Toshiba RAV-SM564KRT-E Service Manual page 77

Hi wall type (indoor unit)
Table of Contents

Advertisement

ON-SITE SETTING AND OTHERS (Continued)
3.1.5 Setting Onboard Switches
Setting of terminating resistors is necessary for central control of custom indoor units only.
• Use SW01 to set terminating resistors.
• Set terminating resistors for the indoor unit only with the smallest refrigerant line address.
Central control device
Central control device
U1
U2
U3
U4
Refrigerant line 1
Outdoor unit
1 2 3
Indoor unit
U3 U4
1 2 3
A B
Remote controller
Line address
1
SW01 Bit 1
ON
Remarks
Bit 1 to ON.
Central control devices: Max. 10 units
U1
U2
U3
U4
Refrigerant line 2
1 2 3
Header
unit
U3 U4
1 2 3
A B
TCC-LINK adapte
(option)
Required for custom
indoor units other
than WallTyoe
Remote controller
Group operation
(Max. 8 units)
2
OFF
Factory setting
Refrigerant line 3
Refrigerant line 4
1 2 3
1 2 3
Followerunit
Follower unit
1 2 3
1 2 3
A B
Remote controller wiring
Remote controller
Remote controller
3
OFF
Factory setting
As status shipped from factory
– 77 –
Indoor/outdoor inter-unit wire (AC230V serial)
Central control system wiring
* Wiring for No.1 and 2 only
Header unit
U3 U4
1 2 3
A B
A B
Twin/Triple operation
(Example of triple)
4
OFF
(OFF at shipment from factory)
Follower
unit
1 2 3
A B

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rav-sm804krt-eRav-sm564krt-trRav-sm804krt-tr

Table of Contents