Safety Coupling Relay SR7D
User Manual
SR7D is a safety coupling relay/safety switchgear with seven safe
Correct Use
relay contacts for fast and safe shutdown of hazardous plant
components in the event of danger. It can be used in particular
for furnaces and thermal process plants.
The device can be operated as a coupling relay for connection to
safe semiconductor outputs (e.g. output of a safety PLC). Due to
the integrated self-monitoring, no feedback loop is required for
error monitoring.
The SR7D is specially designed and certified for the use on
furnaces and thermal process plants in continuous operation
according to EN 50156-1 and EN 746-2.
7 safety contacts
4 auxiliary contacts (relay); 2 solid-state auxiliary outputs
Connection of sensors for:
- temperature
- pressure
- volume flow
Control: single or dual channel
Can be used as emergency stop relay with separate
safety circuit
Feedback loop for external contactors or extension
modules
Function
The emergency stop safety switching device SR7D is
designed for safe isolation of safety circuits according to
EN 60204-1 and can be used up to SIL 3 according to IEC
61508 and safety category 4, PL e according to EN ISO
13849-1.
When the control signal is switched on or off, the safety
contacts are closed or opened by the internal logic of the
SR7D. The SR7D can also be used as a classic emer-
gency-stop relay by appropriate wiring. In this case, the
safety contacts are closed by closing the emergency stop
circuit and a proper start command. Opening the emer-
gency stop circuit immediately opens the safety contacts.
It is ensured that a single fault does not lead to a loss of
the safety function and that every fault is detected by cycli-
cal self-monitoring no later than when the system is
Installation
As per EN 60204-1, the device is intended for installation in
control cabinets with a minimum degree of protection of
IP54. It is mounted on a 35 mm mounting rail according to
EN 60715 TH35.
The load curves (see page 4) specify the maximum permis-
sible total thermal current as a function of the ambient
temperature.
Installation and commissioning of the device must be
Safety
performed only by authorized personnel and who has
Precautions
read and understood this operating instructions.
Observe the country-specific regulations when installing
the device.
The electrical connection of the device is only allowed to
be made with the device isolated.
The wiring of the device must comply with the instruc-
tions in this operating instructions, otherwise there is a
risk that the safety function will be lost.
The contact protection and the insulation of the supply
cables must be designed for the highest voltage to the
device.
Electrical
A safety transformer according to EN 61558-2-6 or a
power supply unit with electrical isolation from the mains
Connection
must be connected
Observe the instructions in the section "Tech. Data"
Use adequate protective circuit for inductive loads (e.g.
free-wheeling diode)
If the device does not function after commissioning, it
must be returned to the manufacturer unopened. Open-
ing the device will void the warranty
The auxiliary outputs 81-82, 91-92, 101-102, 101-112
and O1, O2 may not be used as safety contacts
H. ZANDER GmbH & Co. KG • Am Gut Wolf 15 • 52070 Aachen • Germany
Tel +49 241 9105010 • Fax +49 241 91050138 • info@zander-aachen.de • www.zander-aachen.de
Errors and technical changes reserved
Pwr: AC/DC 24V
Cyclical monitoring of the output contacts
LED indicators for power and status channel 1 and 2
2 start modes:
- monitored manual start
- automatic start
Short-circuit monitoring and earth fault monitoring
Up to PL e, SILCL 3, category 4
Stop category: 0
switched off and switched on again. The operating status of
the device is signalled via the semiconductor monitoring
outputs O1 and O2 (reference potential: 0V terminal).
O1: Device ready for operation, PWR (UB) applied.
O2: Both relays K1 and K2 are switched on.
Fig. 1 Block diagram SR7D
Fig. 2 Mounting / Demounting
It is not allowed to open the device, tamper with the de-
vice or bypass the safety devices.
All relevant safety regulations and standards are to be
observed.
The overall concept of the control system in which the
device is incorporated must be validated by the user.
Failure to observe the safety regulations can result in
death, serious injury and serious damage.
Note down the version of the product (see label "Ver.")
and check it prior to every commissioning of a new de-
vice. If the version has changed, the overall concept of
the control system in which the device is incorporated
must be validated again by the user.
A1:
A2 :
S11:
S10:
S12:
S13:
S14:
S21:
O1;O2:
0V:
81-82:
91-92:
101-102: Auxiliary contact
101-112: Auxiliary contact
13-14 ..
Fig. 3 Terminals
73-74:
English Translation
Power Supply
Power Supply
DC 24 V control voltage
Control line
Control line
Control line
Control line
Control line Start
Solid-state aux. outputs
Ref. potential O1/O2
Auxiliary contact
Auxiliary contact
M03
Ver. A
E61-358-00
Safety contacts 1 to 7
1

Advertisement

loading

Summary of Contents for Zander Aachen SR7D

  • Page 1 Pwr: AC/DC 24V The SR7D is specially designed and certified for the use on furnaces and thermal process plants in continuous operation according to EN 50156-1 and EN 746-2.
  • Page 2 Safety Coupling Relay SR7D User Manual Applications Depending on the application or the result of the risk assessment according to EN ISO 13849-1, the device must be wired as shown in Fig. 4 to Fig. 17. Fig. 5: Fig. 4:...
  • Page 3 Safety Coupling Relay SR7D User Manual 5. Starting the device: 6. Triggering safety function: Switch on the operating voltage. Open the emergency stop circuit by actuating the con- nected safety switch. The safety contacts open immedi- Warning: ately. If the “Automatic start” starting behaviour is set, the 7.
  • Page 4 Please be aware that it is the sole responsibility of the operator to ensure system availability. These are recommendations of the manufacturer, the evaluation of the importance of the system availability is The SR7D is a safety switchgear according to solely the responsibility of the operator. • •...
  • Page 5 Safety Coupling Relay SR7D User Manual Safety Safety characteristics according to EN ISO 13849-1 Charcteristics Load - AC-15 / DC-13 ≤ 1 A / ≤ 1 A ≤ 2A / ≤ 2A ≤ 3A / ≤ 3A Max. duration of use [Years]...