TBIL-S...
Compact IO Hubs with IO-Link
Instructions for Use

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the TBIL-S Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for turck TBIL-S Series

  • Page 1 Your Global Automation Partner TBIL-S… Compact IO Hubs with IO-Link Instructions for Use...
  • Page 2 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
  • Page 3: Table Of Contents

    Table of Contents About These Instructions .......................  5 Explanation of Symbols Used .................. 5 Additional Documents .................... 5 Notes on the Product ........................ 6 Product Identification .................... 6 Scope of Delivery...................... 6 Legal Requirements .....................  6 Manufacturer and Service...................  6 For Your Safety..........................
  • Page 4 Table of Contents Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
  • Page 5: About These Instructions

    This symbol denotes actions that the user must carry out. RESULTS OF ACTION This symbol denotes relevant results of actions. Additional Documents The following additional documents are available online at www.turck.com: Data sheet Declaration of Conformity IO-Link devices commissioning manual...
  • Page 6: Notes On The Product

    For further inquiries in Germany contact the Sales and Service Team on: Sales: +49 208 4952-380 Technology: +49 208 4952-390 Outside Germany, please contact your local Turck representative. Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
  • Page 7: For Your Safety

    The product is designed according to state-of-the-art technology. However, residual risks still exist. Observe the following warnings and safety notices to prevent damage to persons and property. Turck accepts no liability for damage caused by failure to observe these warning and safety notices.
  • Page 8: Product Description

    132 [5.20] 144 [5.67] Fig. 2: Dimensions TBIL-S4-… 4.1.1 Display Elements The device has the following LED indicators: IO-Link communication I/O status Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
  • Page 9: Properties And Features

    Functions and Operating Modes The I/O hubs with IO-Link of the TBIL-S series connect up to 8 digital sensors or 8 digital sensors and actuators with one IO-Link master port. The device provides diagnostics for power supply and short circuit of the sensors and actuators on the IO-Link master.
  • Page 10: Mounting

    The FE connection of the device is connected to the reference potential of the installation via the M4 metal screw. Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
  • Page 11: Connecting

    Connecting WARNING Penetration of liquids or foreign objects through leaking connections Danger to life due to malfunction „ Fasten the M12 connectors with a tightening torque of 0.8 Nm. „ Always seal unused connectors with respective protection caps. Connecting the supply voltage and IO-Link WARNING Defective power supply unit Danger to life due to dangerous voltages on touchable parts...
  • Page 12: Connecting Digital Sensors And Actuators

    Connect the sensors and actuators to the device according to the pin assignment. 1 = V 3 = GND 4 = Signal In/Out C0…C7 Fig. 8: Pin assignment TBIL-S3-8DIP Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
  • Page 13 Connecting Digital Sensors and Actuators – TBIL-S4-… For connecting digital sensors and actuators, 5-pin M12 connectors are available. Fig. 9: TBIL-S4-…: M12 connector for connecting digital sensors and actuators „ Connect the sensors to the device according to the pin assignment. = Signal In = GND = Signal In...
  • Page 14: Parameterizing And Configuring

    0x19 Function Tag read/ Default "***" The application-spe- (25) write cific device function can be stored in this field. Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
  • Page 15 ISDU Object name Access Length Meaning/ Comment Index [Byte] default value Hex. (Dec.) 0x1A Location Tag read/ Default "***" The application-spe- (26) write cific installation loca- tion of the device can be stored in this field. IO-Link object directory – ISDU device parameters: Preferred Index (parameters and diagnostics of the digital in- and outputs) ISDU Object name...
  • Page 16 C1P2 C1P4 C0P2 C0P4 NOTE This parameter can also be set for all connectors of the module via the IODD. Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
  • Page 17 Activate Output – 0x42 (66), Sub Index 0 this parameeter activates or deactivates the output function of the digital channel. Format Length Byte 1 byte 1 bit per channel Default values are shown in bold. Value Meaning Output function deactivated, channel can only be used as input Output function activated, channel can be used as in- or output...
  • Page 18 C1P2 C1P4 C0P2 C0P4 NOTE This parameter can also be set for all connectors of the module via the IODD. Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
  • Page 19 Manual Output Reset after Overcurrent – 0x44 (68), Sub Index 0 This parameter defines if a manual reset is necessary after an overcurrent occurred at the digital channel. Format Length Byte 1 byte 1 bit per channel Default values are shown in bold. Value Meaning Automatic recovery mode...
  • Page 20 C1P2 C1P4 C0P2 C0P4 NOTE This parameter can also be set for all connectors of the module via the IODD. Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
  • Page 21 Undervoltage Diagnosis – 0x46 (70), Sub Index 0 This parameter defines threshold value for the undervoltage diagnostics. Format Length Array of Bytes 2 byte 1 bit per module Default values are shown in bold. Value Meaning Standard lower threshold: 19.2 V (IEC 61131-2) upper threshold: 20.4 V Extended...
  • Page 22: Operating

