Emerson White Rogers SureSwitch 49P11-843 Installation Instructions Manual

Emerson White Rogers SureSwitch 49P11-843 Installation Instructions Manual

Table of Contents

Advertisement

Available languages

Available languages

FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE
INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY
AND/OR PROPERTY DAMAGE.
SureSwitch™ is an electronically-controlled relay that can be used
to replace single and two-pole contactors commonly used in air
conditioners, heat pumps and other applications. A patented switching
algorithm reduces arcing between contacts, which nearly eliminates
pitting and welding for a longer life. The switching mechanism is sealed
to prevent intrusion from insects and other debris.
SureSwitch also provides advanced features for HVAC troubleshooting
and system reliability:
• Line-Voltage Brownout Protection
• Short Cycle Protection
• Random Start Delay
• Lifetime Cycle Count
SureSwitch is similar to a 1
/
1
2
compressor terminal C is switched. The compressor terminal R is
connected by a shorting bar to line input L1, and is energized even
when a call is not present.
Installation should be done by a qualified heating and air conditioning
contractor or licensed electrician.
Do not exceed the specification ratings.
All wiring must conform to local and national electrical codes and
ordinances.
This control is a precision instrument, and should be handled carefully.
Rough handling or distorting components could cause the control to
malfunction.
Following installation or replacement, follow manufacturer's
recommended installation/service instructions to ensure proper
operation.
SureSwitch has no user serviceable parts. Replace as a unit.
CONTENTS
Description ....................................................................... 1
Precautions ....................................................................... 1
Specifications ................................................................... 2
Mounting .......................................................................... 2
Quick Reference ................................................................... 2
Operation ......................................................................... 3
Troubleshooting ............................................................... 3
Wiring Diagram .................................................................... 4
Operator: Save these instructions for future use!
pole contactor, in that only the
www.emersonclimate.com
INSTALLATION INSTRUCTIONS
WARNING
!
Failure to comply with the following warnings could result
in personal injury or property damage.
FIRE HAZARD
• Do not exceed the specified voltage.
• Replace existing control with exact model and dash
number.
• Protect the control from direct contact with water
(dripping, spraying, rain, etc.).
• If the control has been in direct contact with water,
replace the control.
• Label all wires before disconnection when servicing
controls. Wiring errors can cause improper and
dangerous operation.
• Safety route and secure wiring after installation.
SHOCK HAZARD
• Disconnect electric power before servicing.
• Ensure proper earth grounding of appliance.
• Ensure proper connection of line neutral and line hot
wires.
• Compressor output "R" is not switched and is
energized at all times.
49P11-843
Emerson SureSwitch™
DESCRIPTION
PRECAUTIONS
PART NO. 37-7295B
Replaces 37-7295A
1304

Advertisement

Table of Contents
loading

Summary of Contents for Emerson White Rogers SureSwitch 49P11-843

  • Page 1: Table Of Contents

    49P11-843 Emerson SureSwitch™ INSTALLATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE. DESCRIPTION SureSwitch™ is an electronically-controlled relay that can be used to replace single and two-pole contactors commonly used in air conditioners, heat pumps and other applications.
  • Page 2: Specifications

    SPECIFICATIONS ELECTRICAL RATINGS RECOMMENDED TERMINAL TORQUE – L1, L2, R and C Line Voltage Input ........... 240 VAC, 50/60 Hz #4 – 6 AWG ............. 45 in-lbs Full Load Amperes (FLA) ......... 40 A #8 AWG ............40 in-lbs #10 – 14 AWG ..........35 in-lbs Locked Rotor Amperes (LRA) ......
  • Page 3: Operation

    OPERATION CALL FOR COMPRESSOR OPERATION LINE-VOLTAGE BROWNOUT PROTECTION 24 VAC between the Y and C terminals will signal a call for compressor Brownout protection will de-energize the compressor and fan if line operation. The C compressor and fan outputs will be energized. Loss of voltage drops below 180 VAC for more than four seconds during a call 24 VAC between Y and C will de-energize the outputs. for compressor operation.
  • Page 4: Wiring Diagram

