7. FIELD SETTING

There are 3 methods for address setting by FIELD SETTING as follows.
Set by either of the methods.
Each setting method is described (1) to (3) below.
(1) IU AD, REF AD SW settings: This section (7.1. Setting the address)
(2) Remote controller settings:
Refer to the wired or wireless remote controller manual
for detailed setting information. (Set IU AD, REF AD
SW to 0)
(3) Automatic address settings: Refer to the outdoor unit manual for detailed setting
information. (Set IU AD, REF AD SW to 0)
Be sure to turn OFF the power before performing the field setting.
Do not operate any switches other than prescribed, as it can cause the unit to operate
improperly or malfunction.
Use an insulated screwdriver to set the DIP switches.

7.1. Setting the address

Manual address setting method
The indoor unit address and the refrigerant circuit
address can also be set up through the wireless
remote controller.
CAUTION
Use an insulated screwdriver to set the DIP
switches.
Setting
Indoor unit address
• Rotary switch [IU AD × 1]
(Factory setting "0")
• Rotary switch [IU AD × 10]
(Factory setting "0")
When connecting multiple indoor units to 1
refrigerant system, set the address at IU AD SW
as shown in the Table A.
Refrigerant circuit address
• Rotary switch [REF AD × 1]
(Factory setting "0")
• Rotary switch [REF AD × 10]
(Factory setting "0")
In the case of multiple refrigerant systems, set
REF AD SW as shown in the Table A for each
refrigerant system.
Set to the same refrigerant circuit address as the
outdoor unit.
• If working in an environ-
Table A
ment where the wireless
remote controller can be
Address
used, the addresses can
also be set using the
Refrigerant
remote controller.
circuit
• If setting the addresses
0
using the wireless
remote controller, set
1
the indoor unit address
2
and refrigerant circuit
address to "00".
3
(For information on set-
4
ting using the wireless
remote controller.)
5
* Do not set the indoor
10
unit address (IU AD
SW) at 64 to 99.
11
It may result in failure.
99
CAUTION
For indoor
For refrigerant
unit address
circuit address
IU AD
REF AD
×10
×1
×10
×1
SET3
SET4
Setting
Type of switch
range
Setting example "2"
0 to 63
IU AD × 10
IU AD × 1
Setting example "63"
0 to 99
REF AD × 10 REF AD × 1
Rotary switch
Rotary switch
Address
setting
setting
REF AD SW
IU AD SW
Indoor unit
× 10
× 1
× 10
0
0
0
0
0
1
1
0
0
2
2
0
0
3
3
0
0
4
4
0
0
5
5
0
1
0
10
1
1
1
11
1
9
9
63
6

7.2. Custom code setting

Selecting the custom code prevents the indoor unit mix-up.
(Up to 4 codes can be set.)
Perform the setting for both the indoor unit and the remote controller.
Indoor
unit
Remote
controller
Custom code setting for indoor unit
Set the DIP switch SET 3 SW1, SW2 referring to the Table B.
Dip switch "SET 3"
ON
OFF
Table B
DIP switch SET3 SW1
DIP switch SET3 SW2
RC AD

7.3. Static pressure mode

If the applicable static pressure does not match the static pressure mode, the static
pressure mode may be changed to another mode manually.
Recommended range of external static pressure
ARUM24: 0 and 0.56 in WG (0 and 140 Pa)
ARUM30: 0 and 0.44 in WG (0 and 110 Pa)
It is necessary to set up a static pressure mode for each usage of static pressure.
Static pressure can be set at site.
Relation between set values and static pressure are as the following table.
• FUNCTION SETTING can be performed with the wired or wireless remote controller.
(The remote controller is optional equipment)
• Refer to the wired or wireless remote controller manual for detailed setting information.
Function
Setting Number
Number
00
SP mode 00
01
SP mode 01
02
SP mode 02
03
SP mode 03
04
SP mode 04
05
SP mode 05
06
SP mode 06
07
SP mode 07
08
SP mode 08
09
SP mode 09
26
10
SP mode 10
11
SP mode 11
× 1
12
SP mode 12
0
1
13
SP mode 13
2
14
SP mode 14
3
Normal SP
31
4
(Factory setting)
5
* Please refer to FAN PERFORMANCE CURVE within Design & Technical Data for the
features of each setting.
0
1
3
Code change
Confusion
IU AD
REF AD
×10
×1
×10
SET3
SET4
Custom code
A (Factory setting)
B
OFF
ON
OFF
OFF
CAUTION
ARUM36: 0 and 0.36 in WG (0 and 90 Pa)
Setting Static Pressure
ARUM24
ARUM30
0 in WG (0 Pa)
0.04 in WG (10 Pa)
0.08 in WG (20 Pa)
0.12 in WG (30 Pa)
0.16 in WG (40 Pa)
0.20 in WG (50 Pa)
0.24 in WG (60 Pa)
0.28 in WG (70 Pa)
0.32 in WG (80 Pa)
0.36 in WG (90 Pa)
0.40 in WG (100 Pa)
0.44 in WG (110 Pa)
0.48 in WG
(120 Pa)
0.52 in WG
(0.44 in WG
(130 Pa)
(110 Pa))
0.56 in WG
(140 Pa)
0.16 in WG (40 Pa)
RC AD
×1
C
D
OFF
ON
ON
ON
ARUM36
(0.36 in WG
(90 Pa))
En-12