This symbol denotes actions that the user must carry out. RESULTS OF ACTION This symbol denotes relevant results of actions. Additional documents The following additional documents are available online at www.turck.com: Data sheet Commissioning manual IO-Link devices IO-Link parameter manuals for IO-Link devices...
CAD files in numerous export formats. The contact details of Turck subsidiaries worldwide can be found on p. [} 34]. Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
The product is designed according to state-of-the-art technology. However, residual risks still exist. Observe the following warnings and safety notices to prevent damage to persons and property. Turck accepts no liability for damage caused by failure to observe these warning and safety notices.
Functions and operating modes The I/O hubs with IO-Link of the TBIL-S series connect up to eight digital sensors or eight digital sensors and actuators with one IO-Link master port. The device provides diagnostics for power supply and short circuit of the sensors and actuators on the IO-Link master.
The FE connection of the device is connected to the reference potential of the installation via the M4 metal screw. Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Connecting NOTICE Intrusion of liquids or foreign bodies through leaking connections Loss of protection class IP65/IP67/IP69K, device damage possible Tighten connectors with a tightening torque of 0.6 Nm. Only use accessories that guarantee the protection class. Always seal unused connectors with suitable screw caps or blind caps. Connecting the supply voltage and IO-Link WARNING Incorrect or defective power supply unit...
Connect the sensors and actuators to the device according to the pin assignment. = Signal In/Out = GND = Signal In/Out = FE C0...C3 Fig. 9: Pin assignment TBIL-S4-8DXP Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
0x03 Minimum cycle time read only 0x05 IO-Link version ID read only 0x08 Vendor ID read ID for Turck: only 0x013D 0x09 0x0A Device ID read E.g: TBIL-S3-8DXP: only 0x1E2213 0x0B 0x0C IO-Link object directory – ISDU device parameters: Identification...
Page 14
Overcurrent V connector C0…C7 or C0…C3 0x51 Output Short read Overcurrent output 0…7 (81) Circuit only (only valid for TBIL-S…- 8DXP) Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 15
Invert Digital Input – 0x41 (65), sub index 0 This parameter inverts the state of the digital input in the process image. Format Length Byte 1 byte 1 bit per channel Default values are shown in bold. Value Meaning Input signal inverted TBIL-S3-8DIP TBIL-S3-8DXP Byte 0...
Page 16
C1P2 C1P4 C0P2 C0P4 NOTE This parameter can also be set for all connectors of the module via the IODD. Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 17
Impulse Stretching Input – 0x43 (67) This parameter defines the duration of the pulse stretching for digital input edges in multiples of 10 ms. This allows that even short signals with longer PLC cycle times can be detected. Format Length Array of byte 8 byte 1 byte per channel...
Page 18
C1P2 C1P4 C0P2 C0P4 NOTE This parameter can also be set for all connectors of the module via the IODD. Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 19
Failsafe – 0x45 (69), sub index 0 This parameter defines the behavior of the output in case of an interruption of the IO-Link com- munication. Format Length Array of byte 2 byte 2 bit per channel Default values are shown in bold. Value Meaning Set output to 0...
Page 20
18.5 V Byte 0 Bit offset Threshold Byte 1 Bit offset Meaning of parameter bits Name Meaning Port no. Pin no. Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Operating Process input data TBIL-S3-8DIP Byte Bit offset Inputs C7P4 C6P4 C5P4 C4P4 C3P4 C2P4 C1P4 C0P4 Module diagnostics Group Under- Over- diagnostics voltage voltage Connector diagnostics – overcurrent sensor supply Overcur- Overcur- Overcur- Overcur- Overcur- Overcur- Overcur- Overcur- rent C7 rent C6 rent C5 rent C4...