    3 Wire Hardstart Kit (optional) Legend: Line voltage Start Capacitor Low voltage Line voltage optional circuit Optional components Figure 4 - Typical Wiring White-Rodgers is a business of Emerson Electric Co. The Emerson logo is a www.white-rodgers.com trademark and service mark www.emersonclimate.com of Emerson Electric Co.
  • Page 5: Www.white-Rodgers.com

    49P11-843 Emerson SureSwitch™ INSTRUCTIONS D’INSTALLATION Conserver ces instructions pour une utilisation ultérieure! LIRE ET RESPECTER SOIGNEUSEMENT TOUTES LES INSTRUCTIONS AVANT L’INSTALLATION OU L’UTILISATION DE CET APPAREIL POUR PRÉVENIR LES BLESSURES ET LES DOMMAGES MATÉRIELS. DESCRIPTION SureSwitch™ est un relais de commande électronique qui peut remplacer les contacteurs mono ou bipolaires utilisés communément...
  • Page 6: Spécifications

    SPÉCIFICATIONS Paramètres électriques : COUPLE DE BORNE RECOMMANDÉ – L1, L2, R et C Tension de ligne électrique ......240 V c.a., 50/60 Hz 4 – 6 AWG ..........45 po-lb Intensité maximale (FLA) ........ 40 A 8 AWG ............40 po-lb 10 –...
  • Page 7: Opération

    OPÉRATION APPEL DE DÉMARRAGE DU COMPRESSEUR PROTECTION DE BAISSE DE TENSION DE LIGNE La protection de baisse de tension coupe le compresseur et Un signal de 24 V c.a. entre les bornes Y et C fait démarrer le compresseur. le ventilateur lorsque la tension de ligne chute sous 180 V c.a. Les sorties C du compresseur et du ventilateur sont mises sous tension.
  • Page 8: Schéma De Câblage

    Condensateur de démarrage Basse tension Circuit facultatif de tension de ligne Composantes facultatives Figure 4 – Câblage typique White-Rodgers est une entreprise d’Emerson Electric Co. Le logo d’Emerson est une marque www.white-rodgers.com de commerce et une marque de www.emersonclimate.com service d’Emerson Electric Co.
  • Page 9: Www.white-Rodgers.com

    49P11-843 Emerson SureSwitch™ INSTRUCCIONES DE INSTALACIÓN Operador: ¡Guarde estas instrucciones para uso futuro! EL NO LEER Y SEGUIR CON CUIDADO TODAS LAS INSTRUCCIONES ANTES DE INSTALAR O UTILIZAR ESTE CONTROL PODRÍA CAUSAR LESIONES PERSONALES Y/O DAÑOS MATERIALES. DESCRIPCIÓN SureSwitch™ es un relé de control electrónico que puede utilizarse para reemplazar contactores monopolares y bipolares comúnmente...
  • Page 10: Especificaciones

    ESPECIFICACIONES CARACTERÍSTICAS ELÉCTRICAS TORSIÓN DE TERMINAL RECOMENDADA – L1, L2, R y C Entrada de voltaje de línea ......240 VCA, 50/60 Hz #4 – 6 AWG ............. 45 pulg./libra Amperios carga total (FLA) ......40 A #8 AWG ............40 pulg./libra #10 –...
  • Page 11: Funcionamiento

    FUNCIONAMIENTO LLAMADA DE FUNCIONAMIENTO DEL COMPRESOR PROTECCIÓN CONTRA CAÍDA DE VOLTAJE DE LÍNEA 24 VCA entre las terminales Y y C indicarán una llamada de La protección contra caídas de voltaje desenergiza el compresor y el funcionamiento del compresor. Las salidas C del compresor y ventilador si el voltaje de línea cae por debajo de los 180 VCA durante el ventilador se energizarán.
  • Page 12: Diagramas De Conexiones Eléctricas

    Circuito opcional de voltaje de línea Componentes opcionales Figura 4 - Conexiones típicas White-Rodgers es una empresa de Emerson Electric Co. El logotipo de Emerson es una www.white-rodgers.com marca comercial y una marca de www.emersonclimate.com servicio de Emerson Electric Co.

Table of Contents