N Wiring of Main Power Supply and Equipment Capacity
Outdoor unit (3Ø, 380 ~415V, 50Hz ) Indoor unit (1Ø, 220V, 50Hz)
1. Use a separate power supply for the outdoor unit and indoor unit.
2. Bear in mind ambient conditions (ambient temperature,direct sunlight, rain water,etc.) when proceeding with the wiring and connections.
3. The wire size is the minimum value for metal conduit wiring. The power cord size should be 1 rank thicker taking into account the line volt-
age drops. Make sure the power-supply voltage does not drop more than 10%.
4. Specific wiring requirements should adhere to the wiring regulations of the region.
5. Power supply cords of parts of appliances for outdoor use should not be lighter than polychloroprene sheathed flexible cord.
6. Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately from the power supply.
WARNING
• Follow ordinance of your governmental organization for technical standard related to electrical equipment, wiring reg-
ulations and guidance of each electric power company.
• Be sure to use specified wires for connections so that no external force is imparted to terminal connections. If connec-
tions are not fixed firmly, it may cause heating or fire.
• Be sure to use the appropriate type of overcurrent protection switch. Note that generated overcurrent may include
some amount of direct current.
CAUTION
• Some installation site may require attachment of an earth leakage breaker. If no earth leakage breaker is installed, it may
cause an electric shock.
• Do not use anything other than breaker and fuse with correct capacity. Using fuse and wire or copper wire with too large
capacity may cause a malfunction of unit or fire.
Model
Hz
8HP
50
10HP
50
12HP
50
14HP
50
16HP
50
18HP
50
20HP
50
22HP
50
24HP
50
26HP
50
28HP
50
30HP
50
32HP
50
34HP
50
36HP
50
38HP
50
40HP
50
Unit
Power Supply
Volts
Voltage-range
MCA
Min.:342
380-415
20.7
Max.:456
Min.:342
380-415
26.5
Max.:456
Min.:342
380-415
27.2
Max.:456
Min.:342
380-415
30.5
Max.:456
Min.:342
380-415
41.2
Max.:456
Min.:342
380-415
47.0
Max.:456
Min.:342
380-415
52.7
Max.:456
Min.:342
380-415
53.5
Max.:456
Min.:342
380-415
54.2
Max.:456
Min.:342
380-415
67.5
Max.:456
Min.:342
380-415
73.2
Max.:456
Min.:342
380-415
79.0
Max.:456
Min.:342
380-415
79.7
Max.:456
Min.:342
380-415
80.5
Max.:456
Min.:342
380-415
81.2
Max.:456
Min.:342
380-415
84.5
Max.:456
Min.:342
380-415
87.7
Max.:456
COMP
MOP
MSC
34.1
16.5/75
44.5
16.5/75
45.8
16.5/75
51.7
16.5/75
68.0
16.5/75/75/75
78.4
16.5/75/75/75
88.7
16.5/75/75/75
90.1
16.5/75/75/75
91.4
16.5/75/75/75
112.3
16.5/75/75/75/75/75
122.6
16.5/75/75/75/75/75
133.0
16.5/75/75/75/75/75
134.3
16.5/75/75/75/75/75
135.7
16.5/75/75/75/75/75
137.0
16.5/75/75/75/75/75
142.9
16.5/75/75/75/75/75
148.7
16.5/75/75/75/75/75
Electrical Wiring
OFM
RLA
kW
14.5/12
0.56
3.97
14.5/12
0.56
3.97
14.5/12
0.56
3.97
14.5/12
0.56
3.97
14.5/12/12/12
1.1
7.71
14.5/12/12/12
1.1
7.71
14.5/12/12/12
1.1
7.71
14.5/12/12/12
1.1
7.71
14.5/12/12/12
1.1
7.71
14.5/12/12/12/12/12
1.64
11.45
14.5/12/12/12/12/12
1.64
11.45
14.5/12/12/12/12/12
1.64
11.45
14.5/12/12/12/12/12
1.64
11.45
14.5/12/12/12/12/12
1.64
11.45
14.5/12/12/12/12/12
1.64
11.45
14.5/12/12/12/12/12
1.64
11.45
14.5/12/12/12/12/12
1.64
11.45
Installation Manual 47