Figure 2; Jumper Location And Numbering; Table 2; Jumper Connections - Emerson Liebert IntelliSlot IS-RELAY User Manual

Relay card
Table of Contents

Advertisement

4.0
J
UMPER
The card has five jumpers, P3 through P7, as shown in Figure 2.
Each jumper connects two pins.

Figure 2

Jumper location and numbering

FRONT OF
CARD
By default all five jumpers have shunts installed. The two pins are
shunted together to provide the functions shown in Table 2, allowing
relay commons to be tied together.
NOTE: The jumpers should be removed if there is any external volt-
age source that may intentionally or inadvertently be connected to the
relay.
Removing the shunt from any two pins breaks the connection between
the relay commons so they are not tied together.

Table 2

Jumper connections

Jumper
P6
P5
P4
P3
P7
S
ETUP
Relay
On Battery
UPS Fault
Low Battery
On Bypass
Summary Alarm
5
Jumper Setup
Jumper
P6
Jumper
P5
Jumper
P4
Jumper
P3
Jumper
P7