Installation and operating instructions, ATS021
5.4.2 Selector for setting delay times Ts and Tbs
The delay times can be set by means of rotary switch Ts, see Figure 5.1/12 on the front panel.
The time settings possible are:
Time delays
Description
Opening delay of main line CB1 after detection of a fault in
the mains (Generator is not in use)
TS Delay
Generator start delay after detection of a fault in the mains
(Generator in use).
Opening delay of emergency line CB2 after detection of
TBS Delay
power restored on main line.
Table 5.6:
Description of ATS021 delay time
Two different sections are available:
• section Tbs=Ts: select time Ts by turning the rotary switch to one of the possible positions. ATS021
uses a time Tbs equal to time Ts selected.
The possible selections are 0s, 10s, 20s, 30s.
• section Tbs=300s: select time Ts by turning the rotary switch to one of the possible positions. ATS021
uses a fixed time Tbs of 300sec.
The possible selections for Ts are 0s, 10s, 20s, 30s.
Figure 5.3:
Description of Ts rotary selector
2
5.
Ts
Tbs=300s
0s 10
30
20
20
10
30
0 s
Tbs=Ts
18
Using the automatic transfer switch
Value
0...30s
0...30s or Fixed
300s