AMX ENV-VST-C Operation/Reference Manual page 32

Color communicating thermostat
Hide thumbs Also See for ENV-VST-C:
Table of Contents

Advertisement

Programming
AxLink Channels (Cont.)
Channel
149
150
151
152-208
209
210
211
212
213
214
215
216
217-218
219
220
221
222
223
224
225
226
26
Type
Function
CMD
Decrement Humidify Set
Point
CMD
Increment Dehumidify Set
Point
CMD
Decrement Dehumidify Set
Point
Not Used
CMD
Fan Speed Low
CMD
Fan Speed Medium
CMD
Fan Speed High
CMD/FDBK Lock Out State
Not Used
CMD
Fan State On
CMD
Fan State Auto
FDBK
Fan Status
Not Used
CMD
HVAC State Auto
CMD
HVAC State Cool
CMD
HVAC State Heat
CMD
HVAC State Off
CMD
HVAC State Emergency
Heat
FDBK
HVAC Cool Status
FDBK
HVAC Heat Status
Not Used
Description
Continue to decrement the humidify set point
while the channel is active, ON, as if the
decrement button were being pushed.
Continue to increment the dehumidify set
point while the channel is active, ON, as if
the increment button were being pushed.
Continue to decrement the dehumidify set
point while the channel is active, ON, as if
the decrement button were being pushed.
Set the Fan Speed to Low when the channel
is ON.
Set the Fan Speed to Medium when the
channel is ON.
Set the Fan Speed to High when the channel
is ON.
Source ? Master: Set the Lock Out Mode
: TStat: FDBK, Lock Out Mode
Changed
Channel ON: Lock Out Mode Enabled,
Channel OFF: Lock Out Mode Disabled.
Set the Fan state to On while the channel is
ON.
Set the Fan state to Auto while the channel
is ON.
Feedback, Fan Status changed, Fan status
is controlled by the TSTAT.
Channel ON: Fan is On,
Channel OFF: Fan is Off.
Set the HVAC state to auto while the channel
is active, ON.
Set the HVAC state to cool while the channel
is active, ON.
Set the HVAC state to heat while the channel
is active, ON.
Set the HVAC state to off while the channel
is active, ON.
Set the HVAC state to Emergency Heat
while the channel is active, ON.
Feedback, HVAC Cool Status changed
Channel ON: A/C is On,
Channel OFF: A/C is Off.
Feedback, HVAC Heat Status changed
Channel ON: Heat is On,
Channel OFF: Heat is Off.