Self-testing maintained emergency luminaires with white led's

Advertisement

Quick Links

SELF-TESTING MAINTAINED EMERGENCY LUMINAIRES WITH WHITE LED's
TECHNICAL CHARACTERISTICS
OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
BATTERIES (Ni-Cd)
BATTERY PROTECTION
INDICATIONS - CONTROLS
CHARGING TIME
MINIMUM AUTONOMOUS DURATION
ILLUMINATION SOURCE
ILLUMINATION (MAINS / EMERGENCY)
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
CONSTRUCTION MATERIALS
EXTERNAL DIMENSIONS
TYPICAL WEIGHT
GUARANTEE
Thank you for purchasing this product of
Olympia Electronics. A European manufacturer.
GENERAL
These luminaires are used indoors (ta 40 C)
where emergency light is needed.
Each luminaire must be permanently connected
to mains power supply.
In normal operation the led strip lights and the
battery is charging.
In case of a mains power supply failure the
luminaire will light the led strip automatically in
emergency mode (powered by
When the mains power supply is restored the
device turns to normal operation.
INSTALLATION
To install the luminaire follow the installation
instructions on page 4.
Battery Cut-off
The luminaire enters in this operation when the
mains power supply fails and battery has lost its
energy. During this operation the luminaire
enters the idle state and battery consumption is
negligible, in order to be protected from deep
discharge.
Battery charging
The battery charging is completely controlled. In
this
case,
the
maintenance is achieved, as well as the
elongation of its duration. When the battery has
completely
charged,
maintenance current.
Manual Test
The manual test can be conducted only if the
main power supply and the battery is
connected. By pressing the test button briefly an
Page 1 from 4
GR-315/15L GR-315/30L
3.5W / 7VA
15 white LED's
105lm / 105lm
EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3
its battery).
best
possible
it
charges
with
High Quality European based Manufacturers
220-240V AC/50-60Hz
5W / 7.5VA
3.6V/1Ah
From overcharge and full discharge
Charge, lamp fault, fault indication LED, TEST button
90min
30 white LED's
210lm / 210lm
Bayblend FR3010, transparent polycarbonate
350 x 134 x 45 mm (CRV 362 x 134 x 58 mm)
630gr.
3 years (1 year for the battery)
operation test is initiated. During this test period
all indication LEDs are OFF.
Automatic test
o
This test includes all the operations that provide
the manual test and is conducted automatically
every 15 days. In order to be performed, the
main power supply and the battery should be
connected.
Automatic Autonomous Test
The Automatic autonomous Test is conducted
and
measures
operation. This test is conducted automatically
every six months. In order to be performed, the
main power supply and the battery should be
connected (the battery should be charged). If
the battery is not charged, the test is postponed
until the battery is completely charged. If during
the Automatic Autonomous Test the luminaire's
duration is lower than the named, then the
battery must be replaced.
Back Up Operation
The autonomous duration of battery during
emergency mode is at least the one that is
stated in the technical characteristics. During
emergency mode, a LED strip test is also
performed.
Resetting Errors
battery
Push the Test button for 5 seconds, to
extinguish all the indicated LED errors. Then
a
the luminaire enters regular operation mode.
Indication LED status (with connected mains
power supply).
AC Charge
On:
Οff:
GR-316/15L
3.5W / 7VA
3.6V/1.5Ah
24h
180min
15 white LED's
105lm / 105lm
IP 40
o
0 to 40 C
Up to 95%
700gr.
the
luminaire`s
Good charge current.
No battery (No charging current
923316010_09_008
GR-316/30L
5W / 8VA
3.6V/3Ah
30 white LED's
210lm / 210lm
770gr.
back
up

Advertisement

loading

Summary of Contents for olympia electronics GR-315/15L

  • Page 1 GUARANTEE 3 years (1 year for the battery) Thank you for purchasing this product of operation test is initiated. During this test period Olympia Electronics. A European manufacturer. all indication LEDs are OFF. GENERAL Automatic test This test includes all the operations that provide These luminaires are used indoors (ta 40 C) where emergency light is needed.
  • Page 2 or disconnected battery). 1. Operations for installation, maintainance or Lamp fault with L1 connected to L testing must be done by authorized personel Οn (with LED strip off): faulty LED strip (must only. be replaced). 2. The device must be connected to the mains Οn (with LED strip on): Problem in the back up power supply thru a fuse dependent by the total circuit of the LED strip (must be checked by an...
  • Page 3 Mounting methods All “Easy Light” can be mounted either surface or recess mounted in walls or suspended ceilings. For recess mounted installations, special accessories are required which can be found in the catalog and must be ordered separately. Suspended ceiling installation. On the bottom of the base plastic of the Easy light luminaire there are two H shaped cut outs.
  • Page 4 INSTALLATION INSTRUCTIONS Reflector Base plastic Diffusor Cable entry channels Cable Luminaire mounting holes support Base plastic 1 To install the luminaire you must dismantle it to 3 parts. 2 Place a flat blade screwdriver in the area Α to release the diffusor’s plastic hook.

This manual is also suitable for:

Gr-315/30lGr-316/15lGr-316/30l