic switch that allows the user to perform the “IR Zero” function without opening the enclosure.     Sensor Personality  TO DISPLAY Black Wire – Common Ground  Board  Blue Wire – Sensor 4‐20mA Output  White Wire ‐ IR Zero Input  LOCAL  SENSOR  CH 2  CH 1  Red Wire ‐ +18 to +30VDC Input  Important – Remove DC power before connecting or  disconnecting any wiring to / from the GDS‐IR    Figure 3-4: GASMAX CX + GDS-IR Local Sensor Wiring Diagram  ...
  • Page 11: Figure 3-7: Modbus Jbox Location Options

    GASMAX CX + GDS-IR Operation & Maintenance Manual, Revision 1.0   OPTIONAL MODBUS WIRING JUNCTION BOX  MODBUS system architecture requires that the devices in any MODBUS loop be connected in a daisy‐ chain layout. This minimizes signal reflections and improves signal noise margin. A MODBUS Termination  Jumper installs a load resistor across the MODBUS signal lines and should only be set to “A” (ON) at the  last device in the string.   Cable selection for MODBUS systems is important for both signal integrity and power distribution.  MODBUS / RS‐485 transmissions use low‐voltage differential signaling to achieve reasonable data rates  over very long distances, up to 4000 feet without a repeater. For  MODBUS data signals, GDS Corp recommends 20GA to 24GA twisted  shielded cable. Daisy‐chain power distribution may require larger  “A” gauge wire since it is critical that the supply voltage for the GASMAX  “B” CX at the far end of the string not fall below 12VDC during power‐up.   Note that while the GASMAX CX has two sets of wiring terminals for  MODBUS “A” and “B” signals, daisy‐chain power wiring requires that  +24  GND   A     two wires be installed in the “+24” and “GND” terminals on the  GASMAX CX I/O Power Supply board. This can be difficult if wire sizes  are larger than #18GA. For these reasons, if MODBUS is required GDS  Corp recommends the addition of the MODBUS Wiring Junction Box  +24  GND   A     (see Fig. 5‐7). This option minimizes the need to access wiring inside  the GASMAX CX, provides individual wire landing points for incoming  and outgoing MODBUS and power wiring and shields, and makes it  easy to temporarily disconnect the GASMAX CX power or MODBUS  connections without affecting any other MODBUS device.   “A” “B”...
  • Page 12: Initial Startup

    GASMAX CX + GDS-IR Operation & Maintenance Manual, Revision 1.0 4 INITIAL STARTUP    When power is applied to the GASMAX CX, the screen will show ‘GASMAX CX” followed by one or two  Smart Sensor information screens if the sensor(s) are locally connected. Certain sensors may initially  indicate off‐scale high or low values, but should quickly return to zero within a few minutes if no target  gas is present. During this warm‐up delay period, the 4‐20mA output is held at 4.0 mA to eliminate false  alarms in any receiving devices.    GASMAX USER INTERFACE  The GASMAX CX display is shown in Figure 5‐1. There are four magnetic switches on the face of the  GASMAX CX, arranged in a quadrant around the LCD display; these are labeled NEXT, EDIT, DOWN/CAL  and UP.  To activate, or “press” a magnetic switch, swipe the magnetic wand near the switch. For the  balance of this manual, the term “press” will be used to describe activation of any key via the magnetic  wand.    Figure 4-1: Gasmax Single Channel Display   Pressing the NEXT key causes the GASMAX display to switch display screens. In single channel mode, the  display will switch between DATA and TREND. In dual channel systems, the sequence will be: DATA 1,  DATA 2, TREND 1, TREND 2, DUAL CHANNEL, followed by DATA 1.    Figure 4-2: Gasmax Dual Channel Display  ...
  • Page 13: Figure 4-3: User Menu Screen

