166 Resulting heating
curve
en
167 Outside temp. for
frost protection for
the plant
168 Flow temp. setpoint
for frost protection
for the plant
169 Device number
170 Segment number
171 Flow alarm
172 Operating mode
when terminals H1–
M are linked
Building Technologies
Display function
2.0 °C
(--.- / 0...25)
...................
15 °C
(0...140)
...................
0
(0...16)
.........................
0
(0...14)
.........................
--:-- h
(--:-- / 1:00...10:00)
......................
0
(0...9)
.........................
74 319 0618 0 a
Setpoint incl. setting knob position
and setting on operating line 72
Left: Flow setpoint at 15 °C out-
side temperature
Right: Flow setpoint at –5 °C
outside temperature
Setting --.- = no frost protection for
the plant
°C
°C
Data bus address (LPB)
0 = device with no bus
Data bus address (LPB)
Period of time during which the
flow / boiler temperature (sensor
h
at terminal B1) may stay outside
the limit values
--.-- = function deactivated
Space heating mode
PROTECTION OFF
0 =
1 =
AUTO
2 =
REDUCED
3 =
NORMAL
PROTECTION ON
4 =
5 =
AUTO
6 =
REDUCED
7 =
NORMAL
8 =
AUTO
9 =
NORMAL
17.04.2008
D.h.w.
OFF
OFF
OFF
ON
ON
ON
ON,
24 h / day
ON,
24 h / day
58/276