ETC Setup Guide
Rack-mount Repeater
6:
Pull a single ESD ground wire from the ground bar on the DRd or ERn enclosure if LinkConnect wiring
is not installed in grounded metal conduit. ESD ground wires terminate to the ground bus located on
the rear panel.
From Repeater to Architectural Controls
1:
Pull Belden 8471 (or approved equal) control wiring to the rear panel.
2:
Strip 4.8 mm (3/16") of insulation from the ends of each wire pair.
3:
Remove the 12-position connector (labeled LON) from the rear panel of the Rack-mount Repeater.
4:
Loosen the terminal screws for the wire pairs you are terminating.
5:
Insert each white (typical) wire from the pairs into a "A" terminal on the connector and tighten the
screw(s) firmly to secure the wire into the terminal.
6:
Insert each black (typical) wire from the pairs into a "B" terminal on the connector and tighten the
screw(s) firmly to secure the wire into the terminal.
7:
Replace the connector to the rear panel.
8:
For each LinkConnect control run not installed in grounded metal conduit, terminate an ESD ground
wire (14 AWG (2.5 mm
Terminate Auxiliary Power
Auxiliary power is required when you are installing powered Paradigm architectural controls.
1:
Pull auxiliary control power wiring (typically a red/black wire pair) to the Rack-mount Repeater.
2:
Strip 4.8 mm (3/16") of insulation from the ends of each wire pair.
3:
Remove the auxiliary power connector from the rear panel.
4:
Loosen the terminal screws for the auxiliary wire pairs you are terminating.
5:
Insert the black (typical) auxiliary power wire from the pair into a "-" terminal on the connector and
tighten the screw(s) to secure the wire into the terminal.
6:
Insert the red (typical) auxiliary power wire from the pair into a "+" terminal on the connectors and
tighten the screw(s) to secure the wire into the terminal.
7:
Replace the connector to the rear panel.
Final Installation
1:
Connect the provided power cord to the IEC receptacle and supply power to the unit.
2:
Check status indicators for faults.
Rack-mount Repeater
B
A
B
A
B
A
B
A
B
A
B
1
2
2
) to the ground bus bar located on the rear panel.
-
+
-
+
-
+
-
+
-
+
The LON connector is labeled to indicate that the connector
is split between two LON segments (1 and 2). This is
important only when installing the Dual Station Repeater
(P-DREP) and two separate control segments are required. A
single Station Repeater (P-REP) installation can utilize all
available positions as LinkConnect home runs which
A
connect to a single control segment.
The auxiliary power connector (labeled Aux Power) provides
termination for up to 20 wires in the 10-position pluggable
connector. Each terminal allows up to two 16 AWG wires.
Page 3 of 4