    GASMAX CX + GDS-IR Operation & Maintenance Manual, Revision 1.0   Press the EDIT key to access the USER MENU display mode. When in user menu display mode, use UP  and DOWN to select an item, EDIT to change an item, and NEXT to exit the menu or function and return  the GASMAX CX to display mode. See Chapter 8 for more information on User Menus.     Figure 4-3: User Menu Screen NOTE: TAKE CARE WHEN CHANGING GASMAX MENU SETTINGS – INCORRECT SETTINGS COULD CAUSE  THE GASMAX TO BECOME INOPERATIVE AND MAY COMPROMISE THE SAFETY OF THE GAS DETECTION  SYSTEM. BE SURE TO UNDERSTAND WHAT TO CHANGE AND WHY BEFORE ENTERING THE USER MENU.   Press the DN/CAL key, followed by the EDIT key, to access CALIBRATION MODE. Regular calibration is  critically important to the continued safe operation of any gas detection system. See Chapter 6 for more  information on calibration.   Then press the EDIT  To access Cal  key to confirm  Mode, press the  Calibration Mode   DN/CAL key first    Figure 4-4: Accessing Cal Mode NOTE: TAKE CARE WHEN APPLYING CALIBRATION GAS TO THE GASMAX WHILE NOT IN CALIBRATION  MODE. THIS WILL CAUSE AN INCREASE IN THE 4‐20MA OUTPUT SIGNAL AND MAY RESULT IN ...
  • Page 14: Figure 4-5: Gasmax Data Display

    GASMAX CX + GDS-IR Operation & Maintenance Manual, Revision 1.0 MORE INFORMATION ON DISPLAY SCREENS  The DATA display screen shows a single channel’s information. The current value is shown in calibrated  engineering units. A horizontal bargraph tracks the current value and shows the Alarm 1 and Alarm 2  values in graphical form. The user‐programmable Engineering Units (“Eunits”) and Measurement Name  text strings are shown below the real‐time reading.   Above the LCD display, three LEDs indicate the status of the level and fault alarms. If relays are installed,  the LEDs indicate whether the relays are active. Note that if any relay is set for FAILSAFE operation, if LED  is ON the relay will be de‐energized. In dual channel mode, if either channel is in alarm the corresponding  A1 or A2 indicator LED (and relay) will be energized.   Engineering Units Value  MODBUS Communications LEDs Horizontal Bargraph  Alarm Levels  “Measurement Name”    Figure 4-5: GASMAX Data Display Two LEDs monitor the MODBUS RS‐485 transmit (TXD) and receive (RXD) buffers.  Flashing indicates sent  or received data. RXD will flash whenever a message from the MODBUS master is received and TXD will  flash when any response message is transmitted from the GASMAX.      Engineering Units  30 Minute Trend  Alarm 2 Level (RED)  Alarm 1 Level (YELLOW)    Figure 4-6: GASMAX Trend Display  ...
  • Page 15 GASMAX CX + GDS-IR Operation & Maintenance Manual, Revision 1.0   ALARM SETUP – ALARM 1, 2 AND 3  Each channel can be programmed for up to three independent alarm levels, and can be set to alarm  ABOVE the target value for BELOW the target value.  All programming is done in engineering units that  correspond to the channels ZERO and SPAN settings. Alarm processing will trigger an alarm condition  when the input exceeds the programmed value, and includes hysteresis to keep the alarm from rapidly  switching ON and OFF if the input remains close to the programmed alarm value.    NOTE: ALARM RELAYS ARE NORMALLY TRIGGERED IF EITHER CHANNEL 1 OR CHANNEL 2 ALARM  THRESHOLDS ARE EXCEEDED.    NOTE: IF THE OPTIONAL ALARM RELAYS ARE NOT INSTALLED, ALARM SETTINGS AFFECT THE OPERATION  OF THE FRONT PANEL DISPLAY ONLY. SEPARATE ALARM SETTINGS MAY NEED TO BE PROGRAMMED IN  THE 4‐20MA RECEIVING DEVICE.  ALARM OPERATION – FAULT  FAULT is typically used to indicate FAULT conditions that suggest sensor failure or “out of measurement  range” conditions.      SYSTEM SETUP   Once operational, the user should verify the following settings prior to initial calibration:  1. Local time and date: Check date value and adjust time for proper time zone.  2. Tag name or Engineering Units settings: Edit values as necessary.  3. CAL SPAN GAS value: Set to match concentration of calibration gas cylinder.  4. CAL MARKER value: Adjust desired output mA during calibration.  5. ALARM 1, ALARM 2, ALARM 3 settings: Set for desired levels. NOTE: If relays are not installed,  GASMAX CX programmable alarm levels affect operation of display color only (Sec 7‐3).   ...
  • Page 16: Calibration