    Over- Over- Over- Over- current current current current current current current current C7P4 C6P4 C5P4 C4P4 C3P4 C2P4 C1P4 C0P4 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
  • Page 23 TBIL-S4-8DIP Byte Bit offset Inputs C3P2 C3P4 C2P2 C2P4 C1P2 C1P4 C0P2 C0P4 Module diagnostics Group Under- Over- dia- voltage voltage gnostics Connector diagnostics – overcurrent sensor supply Over- Over- Over- Over- current current current current TBIL-S4-8DXP Byte Bit offset Inputs C3P2 C3P4...
  • Page 24 TBIL-S3-…: C0…C3, C4…C7 TBIL-S4-…: C0…C1, C2…C3 Channel diagnostics – overcurrent output Overcurrent CxPy 0 No diagnostic mes- sage Overlaod at the output/short-circuit Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
  • Page 25: Process Output Data

    Process Output Data TBIL-S3-8DXP Byte Bit offset Outputs C7P4 C6P4 C5P4 C4P4 C3P4 C2P4 C1P4 C0P4 TBIL-S4-8DXP Byte Bit offset Outputs C3P2 C3P4 C2P2 C2P4 C1P2 C1P4 C0P2 C0P4 Designation Meaning CxPy Output inactive Output active LED Displays The device has the following LED indicators: IO-Link communication I/O status 8.3.1...
  • Page 26: Evaluating Diagnostic Data

    TBIL-S4-… Byte 1 Bit offset Over- Over- Over- Over- current current current current Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
  • Page 27: Io-Link Events

    Overcurrent Output – 0x51 (81), Sub Index 0 Indicates an overcurrent at the corresponding digital output. Format Length Byte 1 byte 1 bit per output 0 = no diagnostics 1 = diagnostic message TBIL-S3-8DXP Byte 0 Bit offset Over- Over- Over- Over- Over-...
  • Page 28: Io-Link Error Codes

    Parameter length underrun meter. 0x8035 Function not available Function not available in the device 0x8041 Inconsistent parameter set Inconsistent parameters Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
  • Page 29: Troubleshooting

    Troubleshooting If the device does not function as expected, first check whether ambient interference is present. If there is no ambient interference present, check the connections of the device for faults. If there are no faults, there is a device malfunction. In this case, decommission the device and replace it with a new device of the same type.
  • Page 30: Maintenance

    Disposal The devices must be disposed of correctly and must not be included in normal household garbage. Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
  • Page 31: Technical Data

    Technical Data 13.1 General Technical Data Technical Data Connectors IO-Link M12, 5-pole Input/output TBIL-S3-… M8, 3-pole TBIL-S4-… M12, 5-pole Permissible torques IO-Link 0.8 Nm I/O channels M8: 0.4 Nm M12: 0.6 Nm Mounting (M4 screws) 1.3 Nm IO-Link IO-Link specification Specified according to version 1.1 Parameterization FDT/DTM, IODD...
  • Page 32: Tbil-S

    0.010 ms Max. input current 15 mA Potential isolation Inputs to FE, 500 VDC IO-Link Minimum cycle time 2.2 ms Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
  • Page 33: Tbil-S

    13.3 TBIL-S…-8DXP Technical Data Power supply Operating/load voltage 18…30 VDC Operating current < 90 mA Sensor/actuator supply V Supply connectors C0…C7 or C…C3 0.5 A per channel group, short-circuit protec- ted with diagnostics channel groups: TBIL-S3-8DIP: C0…C3, C4…C7 TBIL-S4-8DIP: C0…C1, C2…C3 Total current max.
  • Page 34: Appendix: Declaration Of Conformity

    Ort und Datum der Ausstellung / Name, Funktion und Unterschrift des Befugten / Place and date of issue Name, function and signature of authorized person Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...