HK Instruments DPG Series Installation Instructions

HK Instruments DPG Series Installation Instructions

Differential pressure gauges & manometers

Advertisement

INTRODUCTION

Thank you for choosing an HK Instruments DPG series differential
pressure gauge. The DPG series is intended for use in commercial
environments in HVAC/R applications. It is designed to detect air
and non-corrosive gas pressures (differential and positive) and to
provide a clear analog display of the measured values.
The DPG series includes field adjustable zero point calibration and
overpressure protection.

APPLICATIONS

DPG series devices are commonly used in HVAC/R systems for:
• fan, blower and filter monitoring
• pressure and flow monitoring

SPECIFICATIONS

• pressure monitoring in cleanrooms
SPECIFICATIONS
Performance
Accuracy:
< ± 2 % F.S (20 °C), (DPG60 < ± 4 %; DPG100 < ± 3 %)
Overpressure:
Burst pressure: 20 kPa
Copyright HK Instruments 2017
DIFFERENTIAL PRESSURE GAUGES
& MANOMETERS - DPG series
• READ THESE INSTRUCTIONS CAREFULLY BEFORE
• Failure to observe safety information and comply with
• Retain these instructions for future reference.
• This product, when installed, will be part of an engineered
Technical Specifications
Media compatibility:
Dry air or non-aggressive gases
Measuring units:
Pa
Measurement ranges:
0–60 Pa
0–100 Ps
0–120 Pa
0–200 Pa
0–250 Pa
0–300 Pa
0–400 Pa
0–500 Pa
0–600 Pa
0–800 Pa
0–1 kPa
0–1,5 kPa
0–2 kPa
0–3 kPa
0–5 kPa
Environment:
Operating temperature: -5...+60 °C
Storage temperature: -40...+85 °C
www.hkinstruments.fi

WARNING

ATTEMPTING TO INSTALL, OPERATE OR SERVICE THIS
DEVICE.
instructions can result in PERSONAL INJURY, DEATH AND/OR
PROPERTY DAMAGE.
system whose specications and performance characteristics
are not designed or controlled by HK Instruments. Review
applications and national and local codes to assure that the
installation will be functional and safe. Use only experienced and
knowledgeable technicians to install this device.
Physical
Case:
ABS
Cover:
PC
Membrane:
Silicone
Machinery:
Aluminum and steel spring
Unit mounting diameter
110 mm
Weight:
234 g
Conformance
Meets the requirements for CE marking:
RoHS Directive: 2011/96/EU
COMPANY WITH
MANAGEMENT SYSTEM
CERTIFIED BY DNV GL
= ISO 9001 = ISO 14001 =
INSTALLATION
INSTRUCTIONS
RoHS 2
2011/65/EU
Installation version 3.0 2017

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the DPG Series and is the answer not in the manual?

Questions and answers

Summary of Contents for HK Instruments DPG Series

  • Page 1 DIFFERENTIAL PRESSURE GAUGES INSTALLATION INSTRUCTIONS & MANOMETERS - DPG series INTRODUCTION WARNING Thank you for choosing an HK Instruments DPG series differential • READ THESE INSTRUCTIONS CAREFULLY BEFORE pressure gauge. The DPG series is intended for use in commercial ATTEMPTING TO INSTALL, OPERATE OR SERVICE THIS environments in HVAC/R applications. It is designed to detect air DEVICE. and non-corrosive gas pressures (differential and positive) and to • Failure to observe safety information and comply with...
  • Page 2 1) Mount the device in the desired location. 106.5 Figure 1 - Mounting 93.5 120.0 DPG600 P.max.100 kPa Made in Finland DPG600 P.max.100 kPa Made in Finland ZERO SET ZERO SET Surface mount 60.0 Flush mount 2) Adjust the zero point by turning the zero set screw on top of the lid. 3) Connect the pressure tubes. Connect positive pressure to port labeled "+" and negative pressure to port "-". Copyright HK Instruments 2017 www.hkinstruments.fi Installation version 3.0 2017...
  • Page 3 Under no circumstance is the seller liable for damages compensation for indirect damage. Copyright HK Instruments 2017 www.hkinstruments.fi Installation version 3.0 2017...

This manual is also suitable for:

Dpg60Dpg100Dpg120Dpg200Dpg250Dpg300 ... Show all

Table of Contents