Download Print this page
olympia electronics POWER LIGHT Series Quick Start Manual

olympia electronics POWER LIGHT Series Quick Start Manual

Waterproof non maintained emergency luminaires

Advertisement

Quick Links

``POWER LIGHT`` SERIES FOR WATERPROOF NON MAINTAINED EMERGENCY LUMINAIRES
TECHNICAL CHARACTERISTICS
OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
BATTERY (Pb)
BATTERY PROTECTION
INDICATIONS - CONTROLS
CHARGING TIME
MINIMUM AUTONOMOUS DURATION
LIGHT SOURCE
EMERGENCY ILLUMINATION
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
CONSTRUCTION MATERIALS
EXTERNAL DIMENSIONS
TYPICAL WEIGHT
GUARANTEE
GENERAL
These luminaires are used where emergency
light is needed. Each luminaire must be
permanently connected to mains power
supply. In normal operation the power and
charge indicators are ON to indicate that the
battery is charging. In case of a mains power
supply failure the power and the charge
indicators turns off and the luminaire will light
the spot lamps automatically in emergency
mode. When the mains power
restored the device turns to normal operation.
INSTALLATION
To install the luminaire follow the installation
instructions οn page 3.
OPERATION
When the device is powered from the mains,
and the battery(ies) is(are) connected, the
'power' and 'charge' indicators are ON. The
'charge'
indicator
charging operation. If it does not light,
probably, the batteries are disconnected. If it
does
not
light
connected, then contact the technician. The
power
indicator
connection to the mains. The TEST button,
has a dual use. If pressed instantlly while the
Page 1 from 3
EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3
Thank you for your trust in our products
Olympia Electronics - European manufacturer
supply is
indicates
the
battery
and
the
batteries
confirms
the
proper
(for LED MODULE Specifications see page 2)
GRL-21/H/90/WP
220-240V AC/50-60Hz
13.3W/14VA
12V/7Ah
From overcharge and deep discharge
Power indicator, battery charge indicator, TEST button
90 min
White power LEDs
Aluminum, ABS/PC, PC
307 x 100 x 350 mm.
4250gr.
3 years (1 year for the battery)
device is connected to the mains, the device
simulates the power interruption, by lighting
the lamps for 3''. In that way, we can control
the driver circuit of the lamps and the lamps as
indicated in paragraph 3 in the text below.
DIMMING OPTION
When the luminaire is in emergency mode, with
corresponding pressings of the button, we can
choose the illumination of 100%, 50%, 33% or
turned off, either to increase the autonomy time
or not to consume the battery power
unnecessarily. This option is canceled when the
network is restored.
ΑΤΤΕΝΤΙΟΝ!!!
1. Operations for installation, maintainance or
testing must be done by authorized
personnel only.
2. The device must be connected to the
mains power supply through a fuse
dependent by the total amount of the line's
power load.
3. It is suggested to check every month the
are
indication LED for battery charging, and by
pushing instantly the TEST button to check
the emergency circuit and the lamps. If the
luminaire does not light
GRL-21/H/180/WP
2x12V/7Ah
24h
180 min
3200lm
IP65
o
5 to 40 C
Up to 95%
6440gr.
contact the
923021043_09_004

Advertisement

loading

Summary of Contents for olympia electronics POWER LIGHT Series

  • Page 1 6440gr. 3 years (1 year for the battery) GUARANTEE Thank you for your trust in our products Olympia Electronics - European manufacturer GENERAL device is connected to the mains, the device These luminaires are used where emergency simulates the power interruption, by lighting light is needed.
  • Page 2 The light source contained in this luminaire shall only be replaced by the manufacturer, or his agent, or a similar qualified person. NOTE! The light source is non-user replaceable. LED CHARACTERISTICS GRL-21/H/90/WP GRL-21/H/180/WP Olympia Electronics S.A. Manufacturer Model Number 1005183 Voltage Range 17.5-20.5V...
  • Page 3 Olympia Electronics reserves the right to repair or to replace the returned goods and to or not charge the buyer depending on the reason of defection. Olympia Electronics reserves the right to charge or not the buyer the transportation cost.

This manual is also suitable for:

Grl-21/h/90/wpGrl-21/h/180/wp