Page 22
The sensor/actuator supply is protected in groups. If an overload occurs at one slot, all diagnostic bits of a group are active. Groups: TBIL-S3-…: C0…C3, C4…C7 TBIL-S4-…: C0…C1, C2…C3 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Designation Meaning Channel diagnostics – overcurrent output Overcurrent CxPy 0 No diagnostics Cx: Port no. Py: Pin no. Overlaod at the out- put/short-circuit Process output data TBIL-S3-8DXP Byte Bit offset Outputs C7P4 C6P4 C5P4 C4P4 C3P4 C2P4 C1P4 C0P4 TBIL-S4-8DXP Byte Bit offset Outputs...
In devices with group diagnostics, all connector-LEDs of the supply group flash simultaneously in case of an error. – Output active, overload/overcurrent at output Input inactive Output inactive Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Evaluating diagnostic data Group diagnostics: Supply Error– 0x50 (80), sub index 0 The group diagnosis indicates errors in the module and sensor supply: Group diagnostics: Diagnostics pending at the module Over- or undervoltage, per module Overcurrent sensor supply V , per connector Format Length Array of Bytes...
Page 26
Over- Over- Over- Over- current current current current current current current current C3P2 C3P4 C2P2 C2P4 C1P2 C1P4 C0P2 C0P4 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
IO-Link Events Event Description Event Mode Code 0x5110 Overvoltage 0xF4 (appears) Supply voltage too high supply 0xB4 (disappears) 0x5111 Undervoltage 0xF4 (appears) Supply voltage too low supply 0xB4 (disappears) 0x7710 Overcurrent V 0xF4 (appears) Group event for Overcurrent: connector x Overcurrent of the sensor supply at 0xB4 (disappears) one of the connectors...
If there are no faults, there is a device malfunction. In this case, decommission the device and replace it with a new device of the same type. Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Observe our return acceptance conditions when returning the device to Turck. 11.1 Returning devices Returns to Turck can only be accepted if the device has been equipped with a Decontamination declaration enclosed. The decontamination declaration can be downloaded from https://www.turck.de/en/retoure-service-6079.php and must be completely filled in, and affixed securely and weather-proof to the outside of the packaging.
IP65/IP67/IP69K (not evaluated by UL) Overvoltage category Housing material PA6-GF30 Housing color Black Halogen-free Mounting 2 mounting holes, Ø 4.3 mm Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
13.2 Technical data – TBIL-S…-8DIP Technical Data Power supply Operating/load voltage 18…30 VDC Operating current < 120 mA Sensor/actuator supply V Supply connectors C0…C7 or C…C3 0.5 A per channel group, short-circuit protec- ted with diagnostics channel groups: TBIL-S3-8DIP: C0…C3, C4…C7 TBIL-S4-8DIP: C0…C1, C2…C3 Total current Max.
Load type (UL condition) Resistive, pilot duty Potential isolation Outputs to FE, 500 VDC IO-Link Minimum cycle time 2.8 ms Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Appendix: EU Declaration of Conformity EU-Konformitätserklärung Nr.: 5035-4M EU Declaration of Conformity No.: HANS TURCK GMBH & CO KG / We WITZLEBENSTR. 7, 45472 MÜLHEIM A.D. RUHR erklären in alleiniger Verantwortung, dass die Produkte declare under our sole responsibility that the products...
Turck Banner Malaysia Sdn Bhd Unit A-23A-08, Tower A, Pinnacle Petaling Jaya, Jalan Utara C, 46200 Petaling Jaya Selangor www.turckbanner.my Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 35
Mexico Turck Comercial, S. de RL de CV Blvd. Campestre No. 100, Parque Industrial SERVER, C.P. 25350 Arteaga, Coahuila www.turck.com.mx Netherlands Turck B. V. Postbus 297, NL-8000 AG Zwolle www.turck.nl Austria Turck GmbH Graumanngasse 7/A5-1, A-1150 Wien www.turck.at Poland TURCK sp.z.o.o.
Page 36
Over 30 subsidiaries and over 60 representations worldwide! 100003857 | 2021/04 100003857 www.turck.com...