Pipe Installation; Selecting The Pipe Material; Pipe Requirement; Flare Connection (Pipe Connection) - Fujitsu Airstage ARUM24TLAV2 Installation Manual

Indoor unit
Hide thumbs Also See for Airstage ARUM24TLAV2:
Table of Contents

Advertisement

3.3.5. Fresh air intake
(Processing before use)
(1) When taking in fresh air, cut a slit
shaped cabinet in the left side of
the outer case with nippers.
When removing the cabinet (iron plate), be careful not to damage the indoor unit inter-
nal parts and surrounding area (outer case).
When processing the cabinet (iron plate), be careful not to injure yourself with burrs, etc.
(2) Install the round flange (optional
parts) to the fresh air intake.
(3) Connect the duct to the round
flange.
(4) Seal with a band and vinyl tape, etc. so
that air does not leak from the connection.

4. PIPE INSTALLATION

Be more careful that foreign matter (oil, water, etc.) does not enter the piping than with
refrigerant R410A models. Also, when storing the piping, securely seal the openings by
pinching, taping, etc.
While welding the pipes, be sure to blow dry nitrogen gas through them.

4.1. Selecting the pipe material

Do not use existing pipes from another refrigeration system or refrigerant.
Use pipes that have clean external and internal sides without any contamination which
may cause trouble during use, such as sulfur, oxide, dust, cutting waste, oil, or water.
It is necessary to use seamless copper pipes.
Material: Phosphor deoxidized seamless copper pipes
It is desirable that the amount of residual oil is less than 0.004 oz /100 ft (40 mg /10 m).
Do not use copper pipes that have a collapsed, deformed, or discolored portion (es-
pecially on the interior surface). Otherwise, the expansion valve or capillary tube may
become blocked with contaminants.
Improper pipe selection will degrade performance. As an air conditioner using R410A
incurs pressure higher than when using conventional (R22) refrigerant, it is necessary to
choose adequate materials.
• Thicknesses of copper pipes used with R410A are as shown in the table.
• Never use copper pipes thinner than those indicated in the table even if they are avail-
able on the market.
Thicknesses of
Pipe outside diameter [in (mm)]
Annealed Copper
Pipes (R410A)
En-5
Cut
Cut
Cabinet (Iron plate)
Round hole
CAUTION
Round duct
Duct
CAUTION
CAUTION
Thickness [in (mm)]
1/4 (6.35)
0.032 (0.80)
3/8 (9.52)
0.032 (0.80)
1/2 (12.70)
0.032 (0.80)
5/8 (15.88)
0.039 (1.00)
3/4 (19.05)
0.039 (1.20)

4.2. Pipe requirement

Refer to the Installation Manual of the outdoor unit for description of the length of con-
necting pipe or for difference of its elevation.
• Use pipe with water-resistant heat insulation.
Install heat insulation around both the gas and liquid pipes. Failure to do so may cause
water leaks.
Use heat insulation with heat resistance above 248°F (120°C). (Reverse cycle model
only)
In addition, if the humidity level at the installation location of the refrigerant piping is
expected to exceed 70 %, install heat insulation around the refrigerant piping. If the
expected humidity level is 70 to 80 %, use heat insulation that is 9/16 in (15 mm) or
thicker and if the expected humidity exceeds 80 %, use heat insulation that is 13/16 in
(20 mm) or thicker. If heat insulation is used that is not as thick as specified, condensa-
tion may form on the surface of the insulation. In addition, use heat insulation with heat
conductivity of 0.045 W/(m·K) or less (at 68°F (20°C)).

4.3. Flare connection (pipe connection)

Tighten the flare nuts with a torque wrench using the specified tightening method. Other-
wise, the flare nuts could break after a prolonged period, causing refrigerant to leak and
generate hazardous gas if the refrigerant comes into contact with a flame.
4.3.1. Flaring
• Use special flare tool exclusive for R410A.
(1) Cut the connection pipe to the necessary length with a pipe cutter.
(2) Hold the pipe downward so that cuttings will not enter the pipe and remove any burrs.
(3) Insert the flare nut (always use the flare nut attached to the indoor and outdoor units
(or RB unit) respectively) onto the pipe and perform the flare processing with a flare
tool. Use the special R410A flare tool. Leakage of refrigerant may result if other flare
nuts are used.
(4) Protect the pipes by pinching them or with tape to prevent dust, dirt, or water from
entering the pipes.
Die
Pipe
Pipe outside diameter
[in (mm)]
1/4 (6.35)
3/8 (9.52)
1/2 (12.70)
5/8 (15.88)
3/4 (19.05)
When using conventional (R22) flare tools to flare R410A pipes, the dimension A should
be approximately 0.02 in (0.5 mm) more than indicated in the table (for flaring with R410A
flare tools) to achieve the specified flaring. Use a thickness gauge to measure the dimen-
sion A. It is recommended that a R410A flaring tool is used.
Width
Pipe outside diameter
across flats
[in (mm)]
1/4 (6.35)
3/8 (9.52)
1/2 (12.70)
5/8 (15.88)
3/4 (19.05)
4.3.2. Bending pipes
• If pipes are shaped by hand, be careful not to collapse them.
• Do not bend the pipes in an angle more than 90°.
• When pipes are repeatedly bend or stretched, the material will harden, making it difficult
to bend or stretch them anymore.
• Do not bend or stretch the pipes more than 3 times.
To prevent breaking of the pipe, avoid sharp bends.
If the pipe is bent repeatedly at the same place, it will break.
CAUTION
CAUTION
WARNING
Check if [L] is flared uniformly and
is not cracked or scratched.
Dimension A
[in (mm)]
Dimension B
[in (mm)]
Flare tool for R410A,
clutch type
3/8 (9.1)
1/2 (13.2)
0 to 0.020 (0 to 0.5)
5/8 (16.6)
3/4 (19.7)
15/16 (24.0)
Width across flats of Flare nut
[in (mm)]
11/16 (17)
7/8 (22)
1 (26)
1-1/8 (29)
1-7/16 (36)
CAUTION
0 (0)
-0.015 (-0.4)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Airstage arum30tlav2Airstage arum36tlav2

Table of Contents