Download Print this page

Toshiba S2E21 Instruction Manual page 68

Motor protection relay
Hide thumbs Also See for S2E21:

Advertisement

TOSHIBA
7.5 Detection of the Heating Time Constant and Cooling Time Constant
CAUTION:
Detecting the heating time constant and the cooling time
constant requires three RTDs in the winding and one RTD
for measuring the ambient temperature to determine the
motor temperature rise.
care should be taken of the following points:
The relationship between the motor temperature rise and the heating time
constant is given in equation
temperature and the cooling time constant is given in equation (2).
provides a reference temperature for determining the
motor temperature rise, so make sure that you measure
the ambient temperature precisely.
The measuring error of the ambient temperature will
have great effect on the detection accuracy of the
heating time constant and the cooling time constant.
Do not allow the RTD to be affected by heat
from the motor.
Keep the RTD free from direct sun rays or
radiant heat.
Keep the RTD free from influences of cool air
and drafts.
Keep the RTD free from moisture or high humidity.
time constant and the cooling time constantare
detected under the conditions described later.
The motor must be able to be operated in ways that
meet thm_;tuirements.
To enhance the detection accuracy,