    GASMAX CX + GDS-IR Operation & Maintenance Manual, Revision 1.0 5 CALIBRATION    CALIBRATION OVERVIEW  Calibration is critically important to ensure correct operation of the GASMAX CX.  The built‐in CAL MODE  function is designed to make calibration quick, easy and error free; a successful ZERO and SPAN  calibration for the GASMAX CX requires only four keystrokes.   During CAL MODE zero and span, the sensor output is disconnected and the GASMAX CX transmits a fixed  mA value, called the CAL MARKER, to notify the receiving device that a calibration is in progress. During  the following CAL PURGE DELAY time, the GASMAX CX transmits a fixed 4.0 mA signal to prevent external  alarms during calibration.    Always follow these general calibration guidelines:   Calibration accuracy is only as good as the calibration gas accuracy.  GDS Corp calibration gases are  traceable to NIST (National Institute of Standards and Technology).   Never use calibration gas that has passed its expiration date.    Check the SPAN GAS VALUE setting and make sure it matches the calibration gas value.    Always use a GDS Corp calibration cup or wrap that completely surrounds the sensor head.    Be sure to use ZERO AIR, a mixture of 21% oxygen and 79% nitrogen, as a zero reference unless you  are certain that no target gas exists in the area. Ambient gas may result in an ‘elevated zero’  condition that will cause a FAULT to occur once the ambient gas is no longer present.    Always calibrate a new sensor before depending on the device for personnel or equipment safety   Calibrate on a regular schedule. GDS Corp recommends a full calibration every 3 months, with  periodic ‘bump tests’ on a more frequent basis to ensure that the sensor has not been affected by ...
  • Page 17: Figure 5-2: Calibration Setup

    GASMAX CX + GDS-IR Operation & Maintenance Manual, Revision 1.0   CALIBRATION PROCEDURE   The GDS‐IR infrared sensor is highly stable and should not require calibration more than once every six  months under normal conditions. However, each installation is unique and GDS Corp recommends  performing a calibration upon initial startup and within 3 months.   Allow at least 30 minutes from initial power‐up for the sensor to stabilize before beginning any  calibration procedure!   Before beginning calibration, make sure you have the following items:   1. Cylinder of calibration gas with fixed flow regulator (1.0 LPM is recommended)  2. Cylinder of ‘zero air’ for zero reference and span gas purge (if needed)  3. 3’ length of flexible tubing   4. GDS‐IR calibration wrap accessory (p/n 20‐0243)      Flexible  Tubing  Regulator  Cylinder of Span Gas or  Zero Air     Figure 5-2: Calibration Setup  ...
  • Page 18: Figure 5-3: Ir Zero For Local Sensors

    GASMAX CX + GDS-IR Operation & Maintenance Manual, Revision 1.0 Local GDS‐IR Sensors are zero’d  by placing a magnetic wand  immediately next to the right  side of the explosion proof  enclosure as shown at right    Figure 5-3: IR Zero for Local Sensors     IR Zero Button    GASMAX CX  IR Zero Mag Switch  IR Zero Mag  IR Zero Button   IR Zero  Switch Mag  Remote GDS‐IR Sensors can be  Switch  zero’d from either the GASMAX CX  or remote Sensor Junction Box   ...
  • Page 19: Maintenance

    GASMAX CX + GDS-IR Operation & Maintenance Manual, Revision 1.0   6 MAINTENANCE  GASMAX CX   Normal maintenance for the GASMAX CX primarily involves periodic calibration on standard intervals. GDS  Corp recommends calibration at least every three months, or more often if temperature extremes,  vibration, the presence of incompatible gases or other environmental factors may accelerate the  deterioration of the sensor element. Calibration should also include inspections for clogged or wet sensor  heads, cracked or damaged enclosures and water incursion inside conduit or junction boxes.  GDS‐IR INFRARED SENSOR  When power is applied to the GDS‐IR, it enters a one‐minute warm‐up period.  The output current will be  0.8 mA during the warm up time period.  At the end of the warm‐up period with no faults present, the  GDS‐IR automatically enters normal operating mode and outputs 4.0 mA.  If a fault is present after warm‐ up, the detector current output will indicate a fault.    In the normal operating mode, the 4‐20 mA signal level  Sensor Output: corresponds to the detected gas concentration.  In the event  0.0 mA Unit Fault of an overrange gas release, the GDS‐IR will indicate an  0.2 mA Reference channel fault overrange condition up to approximately 23mA. Excessive  0.4 mA Analytical channel fault gas will not harm the sensor and the output will return to ...
  • Page 20: Figure 6-1: Gds-Ir Disassembly

