Maintenance - Honeywell miniplus FK06 Installation Instructions Manual

Filter combination
Hide thumbs Also See for miniplus FK06:
Table of Contents

Advertisement

Available languages

Available languages

6.2 Assembly instructions
• CAUTION!
When using soldering connections, do not
solder the connections together with the fil-
ter combination!
High temperature will irreparably damage
important internal working components!
1. Throughly flush pipework.
2. Install filter combination.
• Install in horizontal pipework with filter bowl di-
rected downwards
• Note flow direction (indicated by arrow, fig. 1)
• Install without tension or bending stresses
• Provide a straight section of pipework of at least
five times the nominal valve size after the filter
combination
3. Setting outlet pressure (☞ chapter 7).
6.3 Drain for rinse water (fig. 1)
• The rinse water must be piped to the drain
i
in such a way that no back pressure can oc-
cur.
• Discharge into existing floor drainage
• Discharge into floor drain/container
Nominal size
Reverse rinsing quantity** C (mm)
3/4" - 1 1/4"
25 litres
** at 4,0 bar inlet pressure and a rinse duration of 15 seconds
7. Commissioning
7.1 Setting outlet pressure (fig. 2)
• Admission pressure should be approx. 1 bar
i
higher than the outlet pressure that has
been set
1. Close shut off valves on inlet.
2. Release pressure on outlet side (e.g. through water
tap).
3. Loosen slotted screw.
Do not remove slotted screw.
4. Slacken tension in compression spring.
Turn adjuster knob to the left (-).
5. Close shut off valves on outlet.
6. Slowly open shut off valves on inlet.
7. Setting outlet pressure.
Turn adjuster knob until the adjustment scale
shows the desired value.
8. Retighten slotted screw.
9. Slowly open shut off valves on outlet.
10. Filter combination is now ready for use.
MU1H-1126GE23 R1004
GB

8. Maintenance

• WARNING!
In accordance with DIN 1988, part 8, the following mea-
sures must be taken:
8.1 Rinse
• Frequency: at least every two month (de-
i
• To be carried out by an installation company
• To be carried out by the operator
• Filtered water can be drawn during rinsing.
i
8.1.1 Rinsing (fig. 3)
If rinsing is into a container, then a suitable container
must first be put underneath.
1. Open the ball valve by turning the rinse knob.
Rinse knob must be vertical.
2. Rinsing will be started.
3. Close the ball valve after approximately 15 se-
conds..
• A longer reverse rinse period may be neces-
i
20
8.2 Inspection
• Frequency: once annually
i
• To be carried out by an installation company
• To be carried out by the operator
1. Close shut off valves on outlet.
2. Check outlet pressure with a manometer when no
flow is occurring.
• CAUTION!
3. Slowly open shut off valves on outlet.
8
We recommend a planned maintenance
contract with an installation company
pending on local operating conditions)
sary if the filter is very dirty (Replace filter
mesh ☞ Maintenance)
If pressure slowly rises ☞ Maintenance!
Honeywell GmbH

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Miniplus fk06-aam

Table of Contents