MR16in PROCESSOR
Installation and Specifications:
1. General:
The MR16in processor provides a solution to the OEM system integrator for sensor monitoring and output
control. The MR16in has 16 supervised inputs and 2 form-C contact relays for load switching. In
addition, 2 digital inputs are used for cabinet tamper and power fault status monitoring. The processor
requires 12 to 24Vdc for power.
INPUTS
SIO COMMUNICATION
PORT, RS-485
POWER IN
12-24Vdc
2. Supplying Power to the MR16in:
The MR16in accepts 12 to 24Vdc for power. Locate power source as
close to the unit as possible. Connect power with minimum of 18AWG
wires.
Observe POLARITY on VIN!
Mercury Security Corporation © 2009
2355 MIRA MAR AVE. LONG BEACH, CA 90815-1755, (562)986-9105 FAX (562) 986-9205
0.25 [6.35]
TB1
I1
I1
I2
I2
TB2
I3
I3
I4
I4
TB3
I5
I5
I6
I6
TB4
I7
I7
I8
I8
TB9
CT
GND
BA
GND
J1
J2
TB10
TR+
TR-
R+
R-
GND
TB11
VIN
GND
MR16in
This device complies with part 15 of the FCC Rules.
Operation is subject to the following two conditions: (1) This
device may not cause harmful interference, and (2) this
device must accept any interference received, including
interference that may cause undesired operation.
6.00 [152.40]
5.50 [139.70]
9
1
10
2
11
3
12
4
13
5
14
6
15
7
16
8
CT
BA
J4
J9
J7
J5
J6
2W
4W
J3
J8
DOC 10107-0010
www.mercury-security.com
TB5
INPUT STATUS LEDs
I9
I9
I10
I10
TB6
I11
INPUTS
I11
I12
I12
TB7
I13
I13
I14
I14
TB8
I15
I15
I16
I16
MR-16IN
DIP SWITCHES
STATUS LEDs
S1
OUTPUTS
Ø0.16 [Ø3.96]
TB12
8 PLACES
+
VIN
12 TO 24Vdc
-
GND
REV 2.01
TB11
Page 1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MR16in and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Mercury Security MR16in

  • Page 1 Installation and Specifications: 1. General: The MR16in processor provides a solution to the OEM system integrator for sensor monitoring and output control. The MR16in has 16 supervised inputs and 2 form-C contact relays for load switching. In addition, 2 digital inputs are used for cabinet tamper and power fault status monitoring. The processor requires 12 to 24Vdc for power.
  • Page 2: Communication Wiring

    3. Communication Wiring: The MR16in communicates to an intelligent controller (EP2500 for example) via a 2-wire RS-485 interface. The interface allows multi-drop communication on a single bus of up to 4,000 feet (1,200 m). Shielded cable of 24AWG with characteristic impedance of 120 ohm is specified for the RS-485 interface.
  • Page 3: Relay Outputs

    Address 8 Address 9 Address 10 Address 11 Address 12 Address 13 Address 14 Address 15 Address 16 Address 17 Address 18 Address 19 Continued on next page. Mercury Security Corporation © 2009 MR16in DOC 10107-0010 REV 2.01 Page 3...
  • Page 4 Factory use only 2-wire/4-wire select, install in 2W position only Factory use only Factory use only Factory use only Factory use only Factory use only Factory use only Mercury Security Corporation © 2009 MR16in DOC 10107-0010 REV 2.01 Page 4...
  • Page 5: Status Leds

    Input in the active state: ON (briefly flashes OFF every 3 seconds) Input in a fault state: Rapid Flash LED K1 and K2: Illuminates when output relay RLY 1 (K1) or RLY 2 (K2) is energized. Mercury Security Corporation © 2009 MR16in DOC 10107-0010 REV 2.01...
  • Page 6: Specifications

    There are no expressed warranties other than set forth herein. Mercury Security Corporation does not make, nor intends, nor does it authorize any agent or representative to make any other warranties, or implied warranties, and expressly excludes and disclaims all implied warranties of merchantability or fitness for a particular purpose.

Table of Contents