    GASMAX CX + GDS-IR Operation & Maintenance Manual, Revision 1.0 Using the two wrenches, rotate the lower section of the optical waveguide such that it screws into  the upper section. This will eventually allow the waveguide assembly to be removed from the GDS‐IR.   5. Using a cotton swab and alcohol, clean the surfaces of the Receiver and Source as shown.   6. Reassemble the GDS‐IR   7. Perform a ‘hardware zero’ once the sensor is completely reassembled.     NOTE: IT IS NOT NECESSARY TO REMOVE POWER FROM THE GDS‐IR TO PERFORM THIS CLEANING  PROCESS.           Figure 6-1: GDS-IR Disassembly Page 20...
  • Page 21: Troubleshooting

    GASMAX CX + GDS-IR Operation & Maintenance Manual, Revision 1.0   7 TROUBLESHOOTING  GASMAX CX SHOWS FAULT INDICATION ON LOCAL SENSOR   Certain.    Toxic sensors    Sensor reading    Sensor   GASMAX CX SHOWS FAULT INDICATION ON REMOTE SENSOR   Catalytic    Sensor reading    Sensor re   RECEIVING DEVICE AND GASMAX CX DISPLAYED VALUES DON’T MATCH   Check that zero and full scale range values match between GASMAX CX and receiving device  (controller).  Use DIAGNOSTICS menu to force GASMAX CX output to 12mA (1/2 scale) and verify  appropriate half‐scale reading on controller.   Check for high impedance shorts to ground on 4‐20mA wiring.    If 4‐20mA output is off‐scale low or high and cannot be adjusted using DIAGNOSTICS mode,  IO/Power Supply board may be defective and should be replaced.   CONTROLLER MODBUS DATA INCORRECT ...
  • Page 22 GASMAX CX + GDS-IR Operation & Maintenance Manual, Revision 1.0 Note that a COLD BOOT will reset certain values to their default setting, including the MODBUS address  value. If a Smart Sensor is connected to a local sensor head, the GASMAX will reload the sensor type,  range, cal span value and other sensor –related values automatically.       Page 22...
  • Page 23: Specifications

    GASMAX CX + GDS-IR Operation & Maintenance Manual, Revision 1.0   8   SPECIFICATIONS    Model  GASMAX CX + GDS‐IR Infrared Sensor  Power Input  18‐30VDC at < 10 watts with relay board.  Display  Full color LCD with engineering units, bargraph and 30‐minute trend    Channel One  Digital input for GDS Corp 10‐98xx Smart Toxic Sensors  Input  Bridge input for GDS Corp 10‐98xx Catalytic Bead, SmartIR or PID sensors  Analog 4‐20mA input  Channel Two  GDS‐IR Infrared Sensor  Input  Accuracy  ±3% of full scale for values up to 50% LEL, ±5% for values above 50% LEL  Standard  Three‐wire 4‐20mA current source outputs with fault and overrange indication.  Output  Maximum loop resistance is 750 ohms with standard 24VDC supply  Optional  Relay / MODBUS interface with 4x 5A SPDT programmable alarm relays  Output    Temperature  Electronics ‐40°C to +60°C ...
  • Page 24: Spare Parts

    GASMAX CX + GDS-IR Operation & Maintenance Manual, Revision 1.0 9  SPARE PARTS         Electronics Nest Assembly:  10‐0387  Display Board  10‐0388  Relay / MODBUS Board  10‐0390  Power / I/O Board  20‐0195  GDS‐IR Sensor Personality Board Yellow Enclosure:  10‐0160  GASMAX Enclosure  GDS‐IR Sensor:  GDS‐IR  Part number determined by   target gas type   (Contact Factory for details)  20‐0236  Rain Shield    20‐0243  Calibration Wrap      Figure 9-1: GASMAX CX + GDS-IR Local Sensor Spare Parts  ...
  • Page 25: Drawings And Dimensions

    GASMAX CX + GDS-IR Operation & Maintenance Manual, Revision 1.0   10  DRAWINGS AND DIMENSIONS  5.25” 5.0”  12.25”   Figure 10-1 GASMAX CX + GDS-IR DIMENSIONS (Vertical)       Page 25 ...
  • Page 26: Figure 10-2 Gasmax Cx + Gds-Ir Dimensions (Horizontal)

    GASMAX CX + GDS-IR Operation & Maintenance Manual, Revision 1.0     12.25” 5.0”        Figure 10-2 GASMAX CX + GDS-IR DIMENSIONS (Horizontal) Page 26...
  • Page 28 GDS Corp. 1245 Butler Road League City, TX 77573 409-927-2980 409-927-4180 (Fax) ww.gdscorp.com  ...

This manual is also suitable for:

Gds-ir

Table of